background image

4

18-BC51D1-4

Installer’s Guide

10. The gas valve can now be opened. For a ball type gas

valve, open the gas valve by removing the shut-off valve
cap and turning the valve stem 1/4 turn counterclock-
wise, using 1/4" Open End or Adjustable wrench. See
Figure 4. For brass gas line service valve opening, follow
8 and 9 on page 3. See Figure 5.

11. The gas valve is now open for refrigerant flow. Replace

valve stem cap to prevent leaks. Again, these caps MUST
BE REPLACED
 to prevent leaks. Replace valve stem
and pressure tap cap finger tight, then tighten an
additional 1/6 turn. See Figure 3.

If refrigerant lines are longer than 15 feet and/or a different
size than recommended, it will be necessary to adjust system
refrigerant charge upon completion of installation. See page 6
or the unit Service Facts.

E. ELECTRICAL CONNECTIONS

WARNING

!

When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility
of electric shock.

1. Power wiring and grounding of equipment must comply

with local codes.

2. Power supply must agree with equipment nameplate.

3. Install a separate disconnect switch at the outdoor unit.
4. Ground the outdoor unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration

transmission may create a noise problem within the
structure.

6. The use of color coded low voltage wire is recommended to

simplify connections between the outdoor unit, the
thermostat and the indoor unit.

Table 1 — NEC Class II Control Wiring

24 VOLTS

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

7. Table 1 defines maximum total length of low voltage

wiring from outdoor unit, to indoor unit, and to
thermostat.

8. Mount the indoor thermostat in accordance with instruc-

tion included with the thermostat. Wire per appropriate
hook-up diagram (included in these instructions).

F. DEFROST CONTROL

The demand defrost control measures heat pump outdoor
ambient temperature with a sensor located outside the
outdoor coil. A second sensor located on the outdoor coil is
used to measure the coil temperature. The difference
between the ambient and the colder coil temperature is the
difference or delta-T measurement. This delta-T measure-
ment is representative of the operating state and relative
capacity of the heat pump system. By measuring the change
in delta-T, we can determine the need for defrost. The coil
sensor also serves to sense outdoor coil temperature for
termination of the defrost cycle.

FAULT IDENTIFICATION

A fault condition is indicated by the flashing light on the
defrost control inside the heat pump control box.

In normal operation, the defrost control light will flash once
each second. If the light is flashing more than once per
second or not at all, refer to the service manual for that unit.

PIN IDENTIFICATION (See Figure 6.)

1. TEST_COMMON (Shorting any of the other pins to this

pin causes the function of the other pin to be executed.
Leaving this pin open results in the normal mode of
operation.)

2. TST  =  Test (Shorting TEST_COMMON to this pin

speeds up all defrost board timings.)

3. FRC_DFT  =  Forced Defrost (Short TEST_COMMON to

this pin for two [2] seconds to initiate a forced defrost.
Remove the short after defrost initiates.)

FRC_DFT

TEST_COMMON

TST

DEFROST CONTROL CHECKOUT

Normal operation requires:

a. LED on board flashing 1 time/second.

b. 24V AC between R & B.

c. 24V AC between Y & B with unit operating.

d. Defrost initiation when FRC_DFT pin is shorted to

TEST_COMMON pin.

If a defrost control problem is suspected, refer to the service
information in control box.

WARNING

!

Do NOT connect 24 VAC to T1 (ODS-A) terminal. ODS-A
thermistor WILL BE BLOWN.

G. COMPRESSOR START UP

After all electrical wiring is complete, SET THE THERMO-
STAT SYSTEM SWITCH IN THE OFF POSITION SO
COMPRESSOR WILL NOT RUN, and apply power by
closing the system main disconnect switch. This will activate
the compressor sump heat (where used). Do not change the
Thermostat System Switch until power has been applied for
one (1) hour. Following this procedure will prevent potential
compressor overload trip at the initial start-up.

H. OPERATIONAL AND

CHECKOUT PROCEDURES

Final phases of this installation are the unit Operational and
Checkout Procedures which are found in this instruction on
page 8. To obtain proper performance, all units must be
operated and charge adjustments made in accordance with
procedures found in the Service Facts and on page 6.

IMPORTANT:
Perform a final unit inspection to be sure that factory tubing has
not shifted during shipment. Adjust tubing if necessary so tubes
do not rub against each other when the unit runs. Also be sure
that wiring connections are tight and wire routing is secure.

PIN IDENTIFICATION

6

Summary of Contents for 4TWR3

Page 1: ...use by individuals posses sing adequate backgrounds of electrical and mechanical experience Any attempt to repair a central air conditioning product may result in personal injury and or property dama...

Page 2: ...should not exceed sixty 60 feet liquid line 8 Locate and install indoor coil or air handler in accordance with instruction included with that unit C INSTALLING REFRIGERANT LINES CAUTION If using exist...

Page 3: ...indoor units is completed the field brazed connections must be checked for leaks Pressurize through the service valve ports the indoor unit and field refrigerant lines with dry nitrogen to 350 400 ps...

Page 4: ...te and relative capacity of the heat pump system By measuring the change in delta T we can determine the need for defrost The coil sensor also serves to sense outdoor coil temperature for termination...

Page 5: ...E W IR IN G C O M P R E S S O R IO L R U N C A P A C IT O R S T A R T C A P A C IT O R S T A R T R E L A Y C O N T A C T O R C O N T A C T S L O W V O L T A G E W IR IN G C O N T R O L T R A N S F O R...

Page 6: ...Subcool Charging Table Pressure 20 15 Use Design Subcool Value from Table 10 0 Subtract 10 psig from S C Table Pressure 10 20 25 30 40 60 80 TOTAL REFRIGERANT LINE LENGTH FEET REFRIGERANT LINE LIFT FE...

Page 7: ...946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR3060A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR4018A 3 1 933 36 3 4 829 32...

Page 8: ...nry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance an...

Reviews: