Trane 2TTB3 Series Installer'S Manual Download Page 4

4

18-BC56D1-5

Installer’s Guide

6. The use of color coded low voltage wire is recommended to

simplify connections between the outdoor unit, the
thermostat and the indoor unit.

Table 1 — NEC Class II Control Wiring

24 VOLTS

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

7. Table 1 defines maximum

 total

 length of low voltage

wiring from outdoor unit, to indoor unit, and to thermostat.

8. Mount the indoor thermostat in accordance with instruc-

tion included with the thermostat.  Wire per appropriate
hook-up diagram (included in these instructions).

E. DEFROST CONTROL 

(HEAT PUMPS ONLY)

The demand defrost control measures heat pump outdoor
ambient temperature with a sensor located outside the
outdoor coil. A second sensor located on the outdoor coil is
used to measure the coil temperature. The difference between
the ambient and the colder coil temperature is the difference
or delta-T measurement. This delta-T measurement is
representative of the operating state and relative capacity of
the heat pump system. By measuring the change in delta-T,
we can determine the need for defrost. The coil sensor also
serves to sense outdoor coil temperature for termination of
the defrost cycle.

FAULT IDENTIFICATION

A fault condition is indicated by the flashing light on the
defrost control inside the heat pump control box.

In normal operation, the defrost control light will flash once
each second. If the light is flashing more than once per second
or not at all, refer to the service manual for that unit.

PIN IDENTIFICATION

 (See Figure 6.)

1. TEST_COMMON (Shorting any of the other pins to this

pin causes the function of the other pin to be executed.
Leaving this pin open results in the normal mode of
operation.)

2. TST  =  Test (Shorting TEST_COMMON to this pin

speeds up all defrost board timings.)

3. FRC_DFT  =  Forced Defrost (Short TEST_COMMON to

this pin for two (2) seconds to initiate a forced defrost.
Remove the short after defrost initiates.)

DEFROST CONTROL CHECKOUT

Normal operation requires:

a. LED on board flashing 1 time/second.

b. 24V AC between R & B

c. 24V AC between Y & B with unit operating

d. Defrost initiation when FRC_DFT pin is shorted to

TEST_COMMON pin.

If a defrost control problem is suspected, refer to the service
information in control box.

F. COMPRESSOR START UP

After all electrical wiring is complete, SET THE THERMO-
STAT SYSTEM SWITCH IN THE OFF POSITION SO
COMPRESSOR WILL NOT RUN, and apply power by closing
the system main disconnect switch. This will activate the
compressor sump heat (where used). Do not change the
Thermostat System Switch until power has been applied for
one (1) hour. Following this procedure will prevent potential
compressor overload trip at the initial start-up.

WARNING

!

Do NOT connect 24 VAC to T1 (ODS-A) terminal. ODS-A
thermistor WILL BE BLOWN.

G. OPERATIONAL AND CHECKOUT

PROCEDURES

Final phases of this installation are the unit Operational and
Checkout Procedures which are found in this instruction. To
obtain proper performance, all units must be operated and
charge adjustments made in accordance with procedures
found in the Service Facts.

H. ELECTRIC HEATERS

Electric heaters, if used, are to be installed in the air han-
dling device according to the instructions accompanying the
air handler and the heaters.

I. START CONTROL

Some models have quick start components which are factory
installed. For models that do not have factory installed start
components, provisions are made for a field installed start kit
accessory. When adding an accessory, follow the instructions
provided with the kit.

J. OUTDOOR THERMOSTAT

An outdoor thermostat TAYSTAT250B may be field installed.
For data, see wiring diagram attached to unit and instruction
sheet packaged with outdoor thermostat.

K. SEACOAST SALT SHIELD

If installed within one mile of salt water, including sea-
coasts and inland waterways, models without factory sup-
plied Seacoast Salt Shields require the addition of
BAYSEAC001 (Seacoast Kit) at installation time.

IMPORTANT:

See Limited Warranty information in Use and Care Manual.

PIN IDENTIFICATION

FRC_DFT

TEST_COMMON

TST

6

Summary of Contents for 2TTB3 Series

Page 1: ...d manufactured to withstand and operate in severe winter conditions However there are precautionary steps which should be taken at the time of installation which will help assure the efficient operation of the unit It is recommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur 1 Units should be elevated 3...

Page 2: ...f rated line set C SERVICE VALVE OPERATION BRASS LIQUID AND GAS LINE SERVICE VALVES The Brass Liquid and Gas Line Service Valves are factory shipped in the seated position to hold factory nitrogen charge The pressure tap service port when depressed opens only to the field brazing side of the valve when the valve is in the seated position The liquid line valve is not a back seating valve see WARNIN...

Page 3: ...500 microns in one 1 minute then evacuation is incomplete or system has a leak 7 If vacuum gauge does not rise above 500 microns in one 1 minute the evacuation should be complete 8 With vacuum pump and micron gauge blanked off weigh in HCFC 22 refrigerant based on the outdoor unit data plate and refrigerant line set length adjust ments noted on page 1 of the Service Facts 9 Close valve on HCFC 22 ...

Page 4: ...ost initiates DEFROST CONTROL CHECKOUT Normal operation requires a LED on board flashing 1 time second b 24V AC between R B c 24V AC between Y B with unit operating d Defrost initiation when FRC_DFT pin is shorted to TEST_COMMON pin If a defrost control problem is suspected refer to the service information in control box F COMPRESSOR START UP After all electrical wiring is complete SET THE THERMO ...

Page 5: ... O R M E R C O N T A C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E S S O R R E F R I G E R A N T U N D E R C H A R G E R E F R I G E R A N T O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N C O N D E N S A B L E S R E S T R I C T E D O D A I R F L O W O D A I R R E C I R C U L A T I O N T X V S T U C K O P E N S U P E R H E A...

Page 6: ...it nameplate 7 Locate this value in the appropriate column of the Subcooling Charging Table Locate your liquid line temperature in the left column of the table and the intersecting liquid line pressure under your nameplate subcool value column Add refrigerant to raise the pres sure to match the table or remove refrigerant to lower the pressure Again wait 20 minutes for the system conditions to sta...

Page 7: ...8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 2TWB3060A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 MODELS BASE FIG A B C D E F G H J K 2TTB3018A 2 2 651 25 5 8 724 28 1 2 651 25 5 8 5 8 1 4 127 5 57 2 1 4 181 7 1 8 44 1 3 4 457 18 2TTB3024A 2 2 832 32 3 4 724 28 1 2 651 25 5 8 3 4 5 16 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTB3030A 3 2 832 32 3 4 ...

Page 8: ...nry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance and smooth operation 7 Indoor coil drain line drains freely Pour water into drain pan 8 Supply registers and return grilles open and unobstructed 9 Return air filter installed 10 Thermostat thermometer ...

Reviews: