 18-AD37D1-1-EN

Installer’s Guide

Figure 7

CASED

COIL

UPFLOW

FURNACE

TOP COIL FLANGE
FITS INSIDE OF

FURNACE

TOP FLANGE FOR
HORIZONTAL RIGHT
APPLICATION

UPFLOW

Figure 6

Figure 8

Note: when installing coil onto an S-Series furnaces in 
horizontal right  or downflow configuration, bend the 
flanges downward for a flush fit.

UPFLOW FURNACE IN 

HORIZONTAL RIGHT AIRFLOW POSITION

Airflo

w

 

CASED COIL

G. FURNACE IN HORIZONTAL RIGHT POSITION 

CAUTION

!

Both the coil and furnace must be fully supported. Do not 

attempt to suspend the coil using the brackets.
Note: when installing onto an S-Series furnaces in horizontal 

right  or downflow configuration the flanges will be bent 

downward.

1.  HORIZONTAL RIGHT COIL CONVERSION: 

S-Series upflow furnaces can be horizontal left or 

right.  For legacy furnaces, the non-condensing 

furnaces may be laid on either side for horizontal 

application.  The condensing downflow/horizontal 

right and upflow/horizontal  left furnaces may only be 

rotated onto their left side.   

 

While not required, optional removal of some coil 

components will maximize airflow efficiency. 

 a.  Remove the coil by sliding the coil out of the coil

enclosure.

 b.  Optional but recommended: Remove the factory 

installed two-piece baffle assembly from the top of the 

coil by removing the 5/16” hex head screws.  See Figure 

2.  Replace only the top baffle using the same screws 

previously provided.

 

IMPORTANT: 

The A4MX cased coil must be placed downstream of the 

furnace.  See Figure 7 for proper orientation.

2. When the non-condensing Upflow/Horizontal furnace 
is placed on its right side for right airflow, the furnace top 
flange meets the cased coil top flange.  The coil flange fits 
inside of the furnace flange.  See Figure 6 and 8. 

3.  Use field-supplied self-drilling screws to connect the coil 
to the furnace.  Seal all gaps between the furnace and coil.

Summary of Contents for A4MXA1824AC6HA

Page 1: ...oil before beginning the installation Figure 1 18 AD37D1 1 EN Cased Aluminum Convertible Coils Models A4MXA1824AC6HA A4MXB1832AC6HA A4MXA3036AC6HA A4MXB3642AC6HA A4MXC3642AC6HA A4MXB4248AC6HA A4MXC4248AC6HA A4MXD4248AC6HA A4MXC4260AC3HA A4MXD4260AC3HA NOTE OPTIONAL DOWNFLOW GASKET INSTALLATION For unusually humid applications that expect prolonged operation above 70 RH it is recommended to use the...

Page 2: ...GAS FURNACE a Apply gasket material duct seal field supplied to ALL mating surfaces between the furnace and the coil case b Set the coil case on top of the furnace Connect the duct work to the coil case using field supplied screws c Secure the coil case to the furnace and seal for air leaks as required FOR UPFLOW HORIZONTAL LEFT INSTALLATIONS Figure 3 Figure 2 Remove and Discard Replace UPFLOW FUR...

Page 3: ...A0 gasket kit to prevent water from form ing on the bottom of the drain pan and dripping into the supply ductwork a Lay the coil on its back side b Locate the 4 wide gasket material found in BAYGSKT001A0 c Attach the 4 gasket material to three sides of the bottom of the drain pan as shown Make sure to start by matching up the edge of the gasket material to the inner edge of the drain pan by the co...

Page 4: ...ay be laid on either side for horizontal application The condensing downflow horizontal right and upflow horizontal left furnaces may only be rotated onto their left side While not required optional removal of some coil components will maximize airflow efficiency a Remove the coil by sliding the coil out of the coil enclosure b Optional but recommended Remove the factory installed two piece baffle...

Page 5: ...on the coil enclosure two on each side at the bottom Each of the rear brackets will be attached with the wide side of the bracket resting on the top and bottom of the horizontal coil and furnace see Figure 11 Four additional screws will be used to attach each rear bracket f The front bracket is positioned as close to the center as possible with the narrow edge against the coil enclosure and the wi...

Page 6: ...o be replaced with the included 0 077 orifice COIL MODEL NOMINAL TONS FACTORY INSTALLED ORIFICE SIZE ADDITIONAL INCLUDED ORIFICE SIZES A4MXA1824AC6HA 2 0 057 0 052 A4MXB1832AC6HA 0 052 0 064 A4MXA3036AC6HA 2 5 0 064 0 068 A4MXB3642AC6HA 3 0 068 0 077 A4MXC3642AC6HA 0 077 A4MXB4248AC6HA 3 5 0 077 0 082 A4MXC4248AC6HA 4 0 082 0 077 A4MXD4248AC6HA 0 077 A4MXC4260AC3HA 5 TXV none A4MXD4260AC3HA none T...

Page 7: ...t coil 1 Remove both rubber plugs from the indoor coil 2 Field supplied tubing should be cut square round and free of burrs at the connecting end Clean the tubing to prevent contaminants from entering the system 3 Run the refrigerant tubing into the stub tube sockets of the indoor unit coil UNIT PANELS MUST BE SHIELDED DURING BRAZ ING 4 Flow a small amount of nitrogen through the tubing while braz...

Page 8: ...he outdoor unit M CONDENSATE DRAIN PIPING Condensate drain connections are located in the drain pan at the bottom of the coil enclosure assembly The female threadedfittingprotrudesoutsideoftheenclosureforexternal connection A field fabricated trap is not required for proper drainage due to the positive pressure of the furnace however it is recommended to prevent efficiency loss of conditioned air ...

Page 9: ...aller s Guide Outline Drawing for models A4MXA1824AC6HAA A4MXB1832AC6HAA A4MXA3036AC6HAA A4MXB3642AC6HAA A4MXC3642AC6HAA A4MX B4248AC6HAA A4MXC4248AC6HAA A4MXD4248AC6HAA A4MXC4260AC3HAA A4MXD4260AC3HAA From Dwg D346409 RevA ...

Page 10: ... NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is correct NO Before starting insure the blower wheel indoor and outdoor coils are clean Is the liquid line temperature at indoor coil within 8F of outdoor liquid line temperature YES Verify line set is s...

Page 11: ...18 AD37D1 1 EN 11 Installer s Guide ...

Page 12: ...licy of continuous product and product data improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor 06 19 ...

Reviews: