18-AD25D1-4C-EN  

5

Installer’s Guide

Is sub cooling at the 

outdoor unit between 

8 to 12F?

NO

YES

Is superheat       

< 5F?

YES

Correct air 

flow 

problem

Is air flow at least 

350 CFM per ton?

YES

NO

Remove sensing bulb from the 

suction line.  Measure superheat 

at indoor coil while holding the 

bulb in bare hand for one minute.

Does superheat decrease?

Measure superheat at indoor coil 

while placing the bulb in an ice 

and water bath for one minute.

Does superheat increase?

YES

Replace the 

TXV

NO

TXV is OK

NO

Is superheat      

< 20F?

NO

YES

NO

Is indoor 

temperature more 

than 85F?

NO

Is sub cooling less 

than 8F?

YES

Confirm that charge 

is correct and look 

for dirty or restricted  

outdoor coil.

Confirm that 

charge is 

correct.

NO

Before starting

, insure the 

blower wheel, indoor and outdoor 

coils are clean.

Is the liquid line 

temperature at indoor 

coil  within 8F of outdoor 

liquid line temperature?

YES

Verify line set is 

sized properly 

for application

NO

The system is running at max 

capacity and this may be 

causing the High superheat.  

Wait until indoor temperature 

is less than 80F and check 

superheat again.

YES

YES

Verify inlet screen 

of inlet tube 

assembly is clear 

of debris

NO

Has TXV screen 

been checked and 

cleaned?

YES

Inlet screen located in liquid line. Check, clean, & 

replace if necessary.