background image

18-HE58D1-5  

7

Installer’s Guide

10 Ft. min

12 in. min 

above snow line

OA

EA

FA

RA

Legend

RA - Room Air

OA - Outside Air

FA - Fresh Air

EA - Exhaust Air

Figure 12

The exhaust outlet and fresh air inlet on the outside of 

the building 

should be at least ten (10)  feet apart 

to 

avoid cross contamination.

The Outdoor fresh air inlet must be located a mini-

mum of 10 feet from any other exhaust vent, gas 

meter, outdoor grill, or source of open flame.

Fresh air inlets must also be located a minimum of 

ten (10) feet from oil tank fill tubes,  garbage cans and 

any other source of contamination.  Fresh air inlet and 

outlets should not be installed in areas of stagnant air.  

Fresh air inlet and outlet hoods should be located a 

minimum of  twelve (12) inches above the normal snow 

level.

CAUTION

!

Failure to follow installation instructions may lead to 

premature failure of the heat transfer core.  

The ERV fresh air inlet and return air grilles must not 

be located in the same room as an indoor swimming or 

exercise "lap" pool.  

Determine outlet locations. Cut correct size hole.  Cut a 

short piece of 6" round duct to connect to the fresh air in-

let and exhaust air outlet hoods.  For Model EERVR100 

or EERVR200.  Use 8" round duct for Model EERVR300.  

Secure duct to inlet and outlet hood duct collars with 

installer supplied fasteners.  Install hood and ductwork 

through penetration.  See figure 13 for sealing duct pen-

etration and duct collar.  

Fill and seal COMPLETELY

with Expanded Foam

Figure 13

DUCTWORK CONNECTING ERV TO IN-

DOOR TERMINATION POINTS

CAUTION

!

Failure to follow this installation instruction may result 

in property damage from sweating ductwork.

Insulate all connecting ductwork from the ERV to any 

indoor termination point that will be subject to forming 

condensation.  Flexible or metal duct may be used. 

An ERV can be applied either with an independent free 

standing fresh and return air duct system or the fresh 

air supply can be connected to the cooling and heating 

system return air duct. The following guidelines should 

be considered when applying and installing either duct 

system.  

FRESH AIR DUCT CONNECTION TO THE COOLING 

AND HEATING SYSTEM RETURN AIR DUCT

The Fresh Air Supply duct from the ERV should be 

connected a minimum of  three (3) feet up stream of the 

indoor unit return plenum. (See Figure 7)

A connection closer than three 3 foot may result in 

unbalanced airflow. Use a minimum of 5 foot section 

insulated flexible duct to connect the ERV port labeled 

“Fresh Air To Inside” to the return air duct.

 

FREE STANDING DUCT SYSTEM

For free standing ERV duct systems one or two fresh air 

grilles located in a central part of the house will provide 

effective distribution of the fresh air into the home par-

ticularly when the air to be exhausted from the home is 

returned from several points.  Use a minimum of 5 foot 

insulated flexible duct from the ERV port labeled “Fresh 

Air To Inside” to the point of termination.   

Summary of Contents for EERVR100A1P00B

Page 1: ...FORMATION NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE CAUTION To prevent shortening its service life the ERV should not be used during the finishing phases of construc tion Compounds used in construction and construc tion dust may cause rapid deterioration of the cabi net and internal components To avoid damage keep drywall spray construction dust etc from entering the air stream of...

Page 2: ...ations necessary for installation must comply with all applicable building health and safety code requirements ERV LOCATION CONSIDERATIONS Select a location to install the ERV with the objective of keeping the fresh air supply ducts and exhaust ducts as short as possible Short runs provide the best performance and help ensure system balance the amount of air brought into the home equals the amount...

Page 3: ...S Ac cess Door Swings Open Down The unit may be fastened directly to floor joists using the hanging bracket and integral flange Mount as described for installation on a concrete foundation wall except use appropriate fasteners for a floor joist supplied by installer Be sure the fasteners are properly selected to support the load ATTIC INSTALLATION INSTALLATION ON ROOF RAFTERS The unit may be mount...

Page 4: ...ed in a variety of positions EXCEPT as noted in Figure 6d APPROVED MOUNTING POSITIONS HINGE HINGE Figure 6a Hinges on Bottom HINGE HINGE Figure 6b Hinges on Right HINGE HINGE Figure 6c Hinges on Top NOT AN APPROVED MOUNTING POSITION HINGE HINGE Figure 6d Hinges on Left Do not install in this position as door will fall off when opened ALTERNATIVE MOUNT ING OPTION TO D RING ...

Page 5: ...an power humidifier Do not install a by pass humidifier as it can freeze based on the installation outdoor temperature and homeowner thermostat setback requirements APPROVED INSTALLATIONS I Separate Room Exhaust Air Pick Up Fresh Ex changed outside air to central system return air ERV RA Furnace Minimum 3 Furnace SA EA OA FA example from bathrooms dining area OA RA Figure 7 Legend RA Room Air OA O...

Page 6: ...llar Drive a sheet metal screw through the liner to secure the duct spiral wire to the collar Straighten insulation and slide the outer duct jacket onto the outer flange of the duct collar Secure with band or tape The outer flange of the duct collar can be used for both the inner and outer jacket of eight 8 inch flexible duct Care must be taken to insure that the duct is securely fastened and seal...

Page 7: ... figure 13 for sealing duct pen etration and duct collar Fill and seal COMPLETELY with Expanded Foam Figure 13 DUCTWORK CONNECTING ERV TO IN DOOR TERMINATION POINTS CAUTION Failure to follow this installation instruction may result in property damage from sweating ductwork Insulate all connecting ductwork from the ERV to any indoor termination point that will be subject to forming condensation Fle...

Page 8: ...s required to run this pro gram The calculator input can accept a minimum venti lation airflow requirement per local code or calculate the minimum airflow required per ASHRAE 62 2 2004 In addition to the PT control some installations may include Push Button PB or point of use control s The PB controls are typically located in bathrooms or areas where exhaust ventilation is required for short perio...

Page 9: ...gain and the unit will run 40 min utes A third press provides for 60 minutes of operation Percent Timer Control does not need to be on for the PB Control to operate the ERV unit You can cancel a cycle at anytime Just press the logo and hold for about five seconds You can start another cycle by pressing the logo NOTE FOR ERV SYSTEMS WITH MORE THAN ONE CONTROL Another control other than the push but...

Page 10: ...er to indicate percentage proper setting 14 Instruct end user on proper operation procedures and leave use and care manual with them H START UP AND OPERATION OPERATION VERIFYING UNIT PERFORMANCE 1 Airflow Airflow should be occuring in both air streams Sometimes the easiest place to confirm that air is moving is at the external wall caps If exact airflow is critical it may be desirable to permanent...

Page 11: ...he low pressure side to the Exhaust Air EA port If guage drops below zero reverse tubing connec tions Use the reading displayed on your measurement device to cross reference the CFM output using the conversion chart NOTE Be sure to replace cap into pressure port when airflow measuring is completed NOTE For best performance the airflow rate for both the Fresh Air and the Exhaust Air should be rough...

Page 12: ...policy of continuous product and product data improvement it reserves the right to change design and specifications without notice Ingersoll Rand 6200 Troup Highway Tyler TX 75711 For more information contact your local dealer distributor ...

Reviews: