background image

3

INSTALLATION: 

•  Product must be installed by a licensed electrician.
•  Turn off the power and isolate the mains.
•   Mark out appropriate position in the ceiling (ensure it is at a suitable height) and drill a 

40mm hole. Pull through the wiring to be connected, ensuring there are no obstructions in 
the ceiling space. 

•  Remove the transparent plastic cover that is covering the terminals.
•   Loosening the screws in the terminal, connect the Active to the L terminal, Neutral to the N 

terminal and Power to the switched load into the A terminal and tighten all screws.  See the 
detail in Figure 1.

•  Replace the transparent plastic terminal cover into the original position and secure.
•   To assemble into the ceiling, fold the metal springs of the sensor upwards until they are in 

the position shown in step 3 of Figure 1. Then position carefully into the hole in the ceiling, 
ease the sensor up gradually and the springs will release and pull the sensor into place.

•   After installation, the sensor can be connected to power and you can commence testing and 

adjusting the settings by removing the front cover to adjust the small pot knobs.

FIGURE 1:

 
 
 

TEST:

•   Turn the TIME knob anti-clockwise to the minimum, turn the LUX knob anti-clockwise to the 

maximum ‘+’ (day/bright light)

•   Turn on the power, the sensor will switch on and warm-up, 30 sec later, the unit will be 

entered into the functioning AUTO state.

•   5-10 seconds after the light goes out for the first time, the unit will start sensing, the load 

connected should switch on if triggered.

Reviews: