INSTALLATION INSTRUCTIONS

Before installing the component, ensure that

• 

The cable gland is not damaged.

• 

The o-ring/gasket is not damaged and that the gas-
ket bearing areas are flat.

• 

The cable diameter is within the clamping area of the 
sealing ring.

1. 

Compression nut

2. 

Washer

3. 

Sealing Ring

4. 

Gland Body

5. 

O-ring

6. 

Lock Nut

E204 (Thread length 9/15)

Installation

1. 

Screw the gland body (4) into the enclosure with a 
wrench. When used in sheet metal enclosures, use 
a lock nut inside the enclosure. For the E205 series, 
use PTFE gasket (6) between gland body and box/
cabinet. Referring to list on the next page for correct 
tightening torque.

2. 

Place the compression nut (1) over the cable.

3. 

Place the washer (2), then sealing ring (3) over the 
cable.

4. 

Carefully cut back the outer sheet of the cable as 
shown on drawing.

5. 

Feed conductors through gland body (4). Conductors 
and outer sheath goes through the connector (4) and 
into the enclosure.

6. 

Press the sealing ring (3) and Washer (2) into gland 
body (4) by hand.

7. 

Screw the compression nut (1) into the connector (4) 
by hand.

8. 

Use a wrench to fully tighten the compression nut (1). 
Make sure the sealing ring  is tight against the cable. 
Referring to list on the next page for correct tighten-
ing torque.

9. 

Pull the cable to make sure the sealing ring tightens 
around the cable.

1. 

Compression nut

2. 

Washer

3. 

Sealing Ring

4. 

Gland Body

5. 

PTFE Gasket

6. 

Lock Nut

E205 (Thread length 15)

Summary of Contents for TEF E204-622 Ex e

Page 1: ...51 57 89 50 Office Oslo Luhrtoppen 2 N 1470 Lørenskog Norway T 47 24 08 44 10 IMPORTANT Read this instruction carefully before installing the product E204 622 E205 624 CABLE GLANDS TEF E204 622 Ex e CABLE GLAND TEF E205 624 Ex e CABLE GLAND ZONE 1 ZONE 2 SAFE AREA USER MANUAL Subject to change without prior notice TUM4302 REV F 22 10 2019 ...

Page 2: ...If the chamfer is too small the insertion of the gland may be difficult or impossible and if the chamfer is too big the O ring seal may not seal properly with the enclosure wall It is the installer s responsibility to verify that the seal after installation is sufficient for both clearance holes and threaded holes TOOLS REQUIRED Wrench according to size of cable gland MAINTENANCE INSTRUCTIONS The ...

Page 3: ...g to list on the next page for correct tightening torque 2 Place the compression nut 1 over the cable 3 Place the washer 2 then sealing ring 3 over the cable 4 Carefully cut back the outer sheet of the cable as shown on drawing 5 Feed conductors through gland body 4 Conductors and outer sheath goes through the connector 4 and into the enclosure 6 Press the sealing ring 3 and Washer 2 into gland bo...

Page 4: ...4 5 7 5 mm C1 5 C1 9 0 14 3 mm C2 5 C2 6 0 10 0 mm C3 5 C3 8 5 13 0 mm D1 8 D1 15 0 20 1 mm D2 8 D2 11 0 15 0 mm D3 10 D3 5 x 11 mm D4 10 D4 5 x 13 mm D5 10 D5 5 x 15 mm D9 8 D9 13 0 17 0 mm E1 15 E1 20 0 23 0 mm E2 15 E2 18 0 20 1 mm F1 15 F1 26 5 32 4 mm F2 15 F2 23 0 29 0 mm G1 40 G1 32 0 38 5 mm G2 40 G2 29 0 35 0 mm H1 40 H1 35 0 41 0 mm I1 50 I1 40 0 44 5 mm I2 40 I2 38 4 43 0 mm J1 70 J1 44...