TPA TRS67-8I-8O Documentation Download Page 9

 

ETH 1/ETH 2 

500 V AC, 50 Hz, 1 Min

 

US/UA power supply 

500 V AC, 50 Hz, 1 Min

 

UA power supply/ETH 1 

500 V AC, 50 Hz, 1 Min

 

UA power supply/ETH 2 

500 V AC, 50 Hz, 1 Min

 

UA power supply/FE 

500 V AC, 50 Hz, 1 Min

 

 

3.8

 

Mechanical test 

Vibration resistance according to EN60068-2-

6/IEC60068-2-6 

5 g 

Shock complies with EN 60068-2-27/IEC 60068-2-27 

30 g, 1 ms cycle, half-sine shock pulse 

Continuous impact according to EN60068-2-

27/IEC60068-2-27 

10 g 

 

3.9

 

EMC test 

Noise immunity test complies with EN 61000-6-2 standard 
ESD EN 61000-4-2/IEC 61000-4-2 

Standard B, 6 kV contact discharge, 8 kV air discharge 

Electromagnetic field EN 61000-4-3/IEC 61000- 

4-3 

Standard A, field strength: 10 V/m 

Electrical fast transient burst immunity EN 61000- 4-

4/IEC 61000-4-4 

Standard B, 2 kV 

Surge immunity (Surge) EN 61000-4-5/IEC 

61000-4-5 

Standard B; DC power cord: ±0.5 kV/±0.5 kV 

(symmetry/asymmetry) 

Conducted interference EN 61000-4-6/IEC 

61000-4-6 

Standard A; testing voltage 10 V 

Noise emission test according to EN 61000-6-4 
Radio interference EN 55022 

Class A 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.P.A. Srl Tecnologie e Prodotti per l’Automazione – 

Via Carducci, 221 – 20099 Sesto S. Giovanni 

Tel. +390236527550 – 

www.tpaspa.com 

 

P.I.: IT02016240968 

Summary of Contents for TRS67-8I-8O

Page 1: ...1 TRS67 8I 8O Bus Coupler EtherCAT IP67 Documentation...

Page 2: ...d damage caused by omission inaccuracy or typographical errors in this manual Product information The TRS67 8I 8O series remote IO module is a 16 channel industrial digital input and output module ind...

Page 3: ...3 Description of each port 1 3 1 Signal and power Contact definition Contact No ETH ETHERCAT PWR POWER 1 TX 24V US 2 RX GND UA 3 TX GND US 4 RX 24V UA 1 3 2 I O signal...

Page 4: ...H 1 2 unconnected ACT YE Acting flash ETH 1 2 data transmission extinguish ETH 1 2 without data transmission RDY GN Ready green Device turned on will also remain after the normal communication of the...

Page 5: ...undervoltage under 18 V Light indicator of I O signal Light Color Define State Description 2 GN RD Signal performance of PIN 2 green Signal exists in Pin2 extinguish No signal exists in Pin2 red Pin2...

Page 6: ...mage or loss please ensure that the device is well grounded 2 2 2 Shielded Cable To avoid data damage or loss use the EtherCAT cable ensure that the shielding layer of the cable is well grounded 2 2 3...

Page 7: ...Chapter three Configuration and operation instructions 3 1 ESI file TRS67 8I 8O use equipment description files ESI that comply with the EtherCAT V2 3 standard 3 2 Main parameters Housing material PC...

Page 8: ...ethod M12 T code 4 pin Input voltage 18 30 VDC Output current Max 12 A Reverse polarity protection Yes Current consumption 5 mA no load 3 6 IO connection Connection method M12 A code 5 pin Type PNP In...

Page 9: ...EN 61000 6 2 standard ESD EN 61000 4 2 IEC 61000 4 2 Standard B 6 kV contact discharge 8 kV air discharge Electromagnetic field EN 61000 4 3 IEC 61000 4 3 Standard A field strength 10 V m Electrical f...

Reviews: