16
T1000 Series UPS Installation and Operation Manual – 91074-002
7. Wiring the System
7.1 Layout - Power Module
TABLE 7-1: POWER MODULE BACK PANEL LAYOUT
No. Label
Function
1
INPUT MCCB1
208V/240VDC 30A
Main On/Off circuit breaker.
2
REMOTEYE
Cover plate for RemotEye
®
circuit card slot.
3
REM. CONTACTS
Dry contacts DB9 connector.
4
OUTPUT L6-30R
208/240VAC 25A
Output receptacle for L6-30P cord (alternate output for 208/240 only)
5
EXT. BATTERY
External Battery Module Anderson receptacle.
6
INPUT L N G
Hardwire input terminals
L
ine,
N
eutral, and
G
round. (TB1)
7
REM. STOP
Remote Stop Contacts. (TB4) (10 VDC)
8
EPO 240V
Remote Emergency Power Off (EPO) Contacts. (TB3) (240/208 VAC)
9
OUTPUT L N G
Hardwire output terminals
L
ine,
N
eutral, and
G
round. (TB2)
FIGURE 7-2: POWER MODULE -
HARDWIRED CONFIGURATION
(P/N T1P0A6000GVG,
T1P0A6000GVGR3)
FIGURE 7-3: POWER MODULE WITH
6-50P LINECORD (-L1) OPTION
(P/N T1P0A6000GVGL1,
T1P0A6000GVGR3L1)
3-Post Input Terminal Block, and
one each 3-Post Output Terminal
Block and NEMA L6-30R outlet.
Input Power Cord #10-3SO 6-50P
and two each NEMA L6-30R outlets.
FIGURE 7-1: POWER MODULE BACK PANEL LAYOUT
1
2
8
6
5
4
3
7
9
EPO 240V
REM. STOP
REMOTEYE
INPUT MCCB1
208V/240VAC 30A
USE COPPER 75
°
C MIN.
CONDUCTORS ONLY
SEE INSTRUCTION MANUAL FOR WIRING
TERMINATION AND TIGHTENING TORQUE
OUTPUT L6-30R
208/240VAC 25A
REM. STOP
EPO 240V
REM. STOP
EPO 240V
Summary of Contents for T-Series T1000
Page 2: ...b T1000 Series UPS Installation and Operation Manual 91074 002 ...
Page 25: ...15 T1000 Series UPS Installation and Operation Manual 91074 002 FIGURE 6 10 4 POST RACK FIXED ...
Page 74: ...A 8 T1000 Series UPS Installation and Operation Manual 91074 002 ...
Page 94: ...D 2 T1000 Series UPS Installation and Operation Manual 91074 002 ...
Page 112: ...I 4 T1000 Series UPS Installation and Operation Manual 91074 002 ...