Town & Country Fireplaces TCVT.WSPVB Installation And Operating Instructions Manual Download Page 5

 

190907-12 

 

 

 

 

 

TCVT.WSPVB 

 

 

 

      

                           5  

 

 

 

 

Vertical (Through Roof) Venting

This kit uses either Simpson Duravent GS direct vent pipe, Secure Vent direct vent pipe or Selkirk Direct-
temp vent pipe with a 5” inner pipe and an 8” outer pipe. For part numbers see the table of venting 
components on page 8 of this manual.

Vertical installations must use the optional TCCV.PVVCA vertical adaptor box in conjunction with this kit.

 The vertical 

adaptor box can only be installed on a fl at surface. Sloped surfaces require the construction of a chase which provides the 
minimum interior, square opening of 11” x 11” for the venting and wiring to pass through. Flat roofs may require a chase 
depending on local codes and roof construction. (If in doubt check with local inspector)

All part numbers in the following section are shown in Fig. 
#5. 

1. Place the fl ashing (Part A) onto the chase and seal 
using silicone.

2. Put a bead of silicone on the underside of the vertical 
standoff (Part B) and place it on top of the fl ashing. Align 
the eight holes and secure both parts to the chase using 
eight #8 x 1 1/2” screws provided.

3. Install the drip shield (Part C) onto the top of the vertical 
standoff using a bead of silicone between the two. Do not 
screw this part in place.

4. Bring the 14-2 electrical wire (not supplied) up through 
the holes in both the fl ashing and the drip shield leaving at 
least 12” of excess wire above the drip shield.

5. IMPORTANT: Attach an appropriate length(s) of the 
vent to the power vent terminal, suffi cient to pass through 
the chase. 

NOTE: DO NOT CONNECT AN ADJUSTABLE LENGTH 
VENT PIPE TO THE TERMINAL.

6. Seal the connection of the fi rst length of pipe at the 
terminal and any other pipe to pipe joint by both screwing 
and taping the outside joint using high temperature foil 
tape.

7. Remove the junction box cover. (Part D)

8. Remove and discard the exhaust shield. (Part E)

9. Apply a bead of silicone on the bottom fl ange of the 
power vent terminal (TCVT.WSPVB)

10. Slide the vent through the drip shield and at the same 
time thread the electrical lead through the hole in the 
bottom of the terminal.

11. With the power vent terminal resting on the drip shield, 
align the eight holes in each of the vertical standoff, the 
drip shield and the power vent terminal and then screw 
them together using the eight #8 x 1/2” stainless screws 
provided.

12. Join the 14-2 wire lead to the blower wires using 
the appropriate connectors and attach the ground wire. 
Reinstall the junction box cover.

13. Install the vertical rain cap (Part F) over the power vent 
blower. ALIGN THE EXHAUST OUTLET ON THE POWER 
VENT TERMINAL WITH THE EXHAUST PORT ON THE 
VERTICAL RAIN CAP. 

14. Secure the vertical rain cap to the power vent blower 
with the remaining eight #8 x 1/2” stainless screws. 

NOTE:
THERE ARE NO PILOT HOES IN THE BASE OF THE 
POWER VENT TERMINAL. 1/8” DIAMETER PILOT 
HOLES SHOULD BE DRILLED USING THE HOLES IN 
THE VERTICAL RAIN CAP AS A GUIDE.

DO NOT SILICONE THE VERTICAL RAIN CAP TO 
THE POWER VENT TERMINAL AS IT NEEDS TO BE 
REMOVABLE FOR SERVICING.

15. Attach the vent adaptor directly to the appliance with 
three screws and seal outer pipe with aluminium tape 
provided. 

Note: The inner pipe does not need to be 

sealed.

(Fig. #4)

16. Connect the high temperature silicone tube to the 
vacuum pressure taps on the adaptor, secure with the 
hose clamp provided and route the tube through any hole 
back to control box. (Fig. #4) Tube may touch unit and 
be trimmed if required. 

Note: Ensure that there are no 

blockages in this tube, as this will cause the control to 
malfunction.

17. Run the required Simpson Duravent GS / Secure Vent 
/ Selkirk Direct-temp pipe from the adaptor to the terminal 
assembly. Assemble as per the vent pipe manufacturer’s 
instructions.

Installation: 

Summary of Contents for TCVT.WSPVB

Page 1: ... IMPORTANT THESE INSTRUCTIONS ARE TO REMAIN WITH THE APPLIANCE INSTRUCTIONS These instructions are supplementary to the Installation and Operating Instructions supplied with the fireplace and should be kept together Refer to the Installation and Operating Instructions for proper gas supply safety requirements and operating instructions Power Vent Terminal TCVT 502461 Vent Adaptor 5096 814 ...

Page 2: ...in the absence of local codes with the Natural Fuel Gas Code ANSI Z223 1 NFPA 54 or the Natural Gas and Propane Installation Code CSA B149 1 This appliance must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical code CSA C22 1 MINIMUM CLEARANCES TO COMBUSTIBLE Vertical vent pipe 1 5 in 3...

Page 3: ...regula tor I clearance to service regulator vent outlet 6 feet 1 8 m minimum J clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 12 inches 30 cm minimum K clearance to a mechanical air supply inlet 6 feet 1 8 m minimum L clearance above paved side walk or a paved driveway located on public property 7 feet 2 1 m minimum M clearance under vera...

Page 4: ...ng 5 Attach the vent adaptor directly to the appliance with three screws and seal outer pipe with aluminium tape provided Note The inner pipe does not need to be sealed Fig 4 6 Connect the high temperature silicone tube to the vacuum pressure taps on the adaptor secure with the hose clamp provided and route the tube through any hole back to control box Fig 4 Tube may touch unit and be trimmed if r...

Page 5: ...foil tape 7 Remove the junction box cover Part D 8 Remove and discard the exhaust shield Part E 9 Apply a bead of silicone on the bottom flange of the power vent terminal TCVT WSPVB 10 Slide the vent through the drip shield and at the same time thread the electrical lead through the hole in the bottom of the terminal 11 With the power vent terminal resting on the drip shield align the eight holes ...

Page 6: ...T 8074 Part C Drip Shield Part B Vertical Standoff Part A Flashing Site Fabricated Chase MUST ALIGN 8 x 1 2 S S 16 Required 8 x 1 1 2 S S 8 REQUIRED NOTE Holes to secure rain cap are not predrilled SILICONE ALL CONNECTING FACES 14 2 Wire w Ground Final Installation Height 21 6 TCVT WSPVB 190907 12 Fig 5 Vertical Through Roof Venting ...

Page 7: ...of the module and in the orange wire running from the module to the socket on the valve labelled pilot Fig 11 and 12 4 Using the wires provided connect the 120V hot supply wire to one of the black wires from the control module Then connect the hot wire from the power vent blower to the other black wire on the control module Fig 13 ACCESS PANEL Fig 10 SPADE CONNECTORS IN BLACK WIRE LOOP Fig 13 Fig ...

Page 8: ...alve The use of a sheet metal screw will damage the valve 7 Attach the silicone tube from the upper pressure tapping to the low side of the pressure switch and secure using the hose clamp provided Fig 15 8 Attach the silicone tube from the lower pressure tapping to the high side of the pressure switch and secure using the hose clamp provided Fig 16 9 Continuewithinstallationandreassemble all of th...

Page 9: ... 1 4 Female Connector 1 4 Female Connector Optional Power Vent Kit provided by Town Country Communication Wires 1 4 Female Connector 1 4 Male Connector 120 Volt Common wire White 120 Volt Hot wire Black Low volt relay Inside the module 1 4 Female Connector 1 4 Male Connector Pull connectors apart to connect to optional power vent 190907 12 TCVT WSPVB 9 Wiring Diagram 115V 60 Hz 1 8A ...

Page 10: ...AK 4 28 DRIP SHIELD 1 10 SCREW 8 32 x1 1 4 RND HD 4 29 9072 7 PRESSURE SWITCH CLIP 1 11 8 32 x5 16 PAN QUADREX 1 30 VENT COLLAR 1 12 HEX NUT STAINLESS 18 8 PLAIN 4 31 VENT EXHAUST ASSEMBLY 1 13 1 4 20 x1 2 NC GR 5 HEX C S PLTD 5 32 VERTICAL RAIN CAP TCVT 1 14 5096 814 VENTING ADAPTER 1 33 VERTICAL STANDOFF 1 15 1 4 LDF PAPER 1 34 TCVT 5062512 BLOWER WIRING 1 16 35 TCVT 506271C PRESSURE SWITCH WIRI...

Page 11: ...1202 48 Pipe Length 1211 11 to 14 5 8 Pipe Adjustable 1217 4 10 Pipe Adjustable 1245 45 Elbow 1290 90 Elbow 1240 Round Ceiling Support Wall Thimble Cover 1241 Cathedral Ceiling Support Box 1242 Wall Firestop 1247 Wall Thimble 1263 Ceiling Firestop 1288 Wall Strap SECURE VENT COMPONENTS Number Description SV5L6 6 Pipe Length SV5L12 12 Pipe Length SV5L24 24 Pipe Length SV5L36 36 Pipe Length SV5L48 4...

Page 12: ...TECHNICAL SUPPORT 1 877 715 2664 www townandcountryfireplaces net 2975 Allenby Rd Duncan BC V9L 6V8 Printed in Canada ...

Reviews: