6.3.3.4 Averaging
With this parameter the output position value can be averaged and the output jitter can thus be
minimized.
Lower limit
0
Upper limit
32
Default
0
0, 1: No averaging
2:
averaging of 2 values
…
32: averaging of 32 values
6.3.3.5 Parameter initialization control
Alternatively, this parameter can also be set during operation via acyclic parameter access to the
parameter control
PNU 65005
bits 0-1, see page 137.
Selection
Value Description
Default
PRM Data Block
0
Measuring system is initialized during start-up with the
parameters from the parameter data block of the measuring
system. The settings are made in accordance with chapter
"Configurable module parameters" on page 117.
X
RAM data
1
Measuring system is initialized during start-up with the
parameters from the non-volatile RAM area of the measuring
system.
6.3.3.6 Parameter write protection
Alternatively, this parameter can also be set during operation via acyclic parameter access to the
parameter control
PNU 65005
bits 2-4, see page 137.
Selection
Value Description
Default
Writable
0
Write access to all parameters, which can be configured via
acyclic parameter exchange (PNU 9xx, 6x xxx).
PNU 65005 remains read-only, however.
X
Write-protected
1
Parameters PNU 9xx, 6x xxx are read-only.