Trane 2TWR1 Installer'S Manual Download Page 2

© 2002 American Standard Inc.  All Rights Reserved

18-BC51D2-3

Installer’s Guide

ture to prevent excess roof run-off water from pouring
directly on the unit. Do not locate unit(s) close to
bedroom(s).

4. The top discharge area must be unrestricted for at least

five (5) feet above the unit.

5. When the outdoor unit is mounted on a roof, be sure the

roof will support the unit’s weight. Properly selected
isolation is recommended to prevent transmission to the
building structure.

6. The maximum length of refrigerant lines from outdoor

to indoor unit should NOT exceed sixty (60) feet.

7. If outdoor unit is mounted above the air handler, maxi-

mum lift should not exceed sixty (60) feet (suction line). If
air handler is mounted above condensing unit, maxi-
mum lift should not exceed sixty (60) feet (liquid line).

8. Locate and install indoor coil or air handler in accor-

dance with instruction included with that unit.

C. ACCUTRON™ FLOW CONTROL VALVE

If the indoor unit System Refrigerant Flow control is an
Accutron™ orifice and check valve assembly, an orifice size
change may be necessary.

The outdoor model determines the required orifice size.
Check the listed orifice size on nameplate of the selected
outdoor model. If the indoor unit is factory shipped with a
different orifice size, the orifice must be changed to obtain
system rated performance.

IMPORTANT:
The outdoor unit is shipped with the proper size orifice and a
stick-on orifice size label in an envelope attached to the
outdoor unit. Outdoor unit nameplate will have correct orifice
size specified as BAYFCCV --- A for rated performance.

D. INSTALLING REFRIGERANT LINES

CAUTION

!

If using existing refrigerant lines make certain that all joints
are brazed, not soldered.

Condensing units have provisions for braze connections.

Pressure taps are provided on the service valves of outdoor
unit for compressor suction and liquid pressures.

The indoor end of the recommended refrigerant line sets may
be straight or with a 90 degree bend, depending upon
situation requirements. This should be thoroughly checked
out before ordering refrigerant line sets.

The gas line must always be insulated.

CAUTION

!

In scroll compressor applications, dome temperatures may
be hot. Do not touch top of compressor, may cause minor to
severe burning.

The units are factory charged with the system charge re-
quired when using fifteen (15) feet of connecting line. Unit
nameplate charge is the same.

Final refrigerant charge adjustment is necessary. Use
the Charging Charts in the outdoor unit Service Facts.

1. Determine the most practical way to run the lines.

2. Consider types of bends to be made and space limitations.

NOTE:
Large diameter tubing will be very difficult to rebend once it
has been shaped.

3. Determine the best starting point for routing the refriger-

ant tubing - -INSIDE OR OUTSIDE THE STRUCTURE.

4. Provide a pull-thru hole of sufficient size to allow both

liquid and gas lines.

5. Be sure the tubing is of sufficient length.

6. Uncoil the tubing --- do not kink or dent.

7. Route the tubing making all required bends and properly

secure the tubing before making connections.

8. To prevent a noise within the building structure due to

vibration transmission from the refrigerant lines, the
following precautions should be taken:

a. When the refrigerant lines have to be fastened to floor

joists or other framing in a structure, use isolation
type hangers.

BASEPAN TAB REMOVAL

2

BRAZE TYPE INDOOR END

3

SEALING CAP

ADAPTER

FLOW CONTROL
CHECK VALVE
(F.C.C.V.) ORIFICE

FIELD SUPPLIED
LIQUID LINE

AS SHIPPED

BODY

ACCUTRON

TM

COMPONENTS

LIQUID LINE SERVICE VALVE

4

Summary of Contents for 2TWR1

Page 1: ...red sufficiently for the purchaser s purposes the matter should be referred to your installing dealer or local distributor A GENERAL The following instructions cover 2TWR1 and 2TWR2 Heat Pump Units NO...

Page 2: ...are brazed not soldered Condensing units have provisions for braze connections Pressure taps are provided on the service valves of outdoor unit for compressor suction and liquid pressures The indoor...

Page 3: ...zing It is recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body NOTE Use care to make sure that no moisture enters pressure tap port while wet rag i...

Page 4: ...e upon completion of installation See unit Service Facts F ELECTRICAL CONNECTIONS WARNING When installing or servicing this equipment ALWAYS exercise basic safety precautions to avoid the possibility...

Page 5: ...r sump heat where used Do not change the Thermostat System Switch until power has been applied for one 1 hour Following this procedure will prevent potential compressor overload trip at the initial st...

Page 6: ...4 829 32 5 8 756 29 3 4 1 1 8 3 8 137 5 3 8 86 3 3 8 210 8 1 4 79 3 1 8 508 20 2TWR1060A 4 1 841 33 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 2TWR2018A 2 2 651 25 5...

Page 7: ...18 BC51D2 3 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152637 Rev 1...

Page 8: ...ompressor O D Fan Won t Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blower Won t Start DEFROST Unit Won t Initiate...

Reviews: