TOTALINE Gold P274-1100 Installation And Operating Instructions Manual Download Page 15

15

Error Codes — 

 If an error is present, the thermostat will 

display an error code. See Table 5.

Smart Recovery (Heating Mode Only) — 

The th-

ermostat has 2 programmed schedule modes, Normal Occu-
pied mode and Setback mode (a time when the space is unoc-
cupied). The Smart Recovery function begins 1.5 hours before 
the scheduled Occupied mode and gradually adjusts room tem-
perature so the temperature is at the Occupied mode set point 
when the occupied time period begins.

The Smart Recovery Function operates any time the next 

programmed heating set point is more than 2 degrees above 
the current heating set point.

Smart Recovery will not occur if Hold is active. Smart Re-

covery will also be cancelled if the heating set point or time of 
day are changed.

TROUBLESHOOTING

For Troubleshooting and Error Code information, refer to 

 

Table 5.

Table 5 — Error Codes and Troubleshooting

N

OTE: Unoccupied Override may be entered by shorting the remote room sensor for 3 to 10 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROBLEM

SOLUTION

“--” on temperature display

Temperature sensor reading out of range. Check sensor for damage. If recessing 
power does not clear display, thermostat should be replaced.

“E2” on temperature display

Brownout condition or too low of voltage to thermostat. Double check wiring and 
check for 24 vac between R and C. E2 will clear 15 seconds after proper voltage is 
restored.

“E3” on temperature display

Outdoor temperature reading out of range and needed for Option No. 8. Check out-
door temperature sensor and its wiring.

“Clean Filter” on temperature display

After the selected number of hours of blower operation, the CLEAN FILTER indica-
tor will display. This is to remind the homeowner to check the filter. Press the Reset 
Filter button to clear display and reset timer to 0.

Cooling will not come on

Select COOL mode. Decrease the cooling setpoint to 10 degrees below room tem-
perature. Simultaneously press the Up Arrow and Fan buttons together (increase 
temperature). Check for 24 vac at Y/Y2 terminal. If present, the thermostat is OK 
and the problem is with equipment or wiring. If not present, replace the thermostat.

Heating will not come on

Select HEAT mode. Increase the heating setpoint to 10 degrees above room tem-
perature. Simultaneously press the Up Arrow and Fan buttons together (increase 
temperature). Check for 24 vac at Y/Y2 (with HP) or W/W1 (with AC) terminal. If 
present, the thermostat is OK and the problem is with equipment or wiring. If not 
present, replace the thermostat.

Summary of Contents for Gold P274-1100

Page 1: ...evere personal injury or death WARNING signifies a haz ard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage GENERAL Totaline 7 day programmablethermostatsarewall mount ed low voltage thermostats which maintain room temperature by controlling the operation of an HVAC heating ventilation and air...

Page 2: ...default ON Normal recovery HP AC SELECT SWITCH C Active on 1200 and 1300 Models Only Use Switch C to select between AC and HP installations The 1200 and 1300 models have an extra relay to control the HP reversing valve When a 1200 model thermostat is placed in AC mode this extra relay is converted to a second stage heat output This allows thermostat control of 2 stage fur naces or 2 stage strip he...

Page 3: ... pump HS Intelligent heat staging with a variable speed fan coil and 1 speed heat pump Table 1 Model No and Proper Wiring for Intended Applications LEGEND Terminals S2 and C are internally connected Do not ground shield to terminal C of thermostat Be careful not to drill into wiring in the wall Electrical shock could result Improper wiring or installation may cause damage to the thermostat Check t...

Page 4: ...W2 Y1 W2 R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y C MODEL 1100 THERMOSTAT TWO STAGE OR VARIABLE SPEED FURNACE SINGLE SPEED AIR CONDITIONER W W1 Y Y2 HUM W2 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF See Notes 1 and 6 on page 9 24 VAC HOT FAN COOL STAGE 1 HEAT STAGE 1 N A N A R G W W1 Y Y2 O W2 Y1 W2 R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y C MODE...

Page 5: ... Y Y2 O W2 B S1 S2 MODEL 1100 THERMOSTAT SPLICE BOX GRN WHT BRN WHT BRN C Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION HEATER CONTROL BOX RED YEL SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF See Notes 1 9 and 10 on page 9 24 VAC HOT FAN HEAT STAGE 1 COOL STAGE 1 HEAT STAGE 2 N A R G W W1 Y Y2 O W2 Y1 W2 R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y C MODEL 1200 THERMOS...

