Trane A4MXA1824AC6HA Installer'S Manual Download Page 5

18-AD37D1-1-EN  

5

Installer’s Guide

H. FURNACE IN HORIZONTAL LEFT POSITION

CAUTION

!

Both the coil and furnace must be fully supported. Do not 

attempt to suspend the coil using the brackets.

1.  HORIZONTAL LEFT COIL CONVERSION: 

S-Series upflow furnaces can be horizontal left or right.  For 

legacy furnaces, the non-condensing furnaces may be laid on 

either side for horizontal application.  The condensing down-

flow/horizontal right and upflow/horizontal  left furnaces 

may only be rotated onto their left side.  Connection brackets 

for coil/furnace alignment are included with the furnaces.  
 

a. For horizontal left applications, the hairpin baffle 

must be installed.

 

1.  Remove the coil by removing the front panels and 

sliding the coil out of the coil enclosure. 

2.  Using the provided 5/16" hex head screws, install 

the hairpin baffle shipped with the coil onto the rear 

of the left coil slab as close to the coil apex as pos-

sible.  Location of the hairpin baffle with vary by coil 

model.  See Figure 9.   

3.  Slide the coil back into the enclosure and attach 

panels. 

 

a. In horizontal left, the 

A4MX 

coil case is rotated so 

the apex of the coil is away from the furnace and the 

auxiliary drain pan is now on the lower side.

 

b. The two piece baffle ships installed on the coil and is 

required for horizontal left applications.

 

c. The base of the coil enclosure is placed flush against 

the downflow/horizontal furnace. Upflow/horizontal 

condensing furnaces have the coil match the top flange.

 

d. For downflow furnaces with no duct flange, there are 

three brackets included which are used to align and 

connect the furnace and coil together . See Figure 10.  

 

e. Two brackets are used to attach the rear of the coil 

and furnace and one bracket is used to attach the front.  

The rear brackets will use existing screws on the coil 

enclosure (two on each side at the bottom).  Each of the 

rear brackets will be attached with the wide side of the 

bracket resting on the top and bottom of the horizontal 

coil and furnace (see Figure 11).  Four additional screws 

will be used to attach each rear bracket. 

 f. 

The front bracket is positioned as close to the center as 

possible with the narrow edge against the coil enclosure 

and the wide edge against the furnace .  Two screws each 

are driven into the coil enclosure and furnace.

 g. 

There is a 2 piece splash guard packaged with the 

coil for horizontal left coil installation only. First, insert 

the splash guard bracket in the drain pan channel.  The 

splash guard has a bend which is inserted into the front 

channel of the horizontal drain pan on the outlet air side 

of the coil case.  The guard is then rotated downward 

until it rests in the drain pan.  One sheet metal screw is 

driven through the coil case duct flange on the front side 

and into the splash guard side hole.  See Figure 12. 

h. Secure alignment between the furnace and coil cabi-

net using field-provided self-tapping screws (see Figure 

3). For S-series furnaces, bend furnace duct flanges out-

ward for cased coil alignment. Drill screws into furnace 

duct flange though clearance alignment holes located 
near bottom of coil cabinet. The coil and furnace must 
be fully supported when used in the horizontal position.  

These screws are strictly for securing alignment, not for 
support in horizontal.  The coil is always placed down-
stream of the furnace airflow. 

Figure 12

SPLASH GUARD BRACKET

CASED COIL SHOWN INSTALLED HORIZONTAL LEFT WITH A DOWNFLOW

FURNACE AND HORIZONTAL ALIGNMENT BRACKETS

BRACKETS SHIP WITH DOWNFLOW

NON-CONDENSING FURNACES.

REQUIRED FOR ALIGNMENT

ON SOME HORIZONTAL INSTALLATIONS.

AIRFLO

W

FURNA

CE

DUCT

SPLASH

GUARD

CASED COIL

Figure 11

Figure 10

CASED COIL CONNECTION 

BRACKET FOR DOWNFLOW 

FURNACE IN HORIZONTAL

Figure 9

Note:  Downflow legacy 
condensing furnaces can-
not be configured for HL.

