Performance Data Cooling

4YCY4036A1/3 AT 1200 NOM CFM 

(COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)

OD

ID

TOT

SENS CAP AT ENTERING DB TEMP

TOTAL

AMB

WB

CAP

72

75

78

80

KW

85

59

34.5

28.8

32.4

34.5

34.5

2.7

63

36.0

23.4

27.0

30.5

32.9

2.7

67

38.8

18.5

22.0

25.6

27.9

2.8

71

41.9

13.5

17.1

20.6

23.0

2.8

95

59

32.0

27.6

31.2

32.0

32.0

3.0

63

33.4

22.3

25.9

29.4

31.8

3.1

67

35.9

17.4

20.9

24.5

26.9

3.1

71

38.8

12.4

16.0

19.6

21.9

3.1

105

59

29.5

26.5

29.5

29.5

29.5

3.3

63

30.7

21.2

24.8

28.4

30.7

3.4

67

33.1

16.3

19.9

23.4

25.8

3.4

71

35.7

11.4

15.0

18.5

20.9

3.4

115

59

26.9

25.4

26.9

26.9

26.9

3.6

63

28.1

20.2

23.7

27.3

28.1

3.7

67

30.2

15.3

18.8

22.4

24.8

3.7

71

32.7

10.4

13.9

17.5

19.9

3.7

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW

CAPACITY

TOTAL POWER

RATE, CFM

MULTIPLIER

MULTIPLIER

LOW

1050

0.97

0.98

HIGH

1350

1.03

1.02

ARI RATING FOR COOLING

CFM

CAPACITY (A) TEST

SEER

EER

1210

36000

14.20

11.60

ARI Standard Capacity Rating Conditions

ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.

4YCY4024A1 AT 800 NOM CFM 

(COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)

OD

ID

TOT

SENS CAP AT ENTERING DB TEMP

TOTAL

AMB

WB

CAP

72

75

78

80

KW

85

59

22.9

19.1

21.4

22.9

22.9

1.8

63

23.9

15.6

17.9

20.2

21.8

1.8

67

25.8

12.3

14.7

17.0

18.6

1.9

71

27.8

9.1

11.5

13.8

15.3

1.9

95

59

20.9

18.2

20.5

20.9

20.9

2.0

63

21.8

14.7

17.0

19.3

20.9

2.0

67

23.5

11.5

13.8

16.1

17.7

2.0

71

25.3

8.3

10.6

12.9

14.5

2.0

105

59

18.8

17.3

18.8

18.8

18.8

2.1

63

19.6

13.8

16.1

18.5

19.6

2.1

67

21.1

10.6

12.9

15.3

16.8

2.2

71

22.8

7.4

9.7

12.1

13.6

2.2

115

59

16.7

16.4

16.7

16.7

16.7

2.3

63

17.5

13.0

15.3

17.5

17.5

2.3

67

18.8

9.8

12.1

14.4

16.0

2.3

71

20.3

6.6

8.9

11.2

12.8

2.3

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW

CAPACITY

TOTAL POWER

RATE, CFM

MULTIPLIER

MULTIPLIER

LOW

700

0.97

0.98

HIGH

900

1.03

1.02

ARI RATING FOR COOLING

CFM

CAPACITY (A) TEST

SEER

EER

790

23400

14.00

11.60

ARI Standard Capacity Rating Conditions

ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.

4YCY4030A1 AT 1000 NOM CFM 

(COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)

OD

ID

TOT

SENS CAP AT ENTERING DB TEMP

TOTAL

AMB

WB

CAP

72

75

78

80

KW

85

59

29.8

24.1

26.9

29.2

28.9

2.3

63

31.0

19.7

22.6

25.5

27.4

2.3

67

33.4

15.8

18.6

21.5

23.4

2.3

71

36.1

11.8

14.6

17.5

19.4

2.3

95

59

27.3

23.0

25.8

27.3

27.3

2.5

63

28.5

18.7

21.5

24.4

26.3

2.5

67

30.7

14.7

17.6

20.4

22.3

2.5

71

33.1

10.7

13.6

16.5

18.4

2.5

105

59

24.8

21.9

24.7

24.8

24.8

2.7

63

25.9

17.6

20.5

23.3

25.2

2.7

67

27.9

13.7

16.5

19.4

21.3

2.7

71

30.1

9.7

12.6

15.4

17.4

2.7

115

59

22.4

20.8

22.4

22.4

22.4

2.9

63

23.3

16.6

19.5

22.3

23.3

2.9

67

25.1

12.7

15.5

18.4

20.3

2.9

71

27.1

8.7

11.6

14.4

16.4

2.9

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW

CAPACITY

TOTAL POWER

RATE, CFM

MULTIPLIER

MULTIPLIER

LOW

875

0.97

0.98

HIGH

1125

1.03

1.02

ARI RATING FOR COOLING

CFM

CAPACITY (A) TEST

SEER

EER

890

30000

14.00

12.00

ARI Standard Capacity Rating Conditions

ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.

Summary of Contents for 4YCY4024A

Page 1: ... 2008 Trane Pub No 22 1797 03 Product Data 4YCY4024A through 4YCY4060A Single Packaged Convertible Gas Electric 14 SEER 2 5 Ton 40 120 KBTU R 410A 22 1797 03 ...

Page 2: ...ctions are all contained in a single cabinet a Trane single packaged convertible gas electric system is easy to install and service It can be flush mounted beside your home at ground level or placed on the roof for horizontal or downflow installation When connected to an optional Trane thermostat control and air distribution ducts you have a highly efficient total home comfort system Single Packag...

Page 3: ...3 Contents Optional Equipment Listing 4 General Data 5 Performance Data Cooling 9 Indoor Fan 11 TypicalWiring 15 Optional Equipment 18 Dimensional Data 23 Mechanical Specifications 29 ...

Page 4: ...R201B LP Conversion Kit All 40K 120K Models BAYLPKT100A LP Conversion Kit All 64K 96K Models BAYLPKT101A LP Conversion Kit All 75K Models BAYLPKT102A Head Pressure Control Low Ambient Cool 208 240v Kit 5 BAYLOAM105A Quick Start Kit 4YCY4 A1 BAYQSKT301A Crankcase Heater Recip 4YCY4024A1 230v 5 BAYCCHT101A Crankcase Heater Scroll 4YCY4036 060A1 3 230v 5 BAYCCHT102A Adapter Curb 4YCY4024 036A to BAYC...

Page 5: ...per 1000 ft elevation 3 3 3 3 3 Convertible to LPG 4 4 4 4 4 This value is approximate For more precise value see Unit Nameplate 5 5 5 5 5 Based on U S Government Standard Tests 6 6 6 6 6 Filtersmustbeinstalledinreturnairstream Squarefootageslistedarebasedon300f p m facevelocity Ifpermanentfiltersareusedsizepermanufacturer srecommendation with a clean resistance of 0 05 W C 7 7 7 7 7 Unit is shipp...

Page 6: ...08 230 3 60 19 8 30 30 SCROLL 208 230 3 60 11 5 77 SPINE FIN 2 24 15 49 3 8 PLATE FIN 4 15 3 54 3 8 EXPANSION VALVE 3 4 FEMALE NPT PROPELLER 23 4 DIRECT 1 1 5 830 208 230 1 60 1 1 1 9 CENTRIFUGAL 10 X 10 DIRECT VARIABLE SEE FAN PERF TABLE 1 2 VARIABLE 200 230 1 60 4 3 4 3 CENTRIFUGAL DIRECT 2 1 45 2800 1500 208 230 1 60 0 34 NO THROWAWAY 4 0 R410A 6 75 1 2 H X W X L 47 86 44 5 52 03 493 397 4YCY40...

Page 7: ...FAN TYPE Dia x Width in Drive No Speeds CFM 0 0 in w g n Motor HP R P M Volts Ph Hz F L Amps L R Amps COMBUSTION FAN TYPE Drive No Speeds Motor HP R P M Volts Ph Hz FLA FILTER FURNISHED Type Recommended Recmd Face Area sq ft o REFRIGERANT Charge lbs m GAS PIPE SIZE in DIMENSIONS Crated in WEIGHT Shipping lbs Net lbs 4YCY4048A1096A 208 230 1 60 48000 1605 4 034 11 9 14 2 73 72000 96000 80 0 30 60 3...

Page 8: ...8 230 3 60 30 6 45 45 SCROLL 208 230 3 60 17 6 123 SPINE FIN 2 24 23 07 3 8 PLATE FIN 4 15 5 0 3 8 EXPANSION VALVE 3 4 FEMALE NPT PROPELLER 28 2 DIRECT 1 1 3 830 208 230 1 60 1 7 3 5 CENTRIFUGAL 11 X 10 DIRECT VARIABLE SEE FAN PERF TABLE 1 VARIABLE 208 230 1 60 6 9 6 9 CENTRIFUGAL DIRECT 2 1 45 2800 1500 208 230 1 60 0 34 NO THROWAWAY 5 3 R410A 9 75 1 2 H X W X L 51 86 47 4 61 75 676 548 4YCY4048A...

Page 9: ... 7 16 4 16 7 16 7 16 7 2 3 63 17 5 13 0 15 3 17 5 17 5 2 3 67 18 8 9 8 12 1 14 4 16 0 2 3 71 20 3 6 6 8 9 11 2 12 8 2 3 USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW AIR FLOW CAPACITY TOTAL POWER RATE CFM MULTIPLIER MULTIPLIER LOW 700 0 97 0 98 HIGH 900 1 03 1 02 ARI RATING FOR COOLING CFM CAPACITY A TEST SEER EER 790 23400 14 00 11 60 ARI Standard Capacity Rating Conditions ARI S...

Page 10: ...4 43 0 46 4 46 4 46 4 5 8 63 48 3 34 2 40 2 46 2 48 3 5 8 67 52 1 26 0 32 0 37 9 41 9 5 9 71 56 2 17 7 23 7 29 6 33 7 5 9 USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW AIR FLOW CAPACITY TOTAL POWER RATE CFM MULTIPLIER MULTIPLIER LOW 1750 0 97 0 98 HIGH 2250 1 03 1 02 ARI RATING FOR COOLING CFM CAPACITY A TEST SEER EER 1799 58500 14 00 11 90 ARI Standard Capacity Rating Conditions ...

