3. INSTALLATION CAUTIONS
Must observe the following when installing air curtains:
3.1 Please install the unit on a sturdy
supporting structure to avoid shaking and
ensure its security (because the unit running
may cause the wall to become loose or
shake and make noise).
3.2 Please install the unit inside the room.
3
.3 Don’t install the unit too low, no less than
2.5 meters from the ground.
ATTENTION
:
INSTALLER DE SORTE
QUELES PIECES INFERIEURES SOIENT
A AU MOINS 2.5 METRES AU-DESSUS
DU PLANCHER OU DU SOL.
3.4 When the entrance is wider than the
unit, it is recommended to install two or
more units in parallel. In this case, provide
20-40mm gaps between the units.
3
.5 Don’t allow gaps between the unit and
the wall.
3.6
Don’t install the unit at a place where it
is splashed by water, exposed to excessive
steam, explosive gas or corrosive gas.