OPERATION DETAILS
TIME DELAY SAFETY CONTROL FUNCTION - FOR PROTECTION OF COMPRESSOR
•
Compressor will not restart, in any operation modes, for 3 minutes after its stop.
•
Compressor does not stop during the first 6 minutes of its operation even if the room temperature reaches to
the designated temperature, except changing setting temperature.
-1˚C
MAX
MAX
★
2
★
2
MIN
★
3
MIN
★
3
0˚C
0
Hz
Frequency of
Designated
compressor
temperature
Room temperature
TAN/ TAG-A28FWIS
TAN/ TAG-A32FWIS
★
1
40
60
★
2
56Hz
72Hz
★
3
40Hz
40Hz
COOLING MODE OPERATION
•
The compressor will stop when operational frequency reached the minimum frequency and that condition has
been kept for 6 minutes and the room temperature becomes 1
°
C
lower than it
was set.
•
The compressor will re-start when room temperature becomes 0
°
C higher than
it
was set.
•
The operational frequency will be set every
★
1 seconds of operation.
The operational frequency setting will be calculated based on the deviation of the room temperature and the
set temperature on one end and the deviation factor at the time of previous setting on another.