– 2 –
2
Components
* Do not apply an excessive force on the louver. It may cause a trouble.
3
Preparation Before Installing the Ceiling
Panel
Position check of indoor unit
Part name
Quantity
Shape
Usage
Ceiling panel
1
Installation manual
1
1
Confirm the position of the indoor unit
according to the Installation Manual.
2
Check whether size of the ceiling opening hole
is in the following range or not.
580 mm × 580 mm to 594 mm × 594 mm
3
Using the installation gauge which is attached
to the indoor unit package, determine position
of the indoor unit against the ceiling surface. If
the position of the indoor unit is not correct, air
leak, water leak (dewing), or malfunction of the
louver is caused.
• Do not put the ceiling panel downward, lean it, or
leave it on a projection to avoid a damage on the
surface of the ceiling panel.
• Handle with care so as not to deform the tentative
hanging hooks attached to the rear side of the
ceiling panel.
• Do not apply excessive force on the louver or the
styrofoam on the air outlet while hanging it
tentatively to the indoor unit. (It may causes a
trouble on the louver.)
Louver
Indoor unit
Level gauge (levelness: 5 mm or less)
Hanging bolt
Hanging
bracket
Installation gauge
(1) 2.5 - 9.5 mm
Ceiling
board
(2
) 2
3
-
28
m
m
Indoor unit
Installation gauge
(1) 2.5 - 9.5 mm
(2) 23 - 28 mm
Ceiling board
4
Installation to Indoor Unit
Removal of air intake grille
1
Loosen the fixing screw.
2
Slide the fixing bracket toward the inside.
3
Holding the air intake grille, slide the hook in
the direction of the arrow and slowly open
the grille.
4
Take off hook of the fall-preventive strap
from the ceiling panel.
Remove the hinge section of the air intake
grille from the ceiling panel while the air
intake grille is opened.
Air intake grille
Ceiling panel
Hook
Hook of fall-preventive strap
Hook hole of ceiling
panel
Hinge
3-English