82
WX9 ASD Installation and Operation Manual
Always ON Terminal Function
Program
Terminal
Input Terminals
This parameter selects the functionality of the virtual input terminal
ON
. As a
virtual terminal, the
ON
control terminal exists only in memory and is
considered to be always in its
True
(or connected to CC) state.
It is often practical to assign this terminal to a function that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
ON
terminal to one of the possible
functions that are listed in
Direct Access Number — F110
Parameter Type —
Selection List
Factory Default —
No Function is
Assigned
Changeable During Run —
No
Input Terminal 1 (F) Function
Program
Terminal
Input Terminals
This parameter selects the functionality of the
F
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
F
terminal to one of the possible
functions that are listed in
Direct Access Number — F111
Parameter Type —
Selection List
Factory Default —
F: Forward Run
Command
Changeable During Run —
No
Input Terminal 2 (R) Function
Program
Terminal
Input Terminals
This parameter selects the functionality of the
R
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
R
terminal to one of the possible
functions that are listed in
Direct Access Number — F112
Parameter Type —
Selection List
Factory Default —
R: Reverse Run
Command
Changeable During Run —
No
Input Terminal 3 (ST) Function
Program
Terminal
Input Terminals
This parameter selects the functionality of the
ST
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
ST
terminal to one of the possible
functions that are listed in
Direct Access Number — F113
Parameter Type —
Selection List
Factory Default —
ST: Standby
Changeable During Run —
No
Input Terminal 4 (RES) Function
Program
Terminal
Input Terminals
This parameter selects the functionality of the
RES
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
RES
terminal to one of the possible
functions that are listed in
Direct Access Number — F114
Parameter Type —
Selection List
Factory Default —
RES: Reset
Changeable During Run —
No