Trane Technologies V-Traq BAYTRAQ001 Series Installation Instructions Manual Download Page 9

Installation

ACC-SVN256A-EN

6. By this point, the assembly should be structurally 

sound enough to no longer require support from the 
second technician.

7. Install the UC400 assembly, which has been pre-

mounted on DIN rail in the main control panel. Mount 
the provided control transformer, CST-T1.

8. Remove the panel on the right side that exposes the 

return air section, the panel is shown in 

Figure 12

.

9. Mount the VCM Flange in the bottom of the return air 

section using the pre-drilled screw holes and the 
provided drill screws. The VCM flange should be 
oriented as in 

Figure 13

.

10. Once the VCM flange is mounted, mount the VCM 

using the provided sheet metal screws.

11. Use the provided wire whips to wire the RTEM, 

transformer, and UC400 control module according to 
the provided wiring diagram. Follow the same wire 

routing as the factory wiring. 

Figure 13

 shows the open 

RA section.

12. Connect the provided air tubing between the Traq 

assembly and the VCM control module. Be sure to 
match the high and low connections on the Traq 
assembly with the high and low connections on the 
VCM, the high and low connections are shown in 

Figure 14

Note:

The pneumatic tubing is not shown.

13. Once the RTEM and VCM have been wired, replace the 

panel that was removed in 

Step 8

.

14. Reinstall the OA panel that was removed in 

Step 1

replacing all factory screws.

15. The screw holes should line up on the left side of the 

OA hood such that when the (3) screws are replaced, (2) 
of the screws will go through both the Traq assembly, 
and the original backside panel, with the top screw will 
not go through the Traq assembly.

The completed unit should look as it did in 

Figure 8

.

Figure 12.

Panel to remove

Figure 13.

VCM flange

Return Air 
Section Panel

VCM Flange

Figure 14.

High and low pneumatic tubing port 
locations

High

Low

Summary of Contents for V-Traq BAYTRAQ001 Series

Page 1: ...ledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the lite...

Page 2: ...us situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or proper...

Page 3: ...rvice Procedures Failure to follow all precautions in this manual and on the tags stickers and labels could result in death or serious injury Technicians in order to protect themselves from potential...

Page 4: ...allation 6 Precedent Cabinet with Low Leak Economizer BAYTRAQ001A 6 Precedent Cabinet with Low Leak Economizer BAYTRAQ002A 8 Verify System Operation 10 UC400 Application Notes 10 System Tuning Notes i...

Page 5: ...on to all Traq kits Parts List 5x Assorted wiring harnesses 1x Traq Assembly 1x Bullet sensor 1x Control relay 1x Relay base 1x DIN rail 1x UC400 controller 1x Field install wiring diagram 2x Special...

Page 6: ...f the panel and down 3 50 inch from the top edge of the panel Each hole from the top will be spread 3 50 inch between each other 4 Once the holes have been drilled shown in Figure 3 have one technicia...

Page 7: ...ing to the provided wiring diagram Follow the same wire routing as the factory wiring Figure 6 shows the open RA section 12 Connect the provided air tubing between the Traq assembly and the VCM contro...

Page 8: ...and down 4 5 inches from the top edge of the panel Each hole from the top will be spread 4 5 inches between each other 4 Once the holes have been drilled like in Figure 10 have one technician hold th...

Page 9: ...llow the same wire routing as the factory wiring Figure 13 shows the open RA section 12 Connect the provided air tubing between the Traq assembly and the VCM control module Be sure to match the high a...

Page 10: ...the response time of the calculation for the damper position this helps if thedamperisfluctuatingtooquicklyandover shooting the setpoint The Airflow Correction factor can be adjusted if the airflow ca...

Page 11: ...Outdoor Air CFM Setpoint Read Write Default Setpoint 0 cfm Range 0 20 000 cfm 2 Outdoor Air Damper Position Read 3 Outdoor Air CFM Measured Read 4 Minimum Outdoor Air CFM Position Read 5 Damper Diamet...

Page 12: ...gn and specifications without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commerc...

Reviews: