Table 9.7 Warning-3 (Operation control)
# Item
LCD
Message
Indication
Description
1
59C
BYPASS OV
Bypass input voltage is high.
2
27C
BYPASS UV
Bypass input voltage is low.
3
95C
BYPASS ASY
Bypass input frequency error.
Table 9.8 Warning - 4 and 5 (Guidance)
# Item
LCD
Message
Indication
Description
1
49H
LOAD LIMIT
Load has exceeded prescribed level.
2
51LI
O/P OC (PEAK)
Load current peak value is high.
3
72BO
72B MIS OPE.
72B has gone off during operation.
(Including operation error)
4
26B
BATT FAULT1
Battery temperature has risen.
5
33B
BATT FAULT2 *
Battery fluid level has gone below prescribed level.
6
80B2
BATT UV (ALM)
Battery voltage is near discharged voltage.
7
76CH
BATT OC
Charging current is high.
8
47R
AC PHASE ERR
Phase ration of AC input is reserved.
9
47C
BYPASS ERR
Phase ration of bypass input is reserved.
10
48S
STARTUP ERR
Startup was not completed.
11
52CO
52C MIS OPE.
52C has gone off during opearion.
(Including operation error)
12
83F
SWITCH ERR
Changeover switch error.
*
This message is deleted in case of a sealed type NS and HHS or MSE battery.