MD1064 Rev. F
19 of 32
6
Operation
6.1
Passive 4-20mA Current Loop
The passive 4-20mA current loop always represents the system level independent of build-
up on the vessel walls. This is the same value that is presented as the primary variable on
the HART 7 interface.
The passive 4-20mA current loop output is required to be connected to an active 4-20mA
input that provides power for the current loop.
6.2
HART 7
HART 7 communication is available over the 4-20mA loop. To communicate with the
Optimus™ control module you require either a HART 7 active DCS or a HART modem an
d
PC with the Tracerco ToolBox software.
The following sections provide the basic HART information required to obtain status
information from the device. For a complete description of the HART implementation
please refer to Tracerco document TD1071 T221 HART Field Device Specification.
6.2.1
Device Variables
The Optimus™ controls module supports 151 Device Variables. The table below provides
a summary.
Note: Channels are numbered from the bottom up. Also, GM tube counters within each
channel are numbered from the bottom up.
Number
Name
Classification
Unit Codes
0
Process Level
Analytical (81)
Percent (57)
1
Maximum Build Up
Length (69)
cm (48)
2
Elevation of Maximum Build Up
Analytical (81)
Percent (57)
3
Average Gas Phase Build Up
Length (69)
cm (48)
4
Average Total Build Up
Length (69)
cm (48)
5
Process Level by Traditional
Calculation
Analytical (81)
Percent (57)
6
Radiation Source Strength
Analytical (81)
Percent (57)
7-78
Normalised Stage Count Rates (Up
to 72)
Not Classified (0)
None (251)
79-150
Build Up per Stage (Up to 72)
Length (69)
cm (48)
Table 5. Device variables.
6.2.1.1
Device Variable 0
–
Process Level
This Device Variable has a fixed mapping to the Primary Variable. It represents the process
level and is resistant to: