11
English-22
English-21
High Wall Type (MMK-AP
∗∗∗
4MH Series)
For the Flow Selector unit that has power supply cord, connect a power supply cable to it as mentioned below.
1. Open the air inlet grille upward.
2. Remove the four screws securing the front panel.
3. Slightly open the lower part of the front panel then pull the upper part of the front panel toward you to
remove it from the rear plate.
4. After removing the front panel, remove the wiring cover and the cord clamp.
5. Connect and secure the power supply cable of Flow Selector unit and secure the cord clamp.
6. The control wires are included in terminal block part of the power supply.
Take out the control wires outwards through the slit of the terminal block.
7. Fasten the wiring cover surely with screws.
8. Connect the control wire taken out through the slit on the terminal block and the control wire from the Flow
Selector unit at the relay terminal section.
Earth line
Terminal
block
Cord clamp
Screw
Screw
Wiring cover
Slit of the
terminal block
Screw
Power supply cable
of Flow Selector unit
Terminal
block
Control wire from the
Flow Selector unit
Control wire
High Wall Type (MMK-AP
∗∗∗
3H Series)
Connect the power supply wire and the communication wire supplied with the flow selector unit to the indoor unit.
1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
2. Remove the four screws securing the front panel.
3. Slightly open the lower part of the front panel, and then pull the upper part of the front panel toward you to
remove it from the rear plate.
4. Remove the terminal cover and the clamp base.
5. Insert the control wire fully into the control/wired remote controller terminal block and secure it tightly with
screws.
6. Connect the control wire connector of the flow selector unit to the lead with a connector to the left of the
control/wired remote controller terminal block.
7. Clamp the control wire and the control wire of the flow selector unit with the cord clamp.
8. Install the clamp base with a screw.
9. Insert the power supply wire fully into the terminal block and secure it tightly with screws.
Tightening torque: 1.2 N•m (0.12 kgf•m). Secure the earth line with the earth screw.
10. Clamp the power supply wire with the cord clamp.
11. Insert the power supply wire faston terminal of the flow selector unit into the power supply terminal.
Secure the earth line with the earth screw.
12. Clamp the power supply wire of the flow selector unit tight with the cord clamp.
13. Attach the terminal cover, the front panel and the air inlet grille to the indoor unit.
R(L)
A
B
U
1
U
2
S(N)
Power supply
terminal block
Earth screw for
flow selector unit
Cord clamp
Power supply wire
of flow selector unit
Cord clamp
Power supply wire
Terminal block
for control / wired
remote controller wiring
Control wire
Control wire from
the flow selector
Connector
6
ELECTRIC WORK
CAUTION
Confirm that every wires are stored in the electric parts box without getting caught before attaching the
terminal cover.