TEF 1058-5 EASY ACCESS

  

HEAT TRACE JUNCTION BOX

INTRODUCTION

Thank you for purchasing this product!
For installation, maintenance and assurance of a long life 
of this product, please follow this manual.

MAINTENANCE / REPAIR / MODIFICATION

Maintenance according to national regulations and 
company practice.
  
Before opening the junction box make sure that the power 
is disconnected. 

Servicing the junction box is done by checking the 
intactness of the junction box, gasket and glands. If 
necessary lubricate the lid bolt threads with grease type 
Renolit Unitemp 2 from Fuchs.

If repair or overhaul is necessary, only Tranberg spare parts 
must be used. 

Modification of the JB or change of design are not 
permitted, except for installing additional glands according 
to the approval of the JB. 

While unpacking the the product, please ensure that no 
loose items are lost. Inspect the exterior of the product 
for any transport damages and/or other defects. When 
opening the junction box, remove any foreign objects 
that may have been inserted for transportation and/or 
preservation purposes. If the product is to be repacked 
and kept for storage, replace any such preservation 
component(s). 
 
Damages due to transportation is not the responsibility 
of the manufacturer. If the contents is not complete or 
the product does not work at intended, file a claim to the 
supplier or manufacturer immediately.

UNPACKING AND INSPECTIONS

SAFETY INSTRUCTION

Changes made to the product not confirming to the 
approvals of this equipment, is a safety violation. 

The manufacturer is under no circumstances responsible 
for personal injuries, death or any other damage caused 
by such activities. 

For replacement and repairs of the terminal/junction box, 
only Tranberg AS spare parts may be used. 

Repairs effecting the explosion protection of the 
equipment, may only be carried out by Tranberg AS, or 
qualified electricians in compliance with the respective 
national regulations. 

The product should be stored in the original packing 
material, in a dry location and within the operational 
temperature range. The product may have been equipped 
with plastic plugs instead of, or in addition to cable glands, 
and these should be left as they are until cable glands are 
to be installed.

STORAGE AND PRESERVATION

Summary of Contents for 1058-5

Page 1: ...7 89 00 F 47 51 57 89 50 Office Oslo Luhrtoppen 2 N 1470 Lørenskog Norway T 47 24 08 44 10 IMPORTANT Read this instruction carefully before installing the product JUNCTION BOX TYPE 1058 5 EASY ACCESS HT EIT JB PIPE WALL MOUNTED ZONE 1 ZONE 2 SAFE AREA USER MANUAL Subject to change without prior notice TUM3194 REV F 17 07 2017 ...

Page 2: ...transportation and or preservation purposes If the product is to be repacked and kept for storage replace any such preservation component s Damages due to transportation is not the responsibility of the manufacturer If the contents is not complete or the product does not work at intended file a claim to the supplier or manufacturer immediately UNPACKING AND INSPECTIONS SAFETY INSTRUCTION Changes m...

Page 3: ...his aside for better accessibility for termination 3 The keyhole solution prevents loss of screw when the terminal rail is tilted out of the box 4 Safety device 5 Standard holepattern for M25 cableglands stopping plugs drainplug and pipebend 1 Easy accessiblity for termination FEATURES AND BENEFITS OF THE EASY ACCESS JUNCTION BOX ...

Page 4: ...bility of Tranberg AS If the content is not complete file a claim to the manufacturer immediately Assembly of wall mounted type fig 01 1 Mount the Junction Box by at least 2 pcs M6 bolts placed diagonally on a wall or on proper supported rack 2 Remove dust protection or stopping plug and install re quired glands Entry holes not in use must be blinded with stopping plugs Only certified cable entrie...

Page 5: ...al care The isolation must reach up to the terminal and the conductor must not be damaged All screws and nuts of the terminals also those remaining vacant must be tightened down For earth connections to stud or bar cable shoes will have to be used Only certified cable entries and blinds may be used Gland has to be chosen according to cable diameter used To ensure the required minimum protection ca...

Page 6: ...asy Access JB Size 50 Electro Instrument Telecom Easy Access JB Size 50 Heat Trace Pipe Mounted TEF 1058 5 EASY ACCESS HEAT TRACE JUNCTION BOX 100A108925 100A105746 Easy Access JB Size 50 Heat Trace Wall Mounted 100A106166 ...

Page 7: ...EF 1058 5 EASY ACCESS HEAT TRACE JUNCTION BOX 100A108926 100A105745 Easy Access JB Size 55 Electro Instrument Telecom Easy Access JB Size 55 Heat Trace Pipe Mounted Easy Access JB Size 55 Heat Trace Wall Mounted 100A106167 ...

Page 8: ...ATEX Approval Explosion category II 2 G Ex e IIC Gb T6 Operating Temp 20 C to 60 C EPDM gasket 1058 1059 and 1060 II 2 G Ex e IIC Gb T6 Operating Temp 50 C to 100 C Silicone gasket 1058 and 1059 Certificate No Presafe 14ATEX4124 IECEx Approval Exeb IIC Certificate No PRE 14 0001 CSA Approval Canada Explosion category Ex e II Operating Temp 20 C to 60 C EPDM gasket 1058 1059 and 1060 Ex e II Operat...

Reviews: