Trane 2TTB3 Series Installer'S Manual Download Page 2

© 2012 Trane

18-BC56D1-5

Installer’s Guide

(INFORMATION APPLICABLE TO 

ALL UNITS

)

1. When removing unit from the pallet, notice the tabs on

the basepan. Remove tabs by cutting with a sharp tool as
shown in Figure 2.

2. The unit should be set on a level support pad at least as

large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin  SSC-APG001-EN.

3. The support pad must NOT be in direct contact with any

structure.  Unit must be positioned a minimum of 12"
from any wall or surrounding shrubbery to insure
adequate airflow.  Clearance must be provided in front of
control box (access panels) & any other side requiring
service access to meet National Electrical Code.  Also,
the unit location must be far enough away from any
structure to prevent excess roof run-off water from
pouring directly on the unit. Do not locate unit(s) close
to bedroom(s).

4. The top discharge area must be unrestricted for at least

five (5) feet above the unit.

5. When the outdoor unit is mounted on a roof, be sure the

roof will support the unit’s weight.  Properly selected
isolation is recommended to prevent sound or vibration
transmission to the building structure.

6. The maximum length of refrigerant lines from outdoor to

indoor unit should NOT exceed sixty (60) feet.

7. If outdoor unit is mounted above the air handler, maxi-

mum lift should not exceed sixty (60) feet (suction line).
If air handler is mounted above condensing unit, maxi-
mum lift should not exceed sixty (60) feet (liquid line).

NOTE:
Refer to “Refrigerant Piping Software” Pub. No. 32-3312-0*
(the position of the * denotes the latest revision number).
The outdoor unit must be properly matched to the indoor
unit.  Refer to Application Bulletin # SCC-APG009-EN.

CAUTION

!

If using existing refrigerant lines make certain that all joints
are brazed, not soldered.

CAUTION

!

In scroll compressor applications, dome temperatures may
be hot. Do not touch top of compressor, may cause minor
to severe burning.

Final refrigerant charge adjustment is necessary. 

Use

the Subcooling Charging procedure  in the outdoor unit
Service Facts.

NOTE:
The refrigerant charge specified on the data plate is the
system charge plus 15 feet of rated line set.

C. SERVICE VALVE OPERATION

BRASS LIQUID AND GAS LINE SERVICE VALVES

The Brass Liquid and Gas Line Service Valves are factory
shipped in the seated position to hold factory nitrogen charge.
The pressure tap service port (when depressed) opens only to
the field brazing side of the valve when the valve is in the
seated position.  The liquid line valve is 

not 

a back seating

valve (see

 WARNING 

below).

WARNING

!

Extreme caution should be exercised when opening the
Liquid Line Service Valve. Turn valve stem counterclock-
wise only until the stem contacts the rolled edge. (See
Figure 3) No torque is required.

BRASS GAS LINE BALL SERVICE VALVE

The Brass Gas Line Ball Service Valve is shipped in the
closed position to hold the factory nitrogen charge.  The
pressure tap service port (when depressed) opens only to the
field brazing side when the valve is in the closed position. The
Gas Line Ball Service Valve is full open with a 1/4 turn.  See
Figure 4.

BRAZING REFRIGERANT LINES

1. Before brazing, remove plugs from external copper stub

tubes.  Clean internal and external surfaces of stub tubes
prior to brazing.

2. Cut and fit tubing, minimizing the use of sharp

90° bends.

3. Insulate the entire gas line and its fittings.

4. Do 

NOT

 allow uninsulated liquid line to come in direct

contact with bare gas line.

5. Precautions should be taken to avoid heat damage

to the pressure tap valve core during brazing.  It is
recommended that the pressure tap port valve
core be removed and a wet rag wrapped around
the valve body.

NOTE:
Use care to make sure that no moisture enters pressure tap
port, while wet rag is being used.

NOTE:
Precautions should be taken to avoid heat damage to
basepan during brazing.  It is recommended to keep the
flame directly off of the basepan.

6. Use a Dry Nitrogen Purge and Brazing Alloy without flux

when brazing the field line to the copper factory connec-
tion.  Flow dry nitrogen into either valve pressure tap
port, thru the tubing and out the other port while brazing.

7. Braze using accepted good brazing techniques.

LEAK CHECK

IMPORTANT:

Replace pressure tap port valve core before attaching hoses for
evacuation.

After the brazing operation of refrigerant lines to both the
outdoor and indoor unit is completed, the field brazed
connections must be checked for leaks.  Pressurize through
the service valve ports, the indoor unit and field refrigerant

BASEPAN TAB
REMOVAL

2

Summary of Contents for 2TTB3 Series

Page 1: ...d manufactured to withstand and operate in severe winter conditions However there are precautionary steps which should be taken at the time of installation which will help assure the efficient operation of the unit It is recommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur 1 Units should be elevated 3...

Page 2: ...f rated line set C SERVICE VALVE OPERATION BRASS LIQUID AND GAS LINE SERVICE VALVES The Brass Liquid and Gas Line Service Valves are factory shipped in the seated position to hold factory nitrogen charge The pressure tap service port when depressed opens only to the field brazing side of the valve when the valve is in the seated position The liquid line valve is not a back seating valve see WARNIN...

Page 3: ...500 microns in one 1 minute then evacuation is incomplete or system has a leak 7 If vacuum gauge does not rise above 500 microns in one 1 minute the evacuation should be complete 8 With vacuum pump and micron gauge blanked off weigh in HCFC 22 refrigerant based on the outdoor unit data plate and refrigerant line set length adjust ments noted on page 1 of the Service Facts 9 Close valve on HCFC 22 ...

Page 4: ...ost initiates DEFROST CONTROL CHECKOUT Normal operation requires a LED on board flashing 1 time second b 24V AC between R B c 24V AC between Y B with unit operating d Defrost initiation when FRC_DFT pin is shorted to TEST_COMMON pin If a defrost control problem is suspected refer to the service information in control box F COMPRESSOR START UP After all electrical wiring is complete SET THE THERMO ...

Page 5: ... O R M E R C O N T A C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E S S O R R E F R I G E R A N T U N D E R C H A R G E R E F R I G E R A N T O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N C O N D E N S A B L E S R E S T R I C T E D O D A I R F L O W O D A I R R E C I R C U L A T I O N T X V S T U C K O P E N S U P E R H E A...

Page 6: ...it nameplate 7 Locate this value in the appropriate column of the Subcooling Charging Table Locate your liquid line temperature in the left column of the table and the intersecting liquid line pressure under your nameplate subcool value column Add refrigerant to raise the pres sure to match the table or remove refrigerant to lower the pressure Again wait 20 minutes for the system conditions to sta...

Page 7: ...8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 2TWB3060A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 MODELS BASE FIG A B C D E F G H J K 2TTB3018A 2 2 651 25 5 8 724 28 1 2 651 25 5 8 5 8 1 4 127 5 57 2 1 4 181 7 1 8 44 1 3 4 457 18 2TTB3024A 2 2 832 32 3 4 724 28 1 2 651 25 5 8 3 4 5 16 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTB3030A 3 2 832 32 3 4 ...

Page 8: ...nry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance and smooth operation 7 Indoor coil drain line drains freely Pour water into drain pan 8 Supply registers and return grilles open and unobstructed 9 Return air filter installed 10 Thermostat thermometer ...

Reviews: