4
TCVT.WSPVB
190907-12
1. Locate the power vent termination following the clearance
to combustible table, venting confi guration diagram (Fig. #1 &
1a), and terminal location diagram (Fig. #2).
2. Cut and frame an 11” x 11” opening. The centre of
the square hole should line up with the centre line of the
horizontal pipe.
3. Install the Simpson Duravent (or equivalent) Wall thimble,
part number 1247 (not supplied with kit) in the opening
to retain any insulation in the wall and maintain proper
clearances. If the wall being penetrated is constructed of
noncombustible material only (i.e.. Masonry block or concrete)
the wall thimble is not required and a hole with zero clearance
is acceptable. (8” hole)
4. Attach the terminal to the outside wall. Ensure that the
terminal is the right way up and that only the outer fl anges that
are used to secure the terminal to the building are covered by
the exterior wall or siding. (Fig.#3)
Note: No other part of the
terminal can be recessed into the exterior wall or siding.
5. Attach the vent adaptor directly to the appliance with three
screws and seal outer pipe with aluminium tape provided.
Note: The inner pipe does not need to be sealed.
(Fig. #4)
6. Connect the high temperature silicone tube to the vacuum
pressure taps on the adaptor, secure with the hose clamp
provided and route the tube through any hole back to control
box. (Fig. #4) Tube may touch unit and be trimmed if required.
Note: Ensure that there are no blockages in this tube, as
this will cause the control to malfunction.
7. Run the required Simpson Duravent GS / Secure Vent
/ Selkirk Direct-temp pipe from the adaptor to the terminal
assembly. Assemble as per the vent pipe manufacturer’s
instructions.
Horizontal (Side wall) Venting
This kit uses either Simpson Duravent GS direct vent pipe, Secure Vent direct vent pipe or Selkirk Direct-temp
vent pipe with a 5” inner pipe and an 8” outer pipe. For part numbers see the table of venting components on
page 8 of this manual.
Fig.#4
Fig.#3
Blower
Outlet
Finished
Wall
Power Vent
Terminal
UPPER
PRESSURE
TAP
Power Vent Adaptor. Part # 5096.814
MUST BE INSTALLED AT THE UNIT
Secure with three screws and seal
with foil tape
Seal not required
LOWER
PRESSURE
TAP