Summary of Contents for A4MXA1824AC6HA

Page 1: ...oil before beginning the installation Figure 1 18 AD37D1 1 EN Cased Aluminum Convertible Coils Models A4MXA1824AC6HA A4MXB1832AC6HA A4MXA3036AC6HA A4MXB3642AC6HA A4MXC3642AC6HA A4MXB4248AC6HA A4MXC4248AC6HA A4MXD4248AC6HA A4MXC4260AC3HA A4MXD4260AC3HA NOTE OPTIONAL DOWNFLOW GASKET INSTALLATION For unusually humid applications that expect prolonged operation above 70 RH it is recommended to use the...

Page 2: ...GAS FURNACE a Apply gasket material duct seal field supplied to ALL mating surfaces between the furnace and the coil case b Set the coil case on top of the furnace Connect the duct work to the coil case using field supplied screws c Secure the coil case to the furnace and seal for air leaks as required FOR UPFLOW HORIZONTAL LEFT INSTALLATIONS Figure 3 Figure 2 Remove and Discard Replace UPFLOW FUR...

Page 3: ...A0 gasket kit to prevent water from form ing on the bottom of the drain pan and dripping into the supply ductwork a Lay the coil on its back side b Locate the 4 wide gasket material found in BAYGSKT001A0 c Attach the 4 gasket material to three sides of the bottom of the drain pan as shown Make sure to start by matching up the edge of the gasket material to the inner edge of the drain pan by the co...

Page 4: ...ay be laid on either side for horizontal application The condensing downflow horizontal right and upflow horizontal left furnaces may only be rotated onto their left side While not required optional removal of some coil components will maximize airflow efficiency a Remove the coil by sliding the coil out of the coil enclosure b Optional but recommended Remove the factory installed two piece baffle...

Page 5: ...on the coil enclosure two on each side at the bottom Each of the rear brackets will be attached with the wide side of the bracket resting on the top and bottom of the horizontal coil and furnace see Figure 11 Four additional screws will be used to attach each rear bracket f The front bracket is positioned as close to the center as possible with the narrow edge against the coil enclosure and the wi...

Page 6: ...o be replaced with the included 0 077 orifice COIL MODEL NOMINAL TONS FACTORY INSTALLED ORIFICE SIZE ADDITIONAL INCLUDED ORIFICE SIZES A4MXA1824AC6HA 2 0 057 0 052 A4MXB1832AC6HA 0 052 0 064 A4MXA3036AC6HA 2 5 0 064 0 068 A4MXB3642AC6HA 3 0 068 0 077 A4MXC3642AC6HA 0 077 A4MXB4248AC6HA 3 5 0 077 0 082 A4MXC4248AC6HA 4 0 082 0 077 A4MXD4248AC6HA 0 077 A4MXC4260AC3HA 5 TXV none A4MXD4260AC3HA none T...

Page 7: ...t coil 1 Remove both rubber plugs from the indoor coil 2 Field supplied tubing should be cut square round and free of burrs at the connecting end Clean the tubing to prevent contaminants from entering the system 3 Run the refrigerant tubing into the stub tube sockets of the indoor unit coil UNIT PANELS MUST BE SHIELDED DURING BRAZ ING 4 Flow a small amount of nitrogen through the tubing while braz...

Page 8: ...he outdoor unit M CONDENSATE DRAIN PIPING Condensate drain connections are located in the drain pan at the bottom of the coil enclosure assembly The female threadedfittingprotrudesoutsideoftheenclosureforexternal connection A field fabricated trap is not required for proper drainage due to the positive pressure of the furnace however it is recommended to prevent efficiency loss of conditioned air ...

Page 9: ...aller s Guide Outline Drawing for models A4MXA1824AC6HAA A4MXB1832AC6HAA A4MXA3036AC6HAA A4MXB3642AC6HAA A4MXC3642AC6HAA A4MX B4248AC6HAA A4MXC4248AC6HAA A4MXD4248AC6HAA A4MXC4260AC3HAA A4MXD4260AC3HAA From Dwg D346409 RevA ...

Page 10: ... NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is correct NO Before starting insure the blower wheel indoor and outdoor coils are clean Is the liquid line temperature at indoor coil within 8F of outdoor liquid line temperature YES Verify line set is s...

Page 11: ...18 AD37D1 1 EN 11 Installer s Guide ...

Page 12: ...licy of continuous product and product data improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor 06 19 ...

Reviews: