18-AC95D1-5C-EN
3
50’
Max
Vertical
Change
Standard
Line Set
150’ Max
TOTAL Line Length
50’
Max
Vertical
Change
Section 2. Unit Location Considerations
2.1 Unit Dimensions and Weight
2.2 Refrigerant Piping Limits
Table 2.1
When mounting the outdoor unit on a roof, be
sure the roof will support the unit’s weight.
Properly selected isolation is recommended to
alleviate sound or vibration transmission to the
building structure.
1. The maximum TOTAL length of refrigerant
lines from outdoor to indoor unit should
NOT exceed 150 feet* (including lift).
2. The maximum vertical change should not
exceed 50 feet*.
3. Standard and alternate line sizes and
service valve connection sizes are shown in
Table 5.1.
* See Table 5.1 for exceptions for certain
tonnages.
Note:
For other line lengths, Refer to Refriger-
ant Piping Application Guide, SS-APG006-EN
or Refrigerant Piping Software Program, 32-
3312-xx (latest revision).
D
H
W
Unit Dimensions and Weight
Models
H x D x W (in)
Weight* (lb)
4TTX8024A
48 x 34 x 37
265
4TTX8036A
52 x 34 x 37
271
4TTX8048A
52 x 34 x 37
274
4TTX8060A
52 x 34 x 37
295
* Weight values are estimated.