– 11 –
OPERATION DETAILS
TIME DELAY SAFETY CONTROL FUNCTION - FOR PROTECTION OF COMPRESSOR
•
Compressor will not restart, in any operation modes, for 3 minutes after its stop.
•
Compressor does not stop during the first
★
1 seconds of its operation even if the room temperature reaches
to the designated temperature, except changing setting temperature.
TAN/TAG-A28IV
TAN/TAG-A32IV
1
120
180
2
40
60
3
68Hz
72Hz
4
32Hz
TAN/TAG-A53IV
120
120
92Hz
20Hz
32Hz
-1.3˚C
MAX
3
★
MAX
3
★
4
MIN
0.7˚C
0
Hz
Frequency of
Designated
compressor
temperature
Room temperature
★
4
MIN
★
★
★
★
★
COOLING MODE OPERATION
•
The compressor will stop when operational frequency reached the minimum frequency and that condition has
been kept for
★
1 seconds and the room temperature becomes 1.3
°
C lower than it was set.
•
The compressor will re-start when room temperature becomes 0.7
°
C higher than it was set.
•
The operational frequency will be set every
★
2 seconds of operation.
The operational frequency setting will be calculated based on the deviation of the room temperature and the
set temperature on one end and the deviation factor at the time of previous setting on another.