Page 4
TEF 4600 CONTROL SYSTEM -
INSTALLATION AND USER MANUAL
9 DISPOSAL
Disposal
Dispose of according to company regulations and
na¬tional rules. The equipment is recycled/disposed of
as electrical equipment.
8 COMMISSIONING
After configuration, all configured features, as well as the
Fire and gas input and the overall function of the system
should be tested. SEE COMMISSIONING PROCEDURE
TTD 5909.
7.2 CONFIGURATION CIRCLE & H
7.2.1 Adjustment of the «BRIGHT» light level
The “bright” light level can be adjusted up to twice the
intensity specification of “standard” level. The purpose of
this facility is to ensure adequate performance at installa-
tions with high levels of background lighting without risk-
ing glare at less well-lit installations. To adjust light level,
replace resistor plugs in accordance with table below.
7.2.2 On site Control
Once installed and with reference to the Installation Man-
ual (TUM6332), make sure that the system functionality is
as per the Installation Manual and specifications:
•
Check the local on/off control
•
Check the local standard/bright control:
the adjustment of the “BRIGHT” light level must be
checked against the intensity of the perimeter lights
(brightest of the three). The Circle lights must not be
brighter than the perimeter lights and H lights not
brighter than the Circle lights.
•
Check that the remote control repeats the system
functionality as for the control cabinet (as relevant) by
performing the same tests.