Page 11: ...2 899 909 907 895 886 898 910 900 HIGH External Static Pressure in wg LOW MED 4YCY4024A DOWN Motor Speed 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 Watts 113 148 176 203 233 263 291 309 306 267 CFM 880 905 917 918 913 906 901 907 930 979 Watts 146 184 215 243 272 303 330 348 347 312 CFM 996 1009 1013 1012 1008 1003 1000 997 994 991 Watts 195 233 267 303 340 371 388 373 CFM 1122 1132 1134 1136 1138 11...

Page 12: ...377 1377 1375 1366 1352 1344 1360 1340 HIGH External Static Pressure in wg LOW MED 4YCY4036A DOWN Motor Speed 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 Watts 160 185 214 245 277 308 339 368 396 423 CFM 1206 1211 1213 1215 1215 1214 1212 1208 1201 1190 Watts 231 261 292 325 359 394 431 467 503 536 CFM 1389 1398 1405 1409 1410 1408 1403 1399 1396 1399 Watts 326 362 393 421 450 482 517 556 597 CFM 1582...

Page 13: ...4 1624 1624 1621 1618 1618 1620 1618 1606 1574 Watts 364 461 518 558 597 643 693 739 764 785 CFM 1816 1829 1836 1839 1840 1840 1844 1835 1830 1825 HIGH External Static Pressure in wg LOW MED 4YCY4048A DOWN Motor Speed 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 Watts 394 427 464 504 548 591 633 668 CFM 1673 1772 1799 1793 1779 1771 1767 1756 Watts 695 642 660 710 764 811 849 893 966 1108 CFM 2054 2036...

Page 14: ... 3 4YCY4036A 075 4YCY4036A 096 Switch Settings Nominal Airflow Switch Settings Nominal Airflow can be 1 or 3 Selection Low Stage High Stage 7 OFF 8 OFF A 1075 1375 7 ON 8 OFF B 1100 1450 7 OFF 8 ON C 1150 1500 7 ON 8 ON D 1200 1575 4YCY4042A Switch Settings Nominal Airflow Selection Low Stage High Stage 7 OFF 8 OFF A 1075 1375 7 ON 8 OFF B 1100 1450 7 OFF 8 ON C 1150 1500 7 ON 8 ON D 1200 1575 Sel...

Page 15: ... W2 R COMMON FAN COMPRESSOR HEAT FIRST STAGE HEAT SECOND STAGE 24V UNIT CONTROL BOX GROUND WIRE 3 PH POWER UNIT NOTE 1 1 PH POWER B G Y W1 W2 R COMMON FAN COMPRESSOR HEAT FIRST STAGE HEAT SECOND STAGE 24V B G Y W1 W2 R GR WH WH GR WH WH GR WH WH ...

Page 16: ...16 Typical Wiring ...

Page 17: ...17 From Dwg 21D757165 P02 Typical Wiring ...

Page 18: ...is page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use ...

Page 19: ...is page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use ...

Page 20: ...sis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use BAYFLTR101 201B 1 2 Filter Rack Mounts in Filter Coil Section BAYACCDOR1A BAYACCDOR2A Hinged Filter Access Door Replaces Filter Coil Access Panel Filter ...

Page 21: ... only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use Economizer Unit ApplicationM odels A BAYECON101A 2 4YC WC3018 036A 4TC 3018 036A 4W T Y DCY4024 060 20 125 BAY...

Page 22: ...ible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unautho rized use Manual Fresh Air Model Unit Application Models A B C D BAYOSAH001 2 4YC WC3018 036A 4TC 3018 036A 4W T Y DCY4024 036A 4W Y DCZ6036A 22 7 16 20 11 16 12 3 8 9 3 16 BAYOSAH002 2 4YC WC3042 060A 4TC 3042 060A 4W T Y DCY4042 060 4W Y DCZ6048 060A 25 3 16 20 11 16 12 3...

Page 23: ...23 Dimensional Data 4YCY4024A through 4YCY4036A 1 of 3 ...

Page 24: ...24 Dimensional Data 4YCY4024A through 4YCY4036A 2 of 3 ...

Page 25: ...25 4YCY4024A through 4YCY4036A 3 of 3 Dimensional Data ...

Page 26: ...26 Dimensional Data 4YCY4042A through 4YCY4060A 1 of 3 ...

Page 27: ...27 Dimensional Data 4YCY4042A through 4YCY4060A 2 of 3 ...

Page 28: ...28 4YCY4042A through 4YCY4060A 3 of 3 Dimensional Data ...

Page 29: ...ted motor bearings Motor blower assembly isolated from unit with rubber mounts Condenser Fan Direct drive draw through propeller type Weather proofed permanent split capacitor fan motor shall have built in thermal overload and permanently lubricated motor bearings Low Ambient Standard refrigerant system operation down to 55 F Low ambient accessory required for operation to 0 F ambient condition Ga...

Reviews: