5056.4252155D
Figure 22: Firebox access panel.
JUNCTION BOX
FIREBOX
ACCESS PANEL
4. Lift the control box heat shield from the bottom opening to clear the location tabs and pull inwards. Lower the heat shield to clear
the top tab. Lift the heat shield and locate on the screw above the opening.
Note: The flex lines may have to be pushed down to allow the shield to be lowered enough to clear the top tab.
5. Connect 110 V. AC electrical supply to the wires installed inside the junction box (Figure 25). The fireplace is rated at 110 volts,
60Hz, 0.25A. The optional power vent kit is rated at 115 volts, 60Hz, 1.8A.
6. The electrical wires can be accessed from both inside and outside the junction box by removing one of the two small access
panels (Figure 25 and Figure 26).
7. Attach the wall switch to the framing in the desired location (40 ft is supplied with fireplace).
8. Route the wall switch control cable (supplied) as required to the wall switch (Figure 28).
9. Attach one end of the wall switch control cable to the wall control (Figure 28), and the other end to the interface board (Figure 26).
10. Insert the 4 supplied “AA” batteries into the battery pack of the wall switch (Figure 29).
11. If not already installed, install the burner using the
instructions supplied with the burner kit.
12. Turn on the gas supply and check that all connections
are tight and leak free.
13. Turn on gas and electrical supplies.
14. Move the center button on the wall control (Figure 27)
to the “ON” position. The igniter will start to spark.
After a short delay delay, the pilot will light followed
by the main burner.
Figure 23: Heat shield raised.
Figure 24: Heat shield.
Figure 25: Junction box wiring.
Transformer
Vacuum
switch
Inside access
panel
Gas
connector
Wall switch
connector
Junction box
Module
Interface board
Power vent
switch
Regulator
board
Gas valve
Figure 26: Control box.
OUTER ACCESS PANEL
15
TCWS54_D 021216-40