Accessory parts and Parts to be procured locally

„

„

„

„

„

Accessory parts

Thank you very much for purchasing TOSHIBA Super Heat Recovery Multi  (S-HRM) Air conditioner.
Please read this manual carefully before using your Flow Selector unit.
• When installing an indoor or outdoor unit, follow the installation manual supplied with the unit.
• To connect the Flow Selector unit to an outdoor unit with pipes, a branching joint or header is required.

Choose one according to the capacity of the units.

• Nitrogen gas is filled in the selection unit.

ADOPTION OF NEW REFRIGERANT

This SUPER HRM Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the

conventional refrigerant R22 in order to prevent destruction of the ozone layer.
Be sure to use an indoor or outdoor unit in combination with the new refrigerant.

English-1

English-2

Part name

Installation Manual

Attached wire
(For power supply)

Attached wire
(For control wiring)

Heat insulating pipe

Heat insulating pipe

Heat insulating pipe

Attached pipe

Attached pipe

Attached pipe

Wire joint

Q’ty   RBM-

Y1123FE

Y1803FE

Y2803FE

1

1

1

1

1

1

1

1

1

3

3

2

1

2

2

2

1

1

1

2

2

2

Shape

Usage

(Be sure to hand over to customers.)
(For other languages that do not appear in this
Installation Manual, please refer to the enclosed CD-R.)

CD-ROM

1

1

1

 Installation Manual

For power supply from indoor unit (3-core, 6m)

For communication with indoor unit (5-core, 6m)

For heat insulating of suction gas, discharge gas,
and gas pipe connecting sections

For heat insulating of discharge gas

For heat insulating of liquid pipe connecting section

Ø9.5 - Ø6.4, connection pipe

Ø15.9 - Ø12.7, connection pipe

Ø15.9 - Ø9.5, connection pipe

For connection with certain indoor units

CONTENTS

Accessory parts and Parts to be procured locally ...........................................1

1

PRECAUTIONS FOR SAFETY ......................................................................1

2

INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER ..................2

3

SELECTION OF INSTALLATION PLACE .....................................................3

4

INSTALLATION OF FLOW SELECTOR UNIT ...............................................4

5

REFRIGERANT PIPING ................................................................................5

6

ELECTRIC WORK .........................................................................................6

1

PRECAUTIONS FOR SAFETY

• Ensure that all Local, National and International regulations are satisfied.
• Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.
• The precautions described below include the important items regarding safety.  Observe them without fail.
• After the installation work, perform a trial operation to check for any problem.

Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.

• Turn off the main power supply switch (or breaker) before the unit maintenance.
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.

  CAUTION

New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY

OZONE LAYER.

The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is

approx. 1.6 times higher than that of refrigerant R22.  Accompanied with the new refrigerant, refrigerating oil has

also been changed.  Therefore, during installation work, be sure that water, dust,  former refrigerant, or refrigerat-

ing oil does not enter the refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port

of the main unit and installation tools are charged from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A).
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does

not enter.  Moreover, do not use the existing piping because there are problems with pressure-resistance force

and impurity in it.

Summary of Contents for RBM-Y1123FE

Page 1: ...Installation Manual Flow Selector unit RBM Y1123FE RBM Y1803FE RBM Y2803FE English EH99893801 2 ...

Page 2: ...ENTS Accessory parts and Parts to be procured locally 1 1 PRECAUTIONS FOR SAFETY 1 2 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER 2 3 SELECTION OF INSTALLATION PLACE 3 4 INSTALLATION OF FLOW SELECTOR UNIT 4 5 REFRIGERANT PIPING 5 6 ELECTRIC WORK 6 1 PRECAUTIONS FOR SAFETY Ensure that all Local National and International regulations are satisfied Read this PRECAUTIONS FOR SAFETY carefully before...

Page 3: ...rminals Conform to the regulations of the local electric company when wiring the power supply Inappropriate grounding may cause electric shock Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas If a combustible gas leaks and stays around the unit a fire may occur 2 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER This air conditioner adopts the new H...

Page 4: ...fore avoid installing the unit at a place with quiet background sound as follows 1 Rooms with quiet background sound such as bedroom hospital or room in a hotel 2 Rooms which have no ceiling and a fabric does not block the residence space from the Flow Selector unit 3 Rooms which have opening port at the ceiling When installing the unit at the above places separate the unit from the indoor unit wi...

Page 5: ...talled draw the pipes to the position where they are to be connected before hanging the unit Ceiling preparation Because ceiling preparation depends on the building structure consult with the architect or interior finisher After removing the ceiling panels it is important to reinforce the ceiling frames to prevent ceiling panel vibration and to keep the ceiling horizontal Installation of hanging b...

Page 6: ...096 Gas pipe Ø9 5 Ø12 7 Ø15 9 Ø15 9 Ø22 2 Liquid pipe Ø6 4 Ø6 4 Ø9 5 Ø9 5 Ø12 7 Suction gas pipe Ø15 9 Ø15 9 Ø15 9 Ø15 9 Ø22 2 Discharge gas pipe Ø12 7 Ø12 7 Ø12 7 Ø12 7 Ø19 1 Liquid pipe Ø9 5 Ø9 5 Ø9 5 Ø9 5 Ø12 7 Material Flow Selector unit Indoor unit capacity code Indoor unit side pipe size mm Outdoor unit side pipe size mm Connectable indoor units Seamless phosphorus deoxidized copper pipe for...

Page 7: ...the outside causes water leak Flow Selector unit Heat insulating pipe Attached Binding band Local supply Heat insulator The upper slit 6 ELECTRIC WORK WARNING 1 Using the specified wires ensure to connect the wires and fix wires securely so that the external strength of the wires do not transmit to the connecting part of the terminals Incomplete connection or fixation may cause fire etc 2 Be sure ...

Page 8: ...pinched and then attach the cover RBM Y1123FE RBM Y1803FE RBM Y2803FE Cord clamp Control wiring Attached wire Control wire Attached wire Power supply CN02 Green CN01 Red Earth screw Fixing screw 4 parts Earth screw Cord clamp Attached wire Power supply CN01 Red Control P C board Control P C board Fixing screw 4 parts CN02 Green Cord clamp System wiring diagram Power supply Single phase 220 240V 50...

Page 9: ...ttached wire power supply Then check the R L and S N phases and connect the wire and the lead wires with the attached wire joints Connect the ring terminal of the attached wire power supply to the earth screw Connect the connector Black of the attached wire control wiring to CN081 on the indoor P C board Secure the two attached wires with the attached cord clamp Be careful not to apply tension to ...

Page 10: ...tor unit NOTE 1 way Air Discharge Cassette Type MMU AP SH Series wiring refer to the Under Ceiling Type page 11 1 way Air Discharge Cassette Type MMU AP YH Series Floor Standing Type MMF AP H Series R L S N DON T APPLY 220 240V FOR INTER UNIT FOR REMOTE CONTROL Indoor P C board CN081 Attached wire Power supply Cord clamp Attached wire Control wiring Earth screw for Flow Selector unit Faston connec...

Page 11: ...LECTRIC WORK 1 way Air Discharge Cassette Type MMU AP SH Series Indoor P C board R L S N DON T APPLY 220 240V FOR INTER UNIT FOR REMOTE CONTROL Attached wire Power supply Power supply Cord clamp Cord clamp CN081 Black Earth screw for Flow Selector unit Earth screw Faston connection R L S N terminal block for power supply Attached wire Control wiring Under Ceiling Type MMC AP 7H Series CN81 Black I...

Page 12: ...e front panel 3 Slightly open the lower part of the front panel and then pull the upper part of the front panel toward you to remove it from the rear plate 4 Remove the terminal cover and the clamp base 5 Insert the control wire fully into the control wired remote controller terminal block and secure it tightly with screws 6 Connect the control wire connector of the flow selector unit to the lead ...

Page 13: ...k Cord clamp R L S N DON T APPLY 220 240V FOR INTER UNIT FOR REMOTE CONTROL Indoor P C board CN081 Attached wire Control wiring Earth screw for Flow Selector unit Faston connection R L S N terminal block for power supply Attached wire Power supply Cord clamp Power supply Earth screw Air to Air Heat Exchanger with DX Coil Unit MMD VN HEXE Series 6 ELECTRIC WORK Attached wire Power supply Attached w...

Page 14: ... control wire 8 Clamp the power supply wire with the cord clamp 9 Attach the terminal cover with a screw 10 Take the control wire out of the cable slot on the rear panel so that it produces about 600 mm from the front 11 Remove the terminal cover UP 12 Remove the LED BASE 13 Insert the control wire fully into the control Wired remote controller terminal block and secure it tightly with screws 14 C...

Page 15: ...nge SET DATA to 01 by the timer buttons 4 Push SET button 5 Push TEST button Then the setup finished Incorrect example of connection When connecting the multiple indoor units to a single FS unit the indoor units which are connected with the multiple FS units are unavailable for the group control by a single remote controller For the indoor unit a remote controller cannot be individually connected ...

Page 16: ...893801 2 TOSHIBA C TOSHIBA C TOSHIBA C TOSHIBA C TOSHIBA CARRIER CORPORA ARRIER CORPORA ARRIER CORPORA ARRIER CORPORA ARRIER CORPORATION TION TION TION TION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...

Reviews: