Page 24
3. Locate the fuse holders, and pull out the black fuse carrier of the
blown fuse.
4. Replace the blown fuse with a 250V 1 Amp, M205 type. M205 fuses
are 20 x 5 mm.
5. Push the fuse carrier with the new fuse back into place.
ALWAYS REPLACE THE FUSE WITH A 1 AMP, 240V FUSE.
USING A FUSE WITH HIGHER CURRENT RATING MAY
DAMAGE YOUR CONTROLLER, VOIDING THE
WARRANTY.
Before switching the
pro
CHEM
-S
back to
Automatic Control
mode,
ensure that the cause of the blown fuse has been eliminated.
If the current drain of the device connected to the relay output is greater
than 1 Amp, an external contactor should be used. Please consult an
electrical contractor or TPS for details.