Trane Technologies V-Traq BAYTRAQ001 Series Installation Instructions Manual Download Page 8

Installation

8

 ACC-SVN256A-EN

Precedent Cabinet with Low Leak 
Economizer (BAYTRAQ002A)

The Traq airflow measurement system should be installed 
according to the following steps:

1. Remove the outdoor air hood of the unit to gain access 

to the section behind, once the panels are removed, 
the low leak economizer dampers should be visible. 

Figure 8

 highlights the screws to be removed, and the 

panels that need to be removed.

2. Once the OA panel has been removed from the end of 

the unit, the low leak damper section should be visible, 
like in 

Figure 9

. Keep the screws from the removed 

panel, along with the removed panels, they will be 
replaced later during install.

3. With the outdoor air panels removed, mark and drill 

the following holes using a 0.125-inch drill bit, using 
the top and right edges as reference points, as shown 
in 

Figure 10

. The top right hole is to be 5.75 inches left 

from the right edge of the panel, and down 4.5 inches 
from the top edge of the panel. Each hole from the top 
will be spread 4.5 inches between each other.

4. Once the holes have been drilled like in 

Figure 10

, have 

one technician hold the Traq assembly in place, while 
the other technician screws the assembly in place 
using the (2) screw holes from 

Figure 10

 and the 

provided sheet metal screws. 

Ensure the Traq assembly is installed behind the lower 
support panel as shown in 

Figure 11

. An indication that 

the panel is installed correctly is that the screw holes at 
the bottom of the assembly line up with the holes of the 
lower support panel.

5. With one technician holding the assembly, have the 

other technician secure the fixture in place by replacing 
the bottom (5) screws using the holes that were lined 
up in 

Figure 11

Note:

The pneumatic tubing is not shown.

Figure 8.

OA panel at end of unit

Figure 9.

End of unit with OA hood removed

Panels 
to Remove

Screw 
Locations

Duplicated 
on 
Opposite 
Side

Figure 10.

Dimensions of hole locations

Figure 11.

Traq assembly in place before being secured

Lined up 
Assembly 
Holes

Screws 
from 
Step 4

Lower 
Panel 
Support

Summary of Contents for V-Traq BAYTRAQ001 Series

Page 1: ...ledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the lite...

Page 2: ...us situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or proper...

Page 3: ...rvice Procedures Failure to follow all precautions in this manual and on the tags stickers and labels could result in death or serious injury Technicians in order to protect themselves from potential...

Page 4: ...allation 6 Precedent Cabinet with Low Leak Economizer BAYTRAQ001A 6 Precedent Cabinet with Low Leak Economizer BAYTRAQ002A 8 Verify System Operation 10 UC400 Application Notes 10 System Tuning Notes i...

Page 5: ...on to all Traq kits Parts List 5x Assorted wiring harnesses 1x Traq Assembly 1x Bullet sensor 1x Control relay 1x Relay base 1x DIN rail 1x UC400 controller 1x Field install wiring diagram 2x Special...

Page 6: ...f the panel and down 3 50 inch from the top edge of the panel Each hole from the top will be spread 3 50 inch between each other 4 Once the holes have been drilled shown in Figure 3 have one technicia...

Page 7: ...ing to the provided wiring diagram Follow the same wire routing as the factory wiring Figure 6 shows the open RA section 12 Connect the provided air tubing between the Traq assembly and the VCM contro...

Page 8: ...and down 4 5 inches from the top edge of the panel Each hole from the top will be spread 4 5 inches between each other 4 Once the holes have been drilled like in Figure 10 have one technician hold th...

Page 9: ...llow the same wire routing as the factory wiring Figure 13 shows the open RA section 12 Connect the provided air tubing between the Traq assembly and the VCM control module Be sure to match the high a...

Page 10: ...the response time of the calculation for the damper position this helps if thedamperisfluctuatingtooquicklyandover shooting the setpoint The Airflow Correction factor can be adjusted if the airflow ca...

Page 11: ...Outdoor Air CFM Setpoint Read Write Default Setpoint 0 cfm Range 0 20 000 cfm 2 Outdoor Air Damper Position Read 3 Outdoor Air CFM Measured Read 4 Minimum Outdoor Air CFM Position Read 5 Damper Diamet...

Page 12: ...gn and specifications without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commerc...

Reviews: