Hose Connecting
Be sure to fix the center of the hose
to the air conditioner cabinet with the fixture band
to install
a drain trap. (Water leakage may occur without this inclination.)
REQUIREMENT
• Connect the elbow
, drain pipe
, and the socket
to the drain port of the air conditioner. Use
adhesive for vinyl chloride to connect pipes.
• Install the elbow
5 degrees downward by tightening the socket
to torque of 60 to 100 Nm to
provide an inclination for the hose for draining.
• Connect the socket
to the Drain pump unit inlet pipe with the hose
, and tighten both ends of the
hose with the hose bands
. Insert the hose
into the joint by approx. 25 mm.
• Insulate the vinyl chloride joint and the hose at the Drain pump unit connection portion with the heat
insulation for pipe
and heat insulation for elbow
.
Ensure heat insulation by taping at the insulator joint areas.
• Secure the fixture plate
to the attachment plate
with the tapping screw
.
(Be sure to install this fixture plate
as this is for ensuring an angle of 5 degrees.)
Be careful not to damage the Drain pump kit hose during handling before extending it because it
passes under the unit.
CAUTION
5˚
514
86
59
30
5˚
Outlet drain pipe
Fixture plate for
Drain pump unit
Tapping screw
Fixture plate
Heat insulation for elbow
Air conditioner
Drain pump unit
Heat insulation
for pipe
Taping
Drain hose with heat
insulation
Fixture band
Install drain hose trap
Taping
<Enlarged view of joint>
Socket
Drain pipe
Elbow
Less than 175