Page 92
5.5 Quadrature Bi-pulse Counter
This function counts up or down the quadrature bi-pulse (2-phase pulses whose phases are shifted 90° each other).
Counts up when phase A precedes, and counts down when phase B precedes.
1-edge count:
The current value increments or decrements at the rising or falling edge of the phase B input after the phase A input
has turned on.
2-edge Count:
The current value increments or decrements at the rising or falling edge of the phase B input after the phase A input
has turned on or off.
4-edge Count:
The current value increments or decrements at the rising or falling edges of the phase A and B inputs.
Both rising and falling edges of each phase are counted.
Consequently, 4 times count value against the pulse frequency is obtained.
When the count value reaches the comparison value 1 (or 2), the I/O interrupt program#1 (or #2) is activated (if the
interrupt enable flag for each is ON). This counter operation is enabled while the soft-gate is ON. The count value is
reset to 0 when the soft-gate is changed from ON to OFF. The count value is also reset to 0 when the reset input
comes ON. When the soft-gate is OFF, the count value can be changed by writing the data into the comparison
value 1 (or 2) register and setting the count preset flag 1 (or 2) to ON. The comparison value 1 and 2 can be changed
even when the soft-gate is ON. The count value range is 0 to 4294967295 (32-bit data).
Summary of Contents for V200 GAA242**S
Page 66: ...Page 58 V200 PLC with DIN rail slider Front View Rear View ...
Page 78: ...Page 70 Aladder Text Editor appears as shown below Now here you can create your ladder ...
Page 82: ...Page 74 CONFIGURATION Configuring V200 with OIL DS Tag Database Register Memory Allocation ...
Page 84: ...Page 76 5 Press OK Project Configuration window will pop up as shown below ...
Page 104: ...Page 96 OPERATING SYSTEMS OVERVIEW System Operating Modes Mode Selection ...
Page 124: ...Page 116 TROUBLESHOOTING Troubleshooting Procedure Self Diagnostics ...