background image

18-AD25D1-4C-EN  

3

Installer’s Guide

Since coil/ enclosure assembly must be installed within 

the horizontal run of duct, a transition duct must be 

fabricated to mate with the furnace supply outlet duct 

flange on one end and the duct flange connection on the 

coil/ enclosure assembly on the other end.
For maximum performance, it is recommended that the 

transition duct be at least 2 feet in length.

1.  Secure the transition duct to the furnace with the 

furnace in position.

2.  The refrigerant lines and condensate connections of 

cased coils may be on either side of the supply air 

duct. The air may be directed through the coil from 

either side of the coil.

3.  Attach the coil/ enclosure assembly to the transition 

from the furnace, providing proper support for coil/ 

enclosure assembly’s weight. Keep the coil level. 

Extra pitch is not required for coil to drain properly. 

4.  Secure the downstream side of coil/ enclosure 

assembly to the supply air duct.

NOTE: 

Secure properly so there will be no air leakage.

5.  The indoor coil must be evacuated through the 

refrigerant lines at the outdoor unit before opening 

the service valves. See evacuation procedure in Field 

Fabricated Refrigerant Lines section of the Installer’s 

Guide for the outdoor unit.

6.  Complete the installation of the unit per installation 

instructions.

E. INSTALLING/BRAZING REFRIGERANT 

LINES 

CAUTION

!

Do  NOT open refrigerant valve at the outdoor unit 

until the refrigerant lines and coil have been brazed, 

evacuated, and leak checked. This would cause 

contamination of the refrigerant or possible discharge 

of refrigerant to the atmosphere.

FLUE 

STACK

TRANSITION DUCT

COIL/ENCLOSURE ASSY

SUPPLY DUCT

VERTICAL UPFLOW

FURNACE

1.  The following steps are to be considered when 

installing the refrigerant lines:

a. Determine the most practical way to run the lines.

b. Consider types of bends to be made and space 

limitations.

c. Route the tubing making all required bends and 

properly secure the tubing before making final 

connections.

NOTE: 

Refrigerant lines must be isolated from the structure and 

the holes must be sealed weather tight after installation.
IMPORTANT:  

Do not unseal refrigerant tubing until ready to fit 

refrigerant lines.

There is only a holding charge of dry air in the indoor coil, 

therefore no loss of operating refrigerant charge occurs 

when the sealing plugs are removed.

NOTE:  

TXV bulb MUST be protected (wrapped with wet rag) 

or removed, while brazing the tubing. Overheating 

of the sensing bulb will affect the functional 

characteristics and performance of the comfort coil.

Reviews: