background image

 

Page 25

Installer’s Guide

Service Maintenance

Service maintenance should be performed by qualified service 

personnel. 

Cooling Season

To keep the unit operating safely and efficiently, the manufacturer 

recommends that a qualified service technician check the entire 

system at least once each season or more often if needed. The 

service technician should examine these areas of the 4YCZ6 unit:

 

filters (for cleaning or replacement)

  motors and drive system components (for proper operation)

 

economizer gaskets (for possible replacement)

 

safety controls (for mechanical cleaning)

 

electrical components and wiring (for possible replacement 

and connection tightness)

 

condensate drain (for proper sealing and cleaning)

 

unit duct connections (to see that they are physically sound 

and sealed to the unit casing)

 

unit mounting support (for structural integrity)

 

the unit (for obvious unit deterioration)

Heating Season

Complete the following unit inspections and service routines 

described at the beginning of each heating season.

 

Visually inspect the unit to ensure that the airflow required 

for combustion and condenser coil is not obstructed from the 

unit.

 

Inspect the control panel wiring to verify that all electrical 

connections are tight and that the wire insulation is intact.

 

Check the operation of the gas ignition system as follows: 

Turn off the gas supply with the unit operating to verify that 

the gas valve closes and that a re-ignition cycle is initiated 

by the unit. 

 

Visually inspect the inside of the burners and the burner ports 

for deposit buildup and corrosion.  Wipe and brush the inside 

of the burner and the burner ports and then clean with a dry 

cloth.  If the deposit buildup or corrosion is excessive, replace 

the burners.

Flue Hood and Combustion Blower Cleaning

Manifold Pressure Check and Adjust

 

1. Connect a manometer to the pressure tap at the outlet side 

of the unit’s gas valve (remove the Control/Heat access 
panel).  Read the manifold pressure with the burners firing. 
See Figure 16 on page 17 for gas valve connections.

  2. If the manifold pressure reading does not match the value 

indicated on the unit's nameplate, the unit's pressure regula-
tor must be adjusted as follows:

 

a. Remove the cover screw on the gas regulator located on 

the front side of the unit’s gas valve.

 

b. Turn the adjusting screw clockwise to increase manifold 

pressure or counterclockwise to decrease manifold pres-
sure.

  3.  Check the temperature rise during furnace operation to insure 

that it falls within the range specified on the unit's nameplate.

  4.  If the temperature rise noted is outside of the specified limits, 

adjust the indoor air flow to cause the temperature rise of 
the heat exchanger to fall within the required range.

CAUTION

!

Never use combustible cleaning fluids on any part of the 

furnace.

Before each heating season, the Flue Hood and combustion 
blower should be inspected for signs of any blockage or soot-
ing. 

Any cleaning required should be performed only by a 

qualified service technician

 using the following procedure:

1.  Turn the comfort control to OFF. Turn off power to the unit. 

Turn the main power disconnect OFF. Turn the manual gas 
valve OFF.

2.  Remove the Flue Hood from the side panel.
3.  Remove the combustion blower from the vestibule panel. 

Disconnect blower wiring and pressure switch hose.

4.  Wipe blower and Flue Hood clean with a dry cloth. 
5.  Replace the combustion blower gasket with a new one.
6.  Reassemble combustion blower and Flue Hood in reverse 

order of removal. Reconnect pressure switch hose.

7.  Verify all wiring is correct per the unit's wiring diagram.
8.  Follow start-up procedure to place unit back in service. Verify 

proper operation.

Summary of Contents for 4YCY4042C

Page 1: ...out the evaporator fan or coil access panels in place Reinstall the access panels after performing maintenance proceedures on the fan Operating the unit without the access panels properly installed ma...

Page 2: ...per service equipment is required Failure to use proper service tools may result in equipment damage or personal injury SERVICE Use only R 410A Refrigerant and approved POE compres sor oil IMPORTANT W...

Page 3: ...work to Roof Frame 16 Attaching Horizontal Ductwork to Unit 16 Condensate Drain Piping 16 Gas Piping Installation 16 Pipe Delivery Schedule natural gas only 17 Gas Pressure Set up Precautions 17 Gas S...

Page 4: ...Guide Step 2 Determine Unit Clearances Figure 1 4YCZ6036 1 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up from u...

Page 5: ...Page 5 Installer s Guide Figure 2 4YCZ6036 2 of 3...

Page 6: ...Page 6 Installer s Guide Figure 3 4YCZ6036 3 of 3...

Page 7: ...Page 7 Installer s Guide Figure 4 4YCZ6048 through 4YCZ6060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Page 8: ...Page 8 Installer s Guide Figure 5 4YCZ6048 through 4YCZ6060 2 of 3...

Page 9: ...Page 9 Installer s Guide Figure 6 4YCZ6048 through 4YCZ6060 3 of 3...

Page 10: ...to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabricate...

Page 11: ...clearance to combustible mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airfl...

Page 12: ...abs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparing the unit for lifting check the unit dimension drawings for center of gravity for lifting safety Figur...

Page 13: ...roof top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails are...

Page 14: ...ible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars Base of unit rest on top of curb rails Dr...

Page 15: ...rizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Sup port required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Ang...

Page 16: ...ise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two...

Page 17: ...making the gas pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local cod...

Page 18: ...chonthegasvalveinletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the...

Page 19: ...ns Models that require 49 orifices for altitudes from 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1...

Page 20: ...tioning systems been checked at the service ports for charge and leak tested if necessary Does the condenser fan and indoor blower turn free without rub bing and are they tight on the shafts Has the i...

Page 21: ...Page 21 Installer s Guide Figure 22 4YCZ6 Field Wiring Diagram NOTE For economizer wiring instructions see the Installer s Guide that came with your economizer...

Page 22: ...ating Cycle Theseunitsareequippedwithasolid stateignitioncontrolthatlights the burners each time the thermostat calls for heat The burners are extinguished during the OFF cycle The gas heating section...

Page 23: ...nd postpurge The indoor blower motor will continue to operate at the current speed for 60 or 90 seconds after the flames are extinguished Sequence of Operation Safety Sequences This product is equippe...

Page 24: ...stible materials gasoline or other flammable vapors or liquids near the unit WARNING Someoftheperiodicmaintenancefunctionsofthe4YCZ6unitcan beperformedbytheowner thisincludesreplacingthedisposable or...

Page 25: ...Hood and Combustion Blower Cleaning Manifold Pressure Check and Adjust 1 Connect a manometer to the pressure tap at the outlet side of the unit s gas valve remove the Control Heat access panel Read th...

Page 26: ...3 Flashes Pressure switch problem detected Fast Flash Rate Not used 4 Flashes High Limit switch protection device open Steady ON Normal No Call for Heat 5 Flashes Flame sensed and gas valve not energi...

Page 27: ...Page 27 Installer s Guide...

Page 28: ...ide Trane 6200 Troup Highway Tyler TX 75707 9010 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specification without n...

Reviews: