DC Inverter U-match Series Duct Type Unit
8
shall be able to withstand the pressure of 6.0MPa (870psig). The longer the
connecting pipe, the lower the cooling and heating effect performs.
3.4 Electrical Requirement
Electric Wire Size and Fuse Capacity.
Table 3.4
Indoor Units
Power Supply
Fuse Capacity
Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
V/Ph/Hz
A
A
A
TU18HFI
208V/230V ~60Hz
5
1
15
TU24HFI
208V/230V ~60Hz
5
2
15
TU30HFI
208V/230V ~60Hz
5
2
15
TU36HFI
208V/230V ~60Hz
5
3
15
TU42HFI
208V/230V ~60Hz
5
3
15
TU48HFI
208V/230V ~60Hz
5
5
15
Table 3.5
Outdoor Units
Power Supply
Fuse Capacity
Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
V/Ph/Hz
A
A
A
TU18H3O
208V/230V ~60Hz
5
15.9
25
TU24H3O
208V/230V ~60Hz
5
23.4
40
TU30H3O
208V/230V ~60Hz
5
23.4
40
TU36H3O
208V/230V ~60Hz
5
27.7
45
TU42H3O
208V/230V ~60Hz
5
29.7
50
TU48H3O
208V/230V ~60Hz
5
36.5
60
Notes:
①
.
The fuse is located on the main board.
②
.
Install the disconnect device with a contact gap of at least 3mm (1/8inch) in all
poles nearby the units (Both indoor unit and outdoor unit).The appliance must
be positioned so that the plug is accessible.
③
.
Take 2 pieces of power cord of 0.75mm
2
(AWG18) as the communication lines
between indoor and outdoor unit, with their longest lengths of 50m (164feet).
Please select the appropriate line length as per the actual installation