background image

– 2 –

2

Components

* Do not apply an excessive force on the louver. It may cause a trouble.

3

Preparation Before Installing the Ceiling 

Panel

Position check of indoor unit

Part name

Quantity

Shape

Usage

Ceiling panel

1

Installation manual

1

1

Confirm the position of the indoor unit 
according to the Installation Manual.

2

Check whether size of the ceiling opening hole 
is in the following range or not.

580 mm × 580 mm to 594 mm × 594 mm

3

Using the installation gauge which is attached 
to the indoor unit package, determine position 
of the indoor unit against the ceiling surface. If 
the position of the indoor unit is not correct, air 
leak, water leak (dewing), or malfunction of the 
louver is caused.

• Do not put the ceiling panel downward, lean it, or 

leave it on a projection to avoid a damage on the 
surface of the ceiling panel.

• Handle with care so as not to deform the tentative 

hanging hooks attached to the rear side of the 
ceiling panel.

• Do not apply excessive force on the louver or the 

styrofoam on the air outlet while hanging it 
tentatively to the indoor unit. (It may causes a 
trouble on the louver.)

Louver

Indoor unit

Level gauge (levelness: 5 mm or less)

Hanging bolt

Hanging 

bracket

Installation gauge

(1) 2.5 - 9.5 mm

Ceiling 

board

(2

) 2

3

 - 

28

 m

m

Indoor unit

Installation gauge

(1) 2.5 - 9.5 mm

(2) 23 - 28 mm

Ceiling board

4

Installation to Indoor Unit

Removal of air intake grille

1

Loosen the fixing screw.

2

Slide the fixing bracket toward the inside.

3

Holding the air intake grille, slide the hook in 
the direction of the arrow and slowly open 
the grille.

4

Take off hook of the fall-preventive strap 
from the ceiling panel.
Remove the hinge section of the air intake 
grille from the ceiling panel while the air 
intake grille is opened.

Air intake grille

Ceiling panel

Hook

Hook of fall-preventive strap

Hook hole of ceiling 

panel

Hinge

3-English

4-English

Summary of Contents for RBC-UM21PG(W)-E

Page 1: ...Installation Manual 1 English AIR CONDITIONER Compact 4 way type Ceiling panel Model name RBC UM21PG W E Installation Manual For commercial use ...

Page 2: ...e aftereffect and require hospitalization or long term treatment as an outpatient 2 Slight injury indicates injury burns electric shock and other injuries which do not require hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Ask an authorized dealer or qualified installation profession...

Page 3: ...ndle with care so as not to deform the tentative hanging hooks attached to the rear side of the ceiling panel Do not apply excessive force on the louver or the styrofoam on the air outlet while hanging it tentatively to the indoor unit It may causes a trouble on the louver Louver Indoor unit Level gauge levelness 5 mm or less Hanging bolt Hanging bracket Installation gauge 1 2 5 9 5 mm Ceiling boa...

Page 4: ...racket Do the same for all four corners Fig 4 Panel fixed screws are attached to the indoor unit before shipment Slide the bracket after loosening the panel fixed screw so that the bracket is easy to be hooked on the screw head Tighten the panel fixed screw again after sliding the bracket There is no need to remove the panel fixed screw Fig 4 3 Confirm there are no gaps between the indoor unit and...

Page 5: ...ing connector to install the air intake grille Attach a strap to prevent falling of the air intake grille to the ceiling panel Close the air intake grille hooks Slide the fixing brackets and securely fix them with fixing screw Fig 9 1 2 Square hole 5 positions Adjust corner cap Claws 5 positions Screw Note Tightening torque 1 N m or less 4 direction free Hook of fall preventive strap Hook hole of ...

Page 6: ...EB99813701 ...

Reviews: