background image

10 

 18-HE58D1-5

Installer’s Guide

G. START-UP AND CHECK OUT PROCEDURE 

1.   Make sure power is disconnect by unplugging electri-

cal  cord. 

2.   Check field-supplied control wiring to insure proper 

installation and that all connection are tight. 

3.   Check field-supplied power supply for proper voltage 
4.   Make sure that unit is securely mounted or sus-

pended and that there are no tools or loose debris in, 

around or on top of the unit 

5.   Check all duct connection to insure they are sealed 
6.   Check all duct outlets. All outlets must be open 
7.   Check unit filters.
8.   Close unit door – plug in unit.
9.   Turn all controls to off 
10.  Set timer to 10 %; unit should start and run for ap-

proximately six minutes. 

11.  Go to outside of building and check for airflow at in-

let and outlet hoods.  Check that weatherhood screens 

are in place and clean.  Make sure that the intake 

hood is positioned away from any exhausts or other 

sources of pollutants.  

The quality of the intro-

duced fresh air is the most important function 

of this system!

12.  If the unit has a push-button timer installed press it 

one time after the unit has cycled off from the per-

centage timer’s cycle. Unit should run twenty minutes 

and then cycle off. 

13.  Set percent timer to recommended percentage. (See 

application guide) Place peel & stick dot on the face 

of the percentage timer to indicate percentage proper 

setting. 

14.  Instruct end user on proper operation procedures and 

leave use and care manual with them. 

H. START-UP AND OPERATION

OPERATION - VERIFYING UNIT PERFORMANCE

1. Airflow

 - 

Airflow should be occuring in both air-

streams. Sometimes the easiest place to confirm 

that air is moving is at the external wall caps. 

If exact airflow is critical, it may be desirable to 

permanently install flow measuring stations and 

manometers. These can also be used to determine 

when filters should be cleaned or changed. 

2. Use Static Taps to Measure Airflow Rates

 

- See 

"Cross Core Static Drop" in MEASURING AIR-

FLOW  table on page 11. 

3. Use Damper to Balance Air Flow to Desired 

Rates, if necessary

 

- The ERV's blower motor are 

well suited for volume control by dampers on the 

inlet of the unit. One balancing damper is provided 

in the unit parts tray. 

NOTE: 

The unit is consid-

ered balanced if the difference between the two 

airflows is not more than 10 CFM.  

 

After measuring the airflow of the unit, the bal-

anced damper may be used to balance airflow if 

desired. Place the damper between the duct collar 

and the unit for the inlet of the airstream record-

ing higher flow. 

NOTE: 

Install the damper so that 

it slides from the door of the unit down to the duct 

collar.  

 

Slowly move the damper further into the duct until 

the desired airflow is recorded. Secure the damper 

in place using 1/8" tek screws (provided). 

NOTE: 

Drilling through the case while the unit is running 

may cause metal shards to be drawn into the unit.  

 

Summary of Contents for EERVR100A1P00B

Page 1: ...FORMATION NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE CAUTION To prevent shortening its service life the ERV should not be used during the finishing phases of construc tion Compounds used in construction and construc tion dust may cause rapid deterioration of the cabi net and internal components To avoid damage keep drywall spray construction dust etc from entering the air stream of...

Page 2: ...ations necessary for installation must comply with all applicable building health and safety code requirements ERV LOCATION CONSIDERATIONS Select a location to install the ERV with the objective of keeping the fresh air supply ducts and exhaust ducts as short as possible Short runs provide the best performance and help ensure system balance the amount of air brought into the home equals the amount...

Page 3: ...S Ac cess Door Swings Open Down The unit may be fastened directly to floor joists using the hanging bracket and integral flange Mount as described for installation on a concrete foundation wall except use appropriate fasteners for a floor joist supplied by installer Be sure the fasteners are properly selected to support the load ATTIC INSTALLATION INSTALLATION ON ROOF RAFTERS The unit may be mount...

Page 4: ...ed in a variety of positions EXCEPT as noted in Figure 6d APPROVED MOUNTING POSITIONS HINGE HINGE Figure 6a Hinges on Bottom HINGE HINGE Figure 6b Hinges on Right HINGE HINGE Figure 6c Hinges on Top NOT AN APPROVED MOUNTING POSITION HINGE HINGE Figure 6d Hinges on Left Do not install in this position as door will fall off when opened ALTERNATIVE MOUNT ING OPTION TO D RING ...

Page 5: ...an power humidifier Do not install a by pass humidifier as it can freeze based on the installation outdoor temperature and homeowner thermostat setback requirements APPROVED INSTALLATIONS I Separate Room Exhaust Air Pick Up Fresh Ex changed outside air to central system return air ERV RA Furnace Minimum 3 Furnace SA EA OA FA example from bathrooms dining area OA RA Figure 7 Legend RA Room Air OA O...

Page 6: ...llar Drive a sheet metal screw through the liner to secure the duct spiral wire to the collar Straighten insulation and slide the outer duct jacket onto the outer flange of the duct collar Secure with band or tape The outer flange of the duct collar can be used for both the inner and outer jacket of eight 8 inch flexible duct Care must be taken to insure that the duct is securely fastened and seal...

Page 7: ... figure 13 for sealing duct pen etration and duct collar Fill and seal COMPLETELY with Expanded Foam Figure 13 DUCTWORK CONNECTING ERV TO IN DOOR TERMINATION POINTS CAUTION Failure to follow this installation instruction may result in property damage from sweating ductwork Insulate all connecting ductwork from the ERV to any indoor termination point that will be subject to forming condensation Fle...

Page 8: ...s required to run this pro gram The calculator input can accept a minimum venti lation airflow requirement per local code or calculate the minimum airflow required per ASHRAE 62 2 2004 In addition to the PT control some installations may include Push Button PB or point of use control s The PB controls are typically located in bathrooms or areas where exhaust ventilation is required for short perio...

Page 9: ...gain and the unit will run 40 min utes A third press provides for 60 minutes of operation Percent Timer Control does not need to be on for the PB Control to operate the ERV unit You can cancel a cycle at anytime Just press the logo and hold for about five seconds You can start another cycle by pressing the logo NOTE FOR ERV SYSTEMS WITH MORE THAN ONE CONTROL Another control other than the push but...

Page 10: ...er to indicate percentage proper setting 14 Instruct end user on proper operation procedures and leave use and care manual with them H START UP AND OPERATION OPERATION VERIFYING UNIT PERFORMANCE 1 Airflow Airflow should be occuring in both air streams Sometimes the easiest place to confirm that air is moving is at the external wall caps If exact airflow is critical it may be desirable to permanent...

Page 11: ...he low pressure side to the Exhaust Air EA port If guage drops below zero reverse tubing connec tions Use the reading displayed on your measurement device to cross reference the CFM output using the conversion chart NOTE Be sure to replace cap into pressure port when airflow measuring is completed NOTE For best performance the airflow rate for both the Fresh Air and the Exhaust Air should be rough...

Page 12: ...policy of continuous product and product data improvement it reserves the right to change design and specifications without notice Ingersoll Rand 6200 Troup Highway Tyler TX 75711 For more information contact your local dealer distributor ...

Reviews: