TEF E204 - 622/E205 - 624 Ex e
CABLE GLAND USER MANUAL
INSTALLATION INSTRUCTIONS
Before installing the component, ensure that
•
The cable gland is not damaged.
•
The o-ring/gasket is not damaged and that the gas-
ket bearing areas are flat.
•
The cable diameter is within the clamping area of the
sealing ring.
1.
Compression nut
2.
Washer
3.
Sealing Ring
4.
Gland Body
5.
O-ring
6.
Lock Nut
E204 (Thread length 9/15)
Installation
1.
Screw the gland body (4) into the enclosure with a
wrench. When used in sheet metal enclosures, use
a lock nut inside the enclosure. For the E205 series,
use PTFE gasket (6) between gland body and box/
cabinet. Referring to list on the next page for correct
tightening torque.
2.
Place the compression nut (1) over the cable.
3.
Place the washer (2), then sealing ring (3) over the
cable.
4.
Carefully cut back the outer sheet of the cable as
shown on drawing.
5.
Feed conductors through gland body (4). Conductors
and outer sheath goes through the connector (4) and
into the enclosure.
6.
Press the sealing ring (3) and Washer (2) into gland
body (4) by hand.
7.
Screw the compression nut (1) into the connector (4)
by hand.
8.
Use a wrench to fully tighten the compression nut (1).
Make sure the sealing ring is tight against the cable.
Referring to list on the next page for correct tighten-
ing torque.
9.
Pull the cable to make sure the sealing ring tightens
around the cable.
1.
Compression nut
2.
Washer
3.
Sealing Ring
4.
Gland Body
5.
PTFE Gasket
6.
Lock Nut
E205 (Thread length 15)