4
4
3
2
1
ON
Screw
Clamper
Sensors cover
Sensor P.C. board
Adjust corner cap
Dip switch [S003]
Used in [Trial operation]
Tap 1
Used by selecting [Priority/Secondary]
Tap 2
1
2
3
4
HOW TO SET THE FAN SPEED
When installing a 4-way cassette type indoor unit to high ceiling of a room, the fan motor speed
can be selected in agreement with height of the ceiling and numbers of the discharge port.
For details, refer to the Installation Manual for 4-way discharge cassette type unit.
The fan motor speed is selected by Dip switch [S003] on the sensor P.C. board inside or the
adjust corner cap (including sensors) of the ceiling panel of 4-way discharge cassette type
indoor unit.
• After selecting a fan motor speed, reassemble the ceiling panel as before.
Using a clamper, fix the cable connectors with screws.
Setup
No.
(0)
(1)
(3)
Installable ceiling height (Unit: m)
RAV-SM560UT-E
RAV-SM800UT-E
RAV-SM1120UT-E
RAV-SM1400UT-E
4-ways
3-ways
2-ways
4-ways
3-ways
2-ways
4-ways
3-ways 2-ways
2.8
3.2
3.5
3.0
3.3
3.6
3.6
3.9
4.2
3.2
3.5
3.8
3.3
3.5
3.8
3.9
4.1
4.3
3.5
3.8
—
3.6
3.8
—
4.2
4.3
—
Tap 1
Tap 2
OFF
OFF
Setting at shipment
OFF
ON
ON
OFF