background image

 18-AD41D1-1B-EN

Installer’s Guide

NOTE:  

TXV bulb MUST be protected (wrapped with wet rag) or 

removed, while brazing the tubing. Overheating of the 

sensing bulb will affect the functional characteristics and 

performance of the comfort coil.

When replacing the TXV bulb, reinstall the bulb in the 

proper orientation. Some models will use a spring steel clip 

to attach the TXV bulb, and some models will use a hose 

clamp. When supplied with a hose clamp, the clamp should 

be "snug" but not "tight" - the specification is to torque the 

hose clamp to 20 +/- 5 in-lbs.

H.  LEAK CHECK

1.  Using a manifold gauge, connect an external supply of dry 

nitrogen to the gauge port on the liquid line.  

2.  Pressurize the connecting lines and indoor coil to 150 PSIG 

maximum.

3.  Leak check brazed line connections using soap bubbles.

Repair leaks (if any) after relieving pressure.

4.  Evacuate and charge the system per the instructions packaged 

with the outdoor unit.

Figure 7

J.  CLEANING THE COIL

The two piece door allows removal of the outer casing doors 
without interference from refrigerant or condensate lines.

The foil covered insulation on 4PXC coils should be wiped down 
and residual dirt and dust should be vacuumed up to maintain 
good air quality. See Figure 7.

The manufacturer’s recommendation for coil cleaning is to initially 
use only water to wash away debris that may have collected on 
and in the coil fin surface. Removing an evaporator coil is the best 
way to effectively clean a coil that is heavily contaminated. This 
is accomplished by removing the coil from the cabinet, sealing 
the liquid and vapor line and using a strong water stream such 
as from a garden hose, being careful to prevent fin damage. Use 
chemical cleaners, only when necessary.  

Figure 6

Capillary tubes will come 

out the top of bulb when 

positioned correctly.

I.  CONDENSATE DRAIN PIPING

Condensate drain connections are located in the drain pan at the 
bottom of the coil/enclosure assembly. The female threaded fitting 
protrudes outside of the enclosure for external connection.  A field 
fabricated trap is not required for proper drainage due to the positive 
pressure of the furnace; however, it is recommended to prevent 
efficiency loss of conditioned air. 
1.  The drain hole in the drain pan must be cleared of all insulation.
2.  Insulate the primary drain line to prevent sweating where 

dew point temperatures may be met. (Optional depending on 
climate and application needs)  

3.  Connect the secondary drain line to a separate drain line (no 

trap is needed in this line).  

PAINTED AREAS OF THE UNIT MUST BE SHIELDED DURING 

BRAZING.

1.  Remove both rubber plugs from the indoor coil.
2.  Field supplied tubing should be cut square, round and free 

of burrs at the connecting end. Clean the tubing to prevent 
contaminants from entering the system.

3.  Run the refrigerant tubing into the stub tube sockets of the 

indoor unit coil. 

4.  Flow a small amount of nitrogen through the tubing while 

brazing.

5.  Use good brazing technique to make leakproof joints.
6.  Minimize the use of sharp 90 degree bends.
7.  Insulate the suction line and its fittings.
8.  Do NOT allow un-insulated lines to come into contact with 

each other.

9.  Wrap the TXV with insulation after the hose clamp has 

been installed.

NOTE:   

Refer to Service Guideline, UN-SVG001C-EN, Evaporator 

Coil Cleaning and Condensate Drain Maintenance Guide-

lines for important information on cleaning coils with 

chemical treatments.

Summary of Contents for 4PXCAU24BS3HAB

Page 1: ... separately purchased kit Upflow models 4PXCAU24BS3HAB 4PXCAU32BS3HAB 4PXCBU24BS3HAB 4PXCBU30BS3HAB 4PXCCU30BS3HAB 4PXCBU36BS3HAB 4PXCCU36BS3HAB 4PXCBU42BS3HAB 4PXCCU42BS3HAB 4PXCBU48BS3HAB 4PXCCU48BS3HAB 4PXCDU48BS3HAB 4PXCCU60BS3HAB 4PXCDU60BS3HAB Downflow models 4PXCBD30BS3HDB 4PXCBD36BS3HDB 4PXCCD36BS3HDB 4PXCBD42BS3HDB 4PXCCD42BS3HDB 4PXCCD60BS3HDB 4PXCDD60BS3HDB NOTE OPTIONAL DOWNFLOW GASKET...

Page 2: ... coil is pressurized with 8 12 psig of dry air Do not stand directly in front of the coil connections when removing sealing plugs If no pressure is released check for leaks D FURNACE IN UPFLOW POSITION APPLICATION USES UPFLOW COIL MODELS ONLY IMPORTANT If installing the coil in the horizontal position you MUST use the horizontal kit listed below for this coil model num ber and follow the instructi...

Page 3: ...dischargeofrefrigeranttotheatmosphere 1 The following steps are to be considered when installing the refrigerant lines a Determine the most practical way to run the lines b Consider types of bends to be made and space limitations c Route the tubing making all required bends and properly secure the tubing before making final connections NOTE Refrigerant lines must be isolated from the structure and...

Page 4: ...g a strong water stream such as from a garden hose being careful to prevent fin damage Use chemical cleaners only when necessary Figure 6 Capillary tubes will come out the top of bulb when positioned correctly I CONDENSATE DRAIN PIPING Condensate drain connections are located in the drain pan at the bottom of the coil enclosure assembly The female threaded fitting protrudes outside of the enclosur...

Page 5: ...H C IN 13 5 8 13 5 8 16 5 8 16 5 8 20 1 8 16 5 8 20 1 8 23 5 8 20 1 8 23 5 8 TOP OPENING D 12 3 4 12 3 4 15 3 4 15 3 4 19 1 4 15 3 4 19 1 4 22 3 4 19 1 4 22 3 4 GAS CONNECTION 3 4 7 8 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO ADAPTER RQUIRED 14 1 2 14 1 2 17 1 2 17 1 2 21 17 1 2 21 24 1 2 21 24 1 2 DRAIN PAN PLASTIC 4PXCCD36BS3 FIGURE A 42 17 5 8 17 1 2 16 5 8 15 3 4 3 4 17 1 2 4PXCCU30BS3 FI...

Page 6: ...6 18 AD41D1 1B EN Installer s Guide From Dwg D346711 RevB ...

Page 7: ... NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is correct NO Before starting insure the blower wheel indoor and outdoor coils are clean Is the liquid line temperature at indoor coil within 8F of outdoor liquid line temperature YES Verify line set is s...

Page 8: ...lications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 2021 18 AD41D1 1B EN 27 Apr 2021 Supersedes 18 AD41D1 1A EN February 2021 ...

Reviews: