35
Max. switching current:
0,5 ADC/ 0,35 AAC
Nominal load (ohmic load):
50 V / 100 mA
Lifetime:
electrical
1x10
7
at nominal load
1x10
9
at 5V with 100mA
Supply:
SELV or PELV circuit
Interfaces:
RS232 interface:
Format (factory setting):
9600 bauds, 1 start bit, 8 data bits, 1 stop bit, no parity
Baud rates:
9600 bits/s
19200 bits/s
38400 bits/s
57600 bits/s
115200 bits/s
RxD input voltage:
±30 V
RxD input resistance:
3…7 k
TxD output voltage:
±5 V with 3 k
load
TxD output resistance:
300
Supply:
SELV or PELV circuit
USB interface:
Format:
USB 1.1 and 2.0
Converter from USB to RS232 interface
RS232 format (factory
setting):
9600 bauds, 1 start bit, 8 data bits, 1 stop bit, no parity
RS232 baud rates:
9600 bits/s
19200 bits/s
38400 bits/s
57600 bits/s
115200 bits/s
USB input voltage:
-0,5…+3,8 V
Supply:
SELV or PELV circuit
Controller:
FDTI Chip FT232RL
website: http://www.ftdichip.com
Connection interface:
USB 2.0 Typ B
EMC (CE):
Interfer. immunity: IEC 61000-6-2
Interfer. emission: IEC 61000-6-3
The PIREG-D2 complies with the limits of the interference emis-
sion only with the addition of a mains filter (compulsory).
Connections:
Plug-in screw terminals
Clamping range 0.2...2.5 mm² (AWG 24...12), tightening torque 0.5...0.6 Nm
Material: polyamide, not reinforced, flammability class UL94 V0
Connecting cable:
Rigit or Flexible
Mains cable:
cross-section 0,2…4 mm² (AWG 24…10)
Control cable:
cross-section 0,2…2,5 mm² (AWG 24…12)
minimum temperature rating 70 °C
Type:
Encapsulated in isolating case
Housing:
Switchboard housing according to IEC 61554/Din 43700, Material: Noryl fiber reinforced PPE/PS,
flammability class UL94 V0 (no fire protection housing)
Protection class:
Protection class II
Pollution class:
2
(*: not part of the acceptance according to UL 61010)
Protection type:
IP20
Mounting:
Mounted switchboard, cut-out 138 x 68 mm
Dimensions (W x H x D):
144 x 72 x 169 mm
Installation:
Minimum distance to adjacent devices and cabling on all sides at least 20 mm
Weight:
970 g
Shock resistance:
10 g
Altitude:
max. 2000 m
Humidity:
Maximum relative humidity 80% at temperatures up to +31°C, decreasing linearly up to 50% relative
humidity at +40°C.
Operating temperature:
5…50 °C
Storage temperature:
-10…70 °C
UL file:
E509199
8.2. Current transformer
Type:
PIREG-CT-50
Max. nom. input current:
500 A
Through hole
(Primary circuit)
Supply:
Secondary circuit provides by the mains voltage (see above, Overvoltage category III).
The sealing transformer must be configured according to EN 61558 (VDE 0570) resp.
UL 5085
(isolating transformer with reinforced isolation) and UL 61010.
Measurement Category:
CAT II
Max. operation voltage:
160 V
(Voltage between primary and secondary circuit at non isolated though hole conductor.)
Mains frequency:
50 - 60 Hz
Max. nom. output voltage:
2,5 V
Terminal 1 and 2
(Secondary circuit)
Max. nom. output current
500 mA
Maximum load resistor:
5 Ω
Transformation ratio:
1 : 1000
Connections:
Plug-in screw terminals
Clamping range 0.2...2.5 mm² (AWG 24...12), tightening torque 0.5...0.6 Nm
Material: polyamide, not reinforced, flammability class UL94 V0
Connecting cable:
Rigit or Flexible
cross-section 0,2…2,5 mm² (AWG 24…12)
Type:
Encapsulated in isolating case
Housing:
Material: polyamide fibre-reinforced, PA-F: sealing compound: polyurethane, flammability class UL94 V0
Mounting plate:
Material: polyamide, PA, flammability class UL94 V0
Pollution class:
2
Protection type:
IP20*
(*: not part of the acceptance according to UL 61010)
Mounting:
fast mounting on 35-mm mounting rails, in accordance with EN 60715 (EN 50022)
Dimensions (W x H x D):
70 x 42,5 x 103,5 mm
Weight:
180 g
Shock resistance:
10 g
Altitude:
max. 2000 m
Humidity:
Maximum relative humidity 80% at temperatures up to +31°C, decreasing linearly up to 50% relative
humidity at +40°C.
Operating temperature:
0…50 °C
Storage temperature:
-10…70 °C
UL file:
E509199
8.3. Sealing transformer
The sealing transformer must be configured according to EN 61558 (VDE 0570) resp. UL 5085
(isolating transformer with reinforced isolation). The sealing transformer must not be applied with
reduced induction.