background image

TROUBLESHOOTING

PAGE 20

SMOKES OUT FUEL DOOR WHEN OPEN (see 

)

1. The primary air control is closed.
2. The chimney is too cool. Set the primary air control

on "HIGH" with the bypass damper control "OPEN"
for a few minutes before opening the fuel door.

3. Excess creosote will not only restrict your draft but it

will create a risk of a creosote fire. Strictly adhere to
maintenance requirements as outlined in this man-
ual. If excess creosote has built up on the inside of
the firebox sides and door, burn a small hot fire at
intervals that are more frequent with air control on
HIGH for a few minutes.

4. Deposits may have built up in the chimney and are

restricting the draft, or the spark arrester on top of
the chimney may be plugged.

5. Chimney diameter too large or too small to provide

adequate draft.

6. The house is too airtight (usually takes 20 to 30 min-

utes for problem to appear as stove lowers air pres-
sure in house).  Crack a window open or provide an
outside source of air near stove.

7. Insufficient vertical height to chimney to achieve

adequate draft.

8. The combustor is plugged from engaging too soon

(remove combustor and clean, see 

Maintenance

section, pages 17-19).

DOES NOT PRODUCE ENOUGH HEAT (

)

1. Using green or insufficiently cured wood.
2. Excessive draft.
3. High ceilings (heat rises quickly, but can be recircu-

lated by a well-placed ceiling fan with a win-
ter/summer switch).

4. The area to heat, is too large (square foot (305

square mm) heating estimates are based on "aver-
age" climates and home design).

5. There is an obstruction in the chimney.
6. The chimney or chimney cap is restricted by creo-

sote preventing enough draw to sustain a "HIGH"
heat rate.

7. Combustor light off has not occurred.

DOES NOT MAINTAIN A FIRE

 

(

)

Soft wood does not burn as long or as well as seasoned
hardwood resulting in a short burn time.
1.  Wood size too small. Burns at too rapid a rate.
2.  The gasket seal on the fuel door, or glass is leaking

air. Repair or replace it if necessary.

3.  There is an obstruction in the chimney
4.  The stove was not up to normal operating tem-

perature before the bypass damper control was
pushed closed.

5. Excessive 

draft.

BACKPUFFING (

)

1. Downdraft in the chimney (may need a special

wind cap).

2. The catalytic combustor is too hot  (avoid burning

soft, pitchy woods, or large amounts of small-
diameter wood).

3 The house is too air tight (ventilation is needed).
4. Insufficient vertical height to chimney to achieve

adequate draft.

ODORS

1. Creosote accumulation in firebox (brush out on

next cleaning).

2. Chimney downdraft when stove is not operating

(close primary air control).

3. Catalytic combustor not functioning.
4.  Paint curing on first several burns.

DIRTY GLASS (

)

1. Poor draft conditions.
2. Long burn periods at low draft settings.
3. Burning wet, pitchy or spongy wood.

4. Poorly arranged logs (too close to glass).

CATALYST PLUGGING

1.  Burning materials that produce a lot of char and fly

ash. Do not burn materials such as garbage, gift
wrap, cardboard, etc.

2.  Burning wet pitchy woods or burning large loads of

small diameter wood with the combustor in the op-
eration position (without light-off taking place). Burn
proper fuel only. Do not close bypass until tem-
peratures are high enough to initiate light off.

CATALYST DEACTIVATION

1.  Burning large quantities of trash, pressure-treated

lumber or painted woods, etc. will deactivate the
catalyst. Burn proper fuels only. See 

Catalyst Re-

placement,

 page 18.

(

) Draft problems

;

 If installing into a larger flue, it

may be necessary to use a full length liner to
achieve adequate draft for the appliance. A draft
gauge should read a minimum of .05" w.c.
(inches water column) not to exceed .07" w.c.
for optimum performance (see

 Draft Require-

ments

, page 9)

.

f i r e - p a r t s . c o m

Summary of Contents for T150C

Page 1: ...THIS APPLIANCE MUST BE INSTALLED BY A QUALIFIED TECHNICIAN READ MANUAL THOROUGHLY BEFORE INSTALLATION RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE INSTALLATION AND OPERATION MANUAL Ce manuel d inst...

Page 2: ...ABLE FLUIDS SUCH AS GASOLINE NAPHTHA OR ENGINE OIL 9 Never use gasoline gasoline type lantern fuel kerosene charcoal lighter fluid or similar liq uids to start or freshen up a fire in this heater Keep...

Page 3: ...rble is used Place pad under top marble and strips under ash lip marble USING THIS MANUAL Please read and carefully follow all of the instructions found in this manual Please pay special attention to...

Page 4: ...IONS THIS APPLIANCE IS EQUIPPED WITH A THREE PRONG GROUNDING PLUG FOR YOUR PROTEC TION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY GROUNDED THREE PRONG RE CEPTACLE DO NOT CUT O...

Page 5: ...used In some cases if the k value is less or the r value higher a thinner material may be used Methods of determining floor protection equivalents To determine the thickness required for any material...

Page 6: ...A CHIMNEY SYS TEM SERVING ANOTHER STOVE APPLIANCE OR ANY AIR DISTRIBUTION DUCT FAILURE TO FOL LOW THESE INSTRUCTIONS WILL VOID THE MANUFACTURERS WARRANTY If you plan to vent your stove into an existi...

Page 7: ...nd air transfer Other appliances in the dwelling also contribute to re moving air from the dwelling i e clothes dryers exhaust fans fireplaces and other fuel burning appliances If the available fresh...

Page 8: ...ion To A Factory Built Chimney This space heater is to be connected to a factory built chimney con forming to CAN ULC S629 Standard for 650 C Fac tory Built Chimneys For Reduced Residential Clearances...

Page 9: ...on byproducts from the ap pliance If the venting system s design does not promote these ends the system may not function properly Poorly functioning venting systems may create performance problems as...

Page 10: ...INSTALLATION PAGE 10 RESIDENTIAL INSTALLATION DIAGRAM fire parts com...

Page 11: ...stening supports to chimney length do not penetrate the chimney liner the inside wall of the Solid Pak chimney The inner end of the Solid Pak chimney section shall be flush with the inside of the maso...

Page 12: ...a conventional stove The catalytic combustor is designed to make use of this en ergy converting it into useful heat as it lessens chimney creosote build up and air pollution The catalytic com bustor c...

Page 13: ...tion air located above the fuel door Slide the control to the right for a slower burn rate to the left for a higher burn rate It may take a while to get accustomed to the sensitive draft control Small...

Page 14: ...s The high firing rate will ensure that the stove the flue the catalyst and the fuel are all stabilized at proper operating temperatures If the optional temperature probe is used even though it may re...

Page 15: ...Ensure blower is turned off during start up and refueling as it will af fect the accuracy of temperature probe reading If the stove has been burning on a medium to high burn rate for approximately 20...

Page 16: ...that produces heat from a woodstove is the wood It needs to be well seasoned natural wood What does Well Seasoned mean When a tree is cut down the wood is green full of sap and moisture This moisture...

Page 17: ...d the side windows have a 1 8 3 2 mm thick lytherm gasket Should these gaskets become frayed or damaged they should be replaced with the same size and type as the original gasket Contact your dealer f...

Page 18: ...ovincial fire authority for information on how to handle a chimney fire Have a clearly understood plan for handling a chimney fire CATALYST REPLACEMENT The normal expected life of a catalyst catalytic...

Page 19: ...ed is sufficient for most users Reinstall the combustor set according to the following instructions 1 Disconnect pipe from stove flue outlet 2 Looking down into stove flue remove the bypass operating...

Page 20: ...as long or as well as seasoned hardwood resulting in a short burn time 1 Wood size too small Burns at too rapid a rate 2 The gasket seal on the fuel door or glass is leaking air Repair or replace it...

Page 21: ...required flow of combustion air to the fire chamber and for safely re moving unwanted combustion byproducts from the appli ance If the venting system s design does not promote these ends the system m...

Page 22: ...r Size 6 152 mm Approx Burn Time 8 12 hours Fuel Capacity 55 lbs 25 kg Loading Front Catalyst Standard Width 27 686 mm Depth 22 5 572 mm Height to flue 29 737 mm Height 26 5 673 mm Approx Weight With...

Page 23: ...Assembly 6 Also requires 28M09 Gasket Kit 26M78 Top Cast Stove Heat Shield Parts 29108 Shield Bottom Heat 29110 Shield Rear Heat Firebox Parts See Brick Diagram For Brick Part Number Z SC 103 Combusto...

Page 24: ...COMPONENT DIAGRAMS T150C PAGE 24 FIREBRICK 1 thick Part Qty Dimensions FB 1 9 9 x 4 Regular Top View Showing Brick Installed CATALYTIC COMBUSTOR System Components fire parts com...

Page 25: ...PK B Touch up Spray Paint Kit Black 12 oz Spray Can Blower Kit BK T15 A Blower Kit includes rheostat for variable speed control is available for increased heat circulation Blower Variable Speed Contro...

Page 26: ...SAFETY LISTING LABEL PAGE 26 fire parts com...

Page 27: ...EPA LABEL Page 27 fire parts com...

Page 28: ...RSHIP RECORDS Dealer s Name Dealer s Address City State Zip Code Serial Number Date of Purchase Date Installed Notes SERVICE AND MAINTENANCE LOG Service Service Service Date Technician Description fir...

Page 29: ...1110 West Taft Avenue Orange CA 92865 fire parts com...

Reviews: