background image

4

18-AC51D3-3

Installer’s Guide

rolled edge (approximately five [5] turns) observing
WARNING statement on page 2.  See Figure 4.

10. Replace liquid service pressure tap port cap and valve

stem cap.  These caps MUST BE REPLACED to
prevent leaks.  Replace valve stem cap and pressure tap
cap finger tight, then tighten an additional 1/6 turn.

11. The gas valve can now be opened.  For a ball type gas

valve, open the gas valve by removing the shut-off valve
cap and turning the valve stem 1/4 turn counterclock-
wise, using 1/4" Open End or Adjustable wrench.  See
Figure 5. For brass gas line service valve opening, follow
9 and 10 above. See Figure 4.

12. The gas valve is now open for refrigerant flow.  Replace

valve stem cap to prevent leaks. Again, these caps
MUST BE REPLACED to prevent leaks.  Replace valve
stem cap and pressure tap cap finger tight, then tighten
an additional 1/6 turn.  See Figure 5.

If refrigerant lines are longer than 15 feet and/or a
different size than recommended, it will be necessary to
adjust system refrigerant charge upon completion of
installation. See unit Service Facts.

F. ELECTRICAL CONNECTIONS

CAUTION

!

Three phase scroll compressors will run in reverse if
powered up with improper phasing. If the compressor is
running backwards there will be little or no difference in
suction and discharge pressure and it will make a distinct
louder sound. Reversing any two of the field installed
power leads will correct the compressor rotation. Failure to
change the power leads to correct compressor rotation
may result in compressor damage during operation.

WARNING

!

When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility of
electric shock.

1. Power wiring and grounding of equipment must comply

with local codes.

2. Power supply must agree with equipment nameplate.

3. Install a separate disconnect switch at the outdoor unit.

4. Ground the outdoor unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration

transmission may create a noise problem within the
structure.

6. The use of color coded low voltage wire is recommended

to simplify connections between the outdoor unit, the
thermostat and the indoor unit.

Table 1 — NEC Class II Control Wiring

24 VOLTS

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

7. Table 1 defines maximum total length of low voltage

wiring from outdoor unit, to indoor unit, and to thermostat.

REFRIGERANT CIRCUIT

Liquid Pressure Too High

Liquid Pressure Too Low

Suction Pressure Too High

Suction Pressure Too Low

Liquid Refrig. Floodback TXV System

Liquid Refrig. Floodback Capillary Tube System

I.D. Coil Frosting

Compressor Runs Inadequate or No Cooling

ELECTRICAL

Compressor & O.D. Fan Do Not Start

Compressor Will Not Start But O.D. Fan Runs

O.D. Fan Won’t Start

Compressor Hums But Won’t Start

Compressor Cycles on IOL

I.D. Blower Won’t Start

SYSTEM FAULTS

P - Primary Causes      S - Secondary Causes

P

P

P

S

S

P

S

S

S

S

S

S

S

P

S

S

S

S

P

P

P

P

S

S

S

S

S

S

S

P

P

P

P

S

P

P

S

S

S

P

P

P

P

P

P

P

P

P

P

S

S

S

P

P

P

P

P

S

P

S

P

S

S

S

S

S

S

S

P

P

P

P

P

S

P

P

POWER SUPPLY

HIGH VOLTAGE WIRING

COMPR. IOL

RUN CAPACITOR

START CAPACITOR

START RELAY

CONTACTOR CONTACTS

LOW VOLTAGE WIRING

CONTROL TRANSFORMER

CONTACTOR COIL

LOW VOLTAGE FUSE

STUCK COMPRESSOR

INEFFICIENT COMPRESSOR

REFRIGERANT UNDERCHARGE

REFRIGERANT OVERCHARGE

EXCESSIVE EVAP. LOAD

NONCONDENSABLES

RESTRICTED O.D. AIRFLOW

O.D. AIR RECIRCULATION

TXV STUCK OPEN

SUPERHEAT

RESTRICTED I.D. AIRFLOW

REF. CIRCUIT RESTRICTIONS

O.D. FAN SPEED SWITCH

TROUBLESHOOTING CHART — WHAT TO CHECK

8. Mount the indoor thermostat in accordance with instruc-

tion included with the thermostat.  Wire per appropriate
hook-up diagram (included in these instructions).

G. COMPRESSOR START UP

After all electrical wiring is complete, SET THE THERMO-
STAT SYSTEM SWITCH IN THE OFF POSITION SO
COMPRESSOR WILL NOT RUN, and apply power by closing
the system main disconnect switch.  This will activate the
compressor sump heat (where used).  Do not change the
Thermostat System Switch until power has been applied for
one (1) hour. Following this procedure will prevent potential
compressor overload trip at the initial start-up.

H. OPERATIONAL AND CHECKOUT

PROCEDURES

Final phases of this installation are the unit Operational and
Checkout Procedures which are found in this instruction (see
page 8). To obtain proper performance, all units must be
operated and charge adjustments made in accordance with
procedures found in the Service Facts.

I. ELECTRIC HEATERS

Electric heaters, if used, are to be installed in the air han-
dling device according to the instructions accompanying the
air handler and the heaters.

J. OUTDOOR THERMOSTAT

An outdoor thermostat TAYSTAT250B may be field installed.
For data, see wiring diagram attached to unit and instruction
sheet packaged with outdoor thermostat.

K. SEACOAST SHIELD

Units installed within one mile of salt water, including
seacoasts and inland waterways, require the addition of
BAYSEAC001 (Seacoast Kit) at the time of installation.

L. TROUBLESHOOTING

Summary of Contents for 2TTA2 Series

Page 1: ...y cutting with a sharp tool as shown in Figure 2 see page 2 2 The unit should be set on a level support pad at least as large as the unit base pan such as a concrete slab If this is not the application used please refer to application bulletin Trane APB2001 02 3 The support pad must NOT be in direct contact with any structure Unit must be positioned a minimum of 12 from any wall or surrounding shr...

Page 2: ...Provide a pull thru hole of sufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficient length 6 Uncoil the tubing do not kink or dent 7 Route the tubing making all required bends and properly secure the tubing before making connections 8 To prevent a noise within the building structure due to vibration transmission from the refrigerant lines the following precautions ...

Page 3: ...coil before opening the gas and liquid line valves 2 Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps NOTE Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of HCFC 22 and vacuum pump 3 Attach center hose of manifold gauge...

Page 4: ...g Floodback TXV System Liquid Refrig Floodback Capillary Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling ELECTRICAL Compressor O D Fan Do Not Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blower Won t Start SYSTEM FAULTS P Primary Causes S Secondary Causes P P P S S P S S S S S S S P S S S S ...

Page 5: ...ow voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to W2 and W3 PRINTED FROM B152901 P02 PRINTED FROM B152908 P02 PRINTED FROM B152903 P02 NOTE W2 present only on 2 stage thermostat and furnace PRINTED FROM B152907 P03 NOTE W2 present only on 2 stage thermostat and furnace LEGEND FACTORY WIRING FIELD WIRING ...

Page 6: ... 1 4 57 2 1 4 457 18 2TTA0060A 3 1 832 32 3 4 829 32 5 8 756 29 3 4 1 1 8 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 2TTA0072A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 2TTA2030A 2 2 730 28 3 4 724 28 1 2 651 25 5 8 3 4 3 8 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTA2036A 2 2 832 32 3 4 724 28 1 2 651 25 5 8 7 8 3 8 137 5 3 8 65 2 5 8 210 ...

Page 7: ...18 AC51D3 3 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 0 ...

Page 8: ...ng 2 X X X X X 6 Inform owner on how to operate system and what to expect of it At the same time deliver Owner s Use and Care Booklet CHECKOUT PROCEDURE After installation has been completed it is recommended that the entire system be checked against the following list 1 Refrigerant Line Leak checked 2 Suction Lines and Fittings properly insulated 3 Have all Refrigerant Lines been secured and isol...

Reviews: