6.3.4.4 Parameter control (PNU 65005)
Via the parameter control, the initialization of parameters in the start-up phase can be defined and
write protection settings can be made for the parameters
•
PNU 6xxxx and PNU 9xx (encoder-specific and PROFIdrive-specific)
•
PNU 65005 (parameter control) and PNU 971 (save)
•
PNU 972 (RESET, activation)
also see chapter 6.3.2 on page 116.
PNU
65005
Meaning
Parameter control
Data type
Unsigned16
Access
read/write
Activation
PNU 972
Save
PNU 971
Bits
Definition
0-1
Parameter initialization control
, see chap. 6.3.3.5 on page 120
0: PRM Data Block
1: RAM data
2-4
Parameter write protection
, see chap. 6.3.3.6 on page 120
0: writable
1: write-protected
5
Write protection for PNU 65005 and PNU 971
, see chap. 6.3.3.7 on
0: writable
1: write-protected
6
Write protection for PNU 972
, see chap. 6.3.3.8 on page 121
0: writable
1: write-protected
7 - 16
reserved