9
Performance Data Cooling
4YCY4036A1/3 AT 1200 NOM CFM
(COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD
ID
TOT
SENS CAP AT ENTERING DB TEMP
TOTAL
AMB
WB
CAP
72
75
78
80
KW
85
59
34.5
28.8
32.4
34.5
34.5
2.7
63
36.0
23.4
27.0
30.5
32.9
2.7
67
38.8
18.5
22.0
25.6
27.9
2.8
71
41.9
13.5
17.1
20.6
23.0
2.8
95
59
32.0
27.6
31.2
32.0
32.0
3.0
63
33.4
22.3
25.9
29.4
31.8
3.1
67
35.9
17.4
20.9
24.5
26.9
3.1
71
38.8
12.4
16.0
19.6
21.9
3.1
105
59
29.5
26.5
29.5
29.5
29.5
3.3
63
30.7
21.2
24.8
28.4
30.7
3.4
67
33.1
16.3
19.9
23.4
25.8
3.4
71
35.7
11.4
15.0
18.5
20.9
3.4
115
59
26.9
25.4
26.9
26.9
26.9
3.6
63
28.1
20.2
23.7
27.3
28.1
3.7
67
30.2
15.3
18.8
22.4
24.8
3.7
71
32.7
10.4
13.9
17.5
19.9
3.7
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW
CAPACITY
TOTAL POWER
RATE, CFM
MULTIPLIER
MULTIPLIER
LOW
1050
0.97
0.98
HIGH
1350
1.03
1.02
ARI RATING FOR COOLING
CFM
CAPACITY (A) TEST
SEER
EER
1210
36000
14.20
11.60
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
4YCY4024A1 AT 800 NOM CFM
(COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD
ID
TOT
SENS CAP AT ENTERING DB TEMP
TOTAL
AMB
WB
CAP
72
75
78
80
KW
85
59
22.9
19.1
21.4
22.9
22.9
1.8
63
23.9
15.6
17.9
20.2
21.8
1.8
67
25.8
12.3
14.7
17.0
18.6
1.9
71
27.8
9.1
11.5
13.8
15.3
1.9
95
59
20.9
18.2
20.5
20.9
20.9
2.0
63
21.8
14.7
17.0
19.3
20.9
2.0
67
23.5
11.5
13.8
16.1
17.7
2.0
71
25.3
8.3
10.6
12.9
14.5
2.0
105
59
18.8
17.3
18.8
18.8
18.8
2.1
63
19.6
13.8
16.1
18.5
19.6
2.1
67
21.1
10.6
12.9
15.3
16.8
2.2
71
22.8
7.4
9.7
12.1
13.6
2.2
115
59
16.7
16.4
16.7
16.7
16.7
2.3
63
17.5
13.0
15.3
17.5
17.5
2.3
67
18.8
9.8
12.1
14.4
16.0
2.3
71
20.3
6.6
8.9
11.2
12.8
2.3
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW
CAPACITY
TOTAL POWER
RATE, CFM
MULTIPLIER
MULTIPLIER
LOW
700
0.97
0.98
HIGH
900
1.03
1.02
ARI RATING FOR COOLING
CFM
CAPACITY (A) TEST
SEER
EER
790
23400
14.00
11.60
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
4YCY4030A1 AT 1000 NOM CFM
(COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD
ID
TOT
SENS CAP AT ENTERING DB TEMP
TOTAL
AMB
WB
CAP
72
75
78
80
KW
85
59
29.8
24.1
26.9
29.2
28.9
2.3
63
31.0
19.7
22.6
25.5
27.4
2.3
67
33.4
15.8
18.6
21.5
23.4
2.3
71
36.1
11.8
14.6
17.5
19.4
2.3
95
59
27.3
23.0
25.8
27.3
27.3
2.5
63
28.5
18.7
21.5
24.4
26.3
2.5
67
30.7
14.7
17.6
20.4
22.3
2.5
71
33.1
10.7
13.6
16.5
18.4
2.5
105
59
24.8
21.9
24.7
24.8
24.8
2.7
63
25.9
17.6
20.5
23.3
25.2
2.7
67
27.9
13.7
16.5
19.4
21.3
2.7
71
30.1
9.7
12.6
15.4
17.4
2.7
115
59
22.4
20.8
22.4
22.4
22.4
2.9
63
23.3
16.6
19.5
22.3
23.3
2.9
67
25.1
12.7
15.5
18.4
20.3
2.9
71
27.1
8.7
11.6
14.4
16.4
2.9
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW
CAPACITY
TOTAL POWER
RATE, CFM
MULTIPLIER
MULTIPLIER
LOW
875
0.97
0.98
HIGH
1125
1.03
1.02
ARI RATING FOR COOLING
CFM
CAPACITY (A) TEST
SEER
EER
890
30000
14.00
12.00
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
Summary of Contents for 4YCY4024A
Page 16: ...16 Typical Wiring ...
Page 17: ...17 From Dwg 21D757165 P02 Typical Wiring ...
Page 23: ...23 Dimensional Data 4YCY4024A through 4YCY4036A 1 of 3 ...
Page 24: ...24 Dimensional Data 4YCY4024A through 4YCY4036A 2 of 3 ...
Page 25: ...25 4YCY4024A through 4YCY4036A 3 of 3 Dimensional Data ...
Page 26: ...26 Dimensional Data 4YCY4042A through 4YCY4060A 1 of 3 ...
Page 27: ...27 Dimensional Data 4YCY4042A through 4YCY4060A 2 of 3 ...
Page 28: ...28 4YCY4042A through 4YCY4060A 3 of 3 Dimensional Data ...