Page 6: ... N A R G R G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C C MODEL 1200 THERMOSTAT EASY SELECT TERMINAL BOARD J1 JUMPER REMOVE J2 JUMPER FOR HEAT STAGING SINGLE SPEED AIR CONDITIONER DH O Y1 Y Y2 Y Y Y2 O W2 Y1 W2 W W1 W1 W2 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF ON OFF See Notes 2 and 7 on page 9 COOL STAGE 1 FAN HEAT STAGE 1 N A HEAT STAGE 2 24 VAC HOT R G W W1 Y1 W2 O W2 B S1 ...

Page 7: ...MOSTAT SPLICE BOX YEL ORN BRN C O W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION WHT GRN RED COOL HEAT STAGE 1 HEAT STAGE 2 RVS COOLING N A FAN 24 VAC HOT SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF See Notes 3 9 and 10 on page 9 COOL STAGE 1 FAN HEAT STAGE 1 COOL STAGE 2 N A 24 VAC HOT R W W1 Y Y2 O W2 Y1 W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C MODEL 1300 ...

Page 8: ...A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y Y2 C W2 MODEL 1300 THERMOSTAT SINGLE STAGE FURNACE TWO SPEED HEAT PUMP R Y1 O R W3 G W SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF See Notes 3 8 and 9 on page 9 COOL HEAT STAGE 1 RVS COOLING HEAT STAGE 3 COOL HEAT STAGE 2 FAN 24 VAC HOT R W W1 Y Y2 O W2 Y1 W2 G 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 C Y2 C W2 MODEL 1300 THERMOSTAT...

Page 9: ...at operation via furnace control algorithm Refer to indoor equipment installation instructions for proper setup 7 Refer to fan coil installation instructions for proper wiring 8 Select the ZONE position on the 2 speed heat pump control board 9 Refer to outdoor equipment installation instructions for proper setup 10 Program thermostat to bring on fan G with any heat W selec tion See Step 5 Set Ther...

Page 10: ...gu ration value larger on the left of the thermostat display will flash Change the configuration value with the Up and Down Arrow buttons Press the Set Time Temp button again to save the configuration and change a different configuration Record all chosen configuration options on page 16 Press the End but ton to exit Configuration mode The thermostat will automati cally exit Configuration mode if ...

Page 11: ...K RED RED RED BLK BLK SENSOR 8 SENSOR 9 SENSOR 5 RED BLK SENSOR 6 SENSOR 7 BLK RED LEGEND TB Terminal Block Factory Wiring Field Wiring TB S1 S2 TO THERMOSTAT RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SPACE TEMPERATURE AVERAGING 9 SENSOR APPLICATION ...

Page 12: ...just the offset or until the thermostat temperature matches room temperature ENABLE AUTO MODE Option No 15 The enable au to mode selection allows the installer to enable or disable AUTO mode automatic changeover between heat and cool When disabled AUTO indicator does not appear when succes sive presses of the Mode button are used to move between OFF HEAT COOL and E HEAT in heat pump systems Factor...

Page 13: ...to 4 time periods WAKE DAY EVE SLEEP Each time period has a start time heating set point and cooling set point Fill in the schedule table on page 16 as an aid to programming the daily schedules PROGRAMMING MODE To program the daily schedules perform the following procedure 1 Enter Programming mode by pressing the Program button The PROGRAMMING indicator will appear on the thermostat display The cu...

Page 14: ...the Fan and Up Ar row buttons together increase temperature Fifteen Minute Cycle Timer This timer prevents the start of a heating or cooling cycle until at least 15 minutes after the last start of the same cycle Its function is to assure that equipment is not cycled more than 4 times per hour This timer is defeated for 1 cycle when the desired temperature is manual ly changed It can also be defeat...

Page 15: ...at should be replaced E2 on temperature display Brownout condition or too low of voltage to thermostat Double check wiring and check for 24 vac between R and C E2 will clear 15 seconds after proper voltage is restored E3 on temperature display Outdoor temperature reading out of range and needed for Option No 8 Check out door temperature sensor and its wiring Clean Filter on temperature display Aft...

Page 16: ...t Recovery OFF enable ON disable Switch C Heat Pump Operation OFF enable ON disable Switch D Intelligent Heat Staging OFF disable ON enable 01 Anticipator Adjustment 1 9 factory default 3 02 Clean Filter Timer Adjustment OF or 1 9 factory default 2 03 Farenheit or Celsius Operation F or C factory default F 04 Enable Fan G On with Any Heat W OF or On factory default OF 05 07 N A 08 Auxiliary Heat L...

Reviews: