DC Inverter U-match Series Floor Ceiling Type Unit
4
3.2 Selection of the Installation Location
WARNING!
The unit must be installed where strong enough to withstand the weight of the unit and fixed securely,
otherwise the unit would topple or fall off.
CAUTION!
① .
Do not install where there is a danger of combustible gas leakage.
② .
Do not install the unit near heat source, steam, or flammable gas.
③ .
Children under 10 years old must be supervised not to operate the unit.
Decide the installation location with the customer as follows:
3.2.1
Indoor Unit
(1). Install the unit at a place where is strong enough to withstand the weight of the unit.
(2).
The air inlet and outlet of the unit should never be clogged so that the airflow can reach
every corner of the room.
(3). Leave service space around the unit as required in Fig.2.
◆
Floor type
Unit: mm
>600
>1000
>300
>600
>1500
◆
Ceiling type
Unit: mm
>300
>600
>600
>1500
>200
>2300
Fig. 2
(4). Install the unit where the drain pipe can be easily installed.
(5). The space from the unit to the ceiling should be kept as much as possible so as for more
convenient service.
Summary of Contents for TTH09K3FI