Air leak
Air leak from ceiling
Generation of dust
Dewing/water leak
Adjust so that there is no clearance.
(3) Installation of ceiling panel
Be sure to change angle of the flap while the power supply is
turned on.
(Never move the flap forcibly with hands; otherwise the flap may
be broken.)
1. Hang tentatively the tentative metal (stainless) of the indoor unit to
hanging section of the ceiling panel. (Fig.2)
• The ceiling panel has the directive performances against the indoor
unit. Mount the ceiling panel with arranging the tentative hanging
position.
• When removing the ceiling panel, push the tentative hanging metal
toward outside while holding the ceiling panel.
2. Match the mounting hole of the panel with the screw hole of the indoor
unit.
3. Using the attached washer based screw, tighten 4 positions at 4 corners
of the suction port until the panel is fitted closely to the main unit. (Fig. 3)
4. Check the panel is fitted closely to the ceiling.
• In this time, check there is no clearance between the indoor unit and
the ceiling panel, and also between the ceiling panel and the ceiling
surface. (Fig.4)
(Fig. 2)
Indoor unit
No clearance
Ceiling panel
Ceiling surface
(Fig. 4)
(Fig. 3)
CAUTION
(Fig. 5)
(4) Cabling of ceiling panel
1. Open cover of the electric parts box.
2. Connect the flap motor wiring connector which
comes forth from the ceiling panel to the connector
5P (CN33: white) on the P.C. board of the indoor unit.
• Connect the connector surely because the
flap does not work if the connector is
incompletely connected.
3. Mount cover of the electric parts box in the
reverse procedure of opening of the cover.
• Check whether the wiring connector is not
pinched between the electric parts box and
the cover.
• Check whether the wiring connector is not
pinched between the indoor unit and the
ceiling panel.
Hanging
section of tentative
hook of ceiling panel
Tentative
hanging metal
Push to remove
Drain piping corner
Ceiling panel
Hanging section of
tentative hanging metal
Washer
based screw
Tentative
hanging metal
Electric parts box cover
Screws
(3 positions)
Flap motor
wiring connector
Cable clamp
CN33
• As shown in the following figure, a trouble may be
caused if the screws are incompletely tightened.
• When a clearance is found between the ceiling
surface and the ceiling panel, readjust height of the
indoor unit even if the screws have been tightened.
As shown in the figure, pass pipes so that the clamping material is
mounted inner side.
After connection, store the connector section in the electric parts box.
(Fig. 6)