11-
3. Address Setting
When determining indoor unit addresses with wiring completed without piping construction
(Manual setting by remote controller)
<Address setting procedure>
• Connect a remote controller to the indoor unit whose
address you want to set one to one.
• Turn ON the power.
1
Push
TEST
,
SET
, and
CL
on the remote controller
simultaneously for 4 seconds or more.
2
Set code
with
TEMP.
buttons.
3
Set a refrigerant line address with
TIME
buttons.
4
Push
SET
Indication on the LCD shows normal
operation.
5
Set code
!
with
TEMP.
buttons.
6
Set indoor unit addresses with
TIME
but-
tons.
7
Push
SET
Indication on the LCD shows normal
operation.
8
Set code
"
with
TEMP.
buttons.
9
Set indoor unit addresses with
TIME
buttons
as follows:
Individual=
0000
, header unit=
0001
, follower
unit=
0002
10
Push
SET
Indication on the LCD shows
normal operation.
11
Push
TEST
.
Indoor unit address setting is completed.
The operation mode returns to normal OFF.
For systems like this example, connect
a wired remote controller independently
without connecting remote controller wires,
and then set these addresses.
Refrigerant
line address ®
Indoor unit
address ®
Group
address ®
FILE NO. SVM-12042
–
85
–
O/U
I/U
O/U
I/U
I/U I/U
1
2
2
1
3
2
2
1
2
2
2
2
Wiring example of 2 refrigerant systems
(Solid line: wiring, broken line: refrigerant piping)
(Power cable only)
(Power cable only)
Refrigerant line
address
Indoor unit address
Group address
1
1
1
END
Operation procedure
1
→
2
→
3
→
4
→
5
→
6
→
7
8
→
9
→
10
→
11
END
Group address
Individual:
0000
Header unit: 0001
Follower unit: 0002
in case of group control
ON / OFF
SET
TEST
FILTER
RESET
CL
VE
SWING/FIX
VENT
UNIT LOUVER
CODE No.
UNIT No.
R.C.
No.
MODE
AN
SET DATA
SETTING
8, 5, 2
11
1
4,
7,
10
3, 6, 9
Summary of Contents for RAV-SM566KRT-A
Page 13: ...RAV SM806KRT A FILE NO SVM 12042 13 ...
Page 111: ...TOSHIBA CARRIER CORPORATION ...