Trane 2TTA2 Series Installer'S Manual Download Page 3

18-AC51D3-3

3

Installer’s Guide

5. Do NOT allow uninsulated liquid line to come in direct

contact with bare gas line.

6. Precautions should be taken to avoid heat damage

to the pressure tap valve core during brazing.  It
is recommended that the pressure tap port valve
core be removed and a wet rag wrapped around
the valve body.

NOTICE:
Use care to make sure that no moisture enters pressure tap
port, while wet rag is being used.

NOTICE:
Precautions should be taken to avoid heat damage to
basepan during brazing.  It is recommended to keep the
flame directly off of the basepan.

7. Use a Dry Nitrogen Purge and Brazing Alloy without flux

when brazing the field line to the copper factory connec-
tion.  Flow dry nitrogen into either valve pressure tap
port, thru the tubing and out the other port while brazing.

8. Braze using accepted good brazing techniques.

LEAK CHECK

IMPORTANT:
Replace pressure tap port valve core before attaching hoses for
evacuation.

After the brazing operation of refrigerant lines to both the
outdoor and indoor unit is completed, the field brazed
connections must be checked for leaks.  Pressurize through
the service valve ports, the indoor unit and field refrigerant
lines with dry nitrogen to 350-400 psi.  Use soap bubbles or
other leak-checking methods to see that all field joints are
leak-free!  If not, release pressure; then repair!

SYSTEM EVACUATION

NOTE:
Since the outdoor unit has a refrigerant charge, the gas and
liquid line valves must remain closed.

1. Upon completion of leak check, evacuate the refrigerant

lines and indoor coil before opening the gas and liquid
line valves.

2. Attach appropriate hoses from manifold gauge to gas

and liquid line pressure taps.

NOTE:
Unnecessary switching of hoses can be avoided and
complete evacuation of all lines leading to sealed system
can be accomplished with manifold center hose and
connecting branch hose to a cylinder of HCFC-22 and
vacuum pump.

3. Attach center hose of manifold gauges to vacuum pump.

4. Evacuate until the micron gauge reads no higher than

350 microns.

5. Close off valve to vacuum pump and observe the micron

gauge. If gauge pressure rises above 500 microns in one (1)
minute, then evacuation is incomplete or system has a leak.

6. If vacuum gauge does not rise above 500 microns in one

(1) minute, the evacuation should be complete.

7. With vacuum pump and micron gauge blanked off, open

valve on HCFC-22 cylinder and charge refrigerant lines
and indoor coil with vapor to tank pressure of HCFC-22
supply.

NOTE:
DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE.

8. Close valve on HCFC-22  supply cylinder.  Close valves

on manifold gauge set and remove refrigerant charging
hoses from liquid and gas pressure tap ports.

NOTE:
A  3/16" Allen wrench is required to open liquid line service
valve.  A  1/4" Open End or  Adjustable wrench is required
to open gas line valve.  A 3/4" Open End wrench is required
to take off the valve stem cap.

9. The liquid line shut-off valve can now be opened.  Remove

shut-off valve cap.  Fully insert hex wrench into the stem
and backout counterclockwise until valve stem just touches

LIQUID LINE SERVICE VALVE

4

CAP

1/4 TURN ONLY
COUNTERCLOCKWISE
FOR FULL OPEN 
POSITION

VALVE STEM

GAS LINE CONNECTION

UNIT SIDE
OF VALVE

CAP

BODY

COOLING

CORE

PRESSURE TAP PORT

GAS LINE BALL SERVICE VALVE

5

GAS LINE SERVICE VALVE

Summary of Contents for 2TTA2 Series

Page 1: ...y cutting with a sharp tool as shown in Figure 2 see page 2 2 The unit should be set on a level support pad at least as large as the unit base pan such as a concrete slab If this is not the application used please refer to application bulletin Trane APB2001 02 3 The support pad must NOT be in direct contact with any structure Unit must be positioned a minimum of 12 from any wall or surrounding shr...

Page 2: ...Provide a pull thru hole of sufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficient length 6 Uncoil the tubing do not kink or dent 7 Route the tubing making all required bends and properly secure the tubing before making connections 8 To prevent a noise within the building structure due to vibration transmission from the refrigerant lines the following precautions ...

Page 3: ...coil before opening the gas and liquid line valves 2 Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps NOTE Unnecessary switching of hoses can be avoided and complete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hose to a cylinder of HCFC 22 and vacuum pump 3 Attach center hose of manifold gauge...

Page 4: ...g Floodback TXV System Liquid Refrig Floodback Capillary Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling ELECTRICAL Compressor O D Fan Do Not Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blower Won t Start SYSTEM FAULTS P Primary Causes S Secondary Causes P P P S S P S S S S S S S P S S S S ...

Page 5: ...ow voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to W2 and W3 PRINTED FROM B152901 P02 PRINTED FROM B152908 P02 PRINTED FROM B152903 P02 NOTE W2 present only on 2 stage thermostat and furnace PRINTED FROM B152907 P03 NOTE W2 present only on 2 stage thermostat and furnace LEGEND FACTORY WIRING FIELD WIRING ...

Page 6: ... 1 4 57 2 1 4 457 18 2TTA0060A 3 1 832 32 3 4 829 32 5 8 756 29 3 4 1 1 8 3 8 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 2TTA0072A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 2TTA2030A 2 2 730 28 3 4 724 28 1 2 651 25 5 8 3 4 3 8 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTA2036A 2 2 832 32 3 4 724 28 1 2 651 25 5 8 7 8 3 8 137 5 3 8 65 2 5 8 210 ...

Page 7: ...18 AC51D3 3 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 0 ...

Page 8: ...ng 2 X X X X X 6 Inform owner on how to operate system and what to expect of it At the same time deliver Owner s Use and Care Booklet CHECKOUT PROCEDURE After installation has been completed it is recommended that the entire system be checked against the following list 1 Refrigerant Line Leak checked 2 Suction Lines and Fittings properly insulated 3 Have all Refrigerant Lines been secured and isol...

Reviews: