Jog Frequency
Range:
0 to 200 Hz
Default Setting:
10
This parameter sets the Output Frequency of the drive in Jog mode and can be adjusted in steps of 10 Hz. If wired
to digital input 3 or 4 and enabled in parameter 3-2 or 3-3, the drive output can momentarily run the motor,
accelerating and decelerating as per parameters 1-1 and 1-2. The Jog command is disabled if the motor is running
and will only function from STOP mode.
Digital Parameters
DIC is the common feed of -24VDC supplied by an internal power supply.
3-0
Source of Operation Command
Range:
0: Operation determined by digital keypad, 1: Operation determined by external control terminals,
keypad STOP is enabled, 2: Operation determined by external control terminals, keypad STOP is disabled.
Default Setting:
0
This parameter enables external switches or buttons to control start, stop, reverse or jog commands. Refer to 3-1
through 3-3
3-1
Digital Inputs 1 and 2 (DI1 & DI2)
DI-1 & DI-2 are used together
Range:
0: DI1 - FWD/STOP, DI2 – REV/STOP. 1: DI1 - RUN/STOP, DI2- FWD/REV. 2: DI1 - RUN momentary
(N.O. latching input), DI2 - FWD/REV, DI3 - STOP momentary (N.C. Latching input)
Default Setting:
0
Inputs for setting 0 and 1 are non-latching and must be maintained.
Inputs DI1 & DI3 for setting 2 are momentary, latching.
When parameter 3-1 is set to 2, DI3 becomes a NC stop input. Loss of connection to DIC puts the drive in stop mode.
Stop Method still